Protect

Circuit protection

C60N circuit breakers

B, C and D curves
IEC 60898: 6000 A , IEC 60947-2: 10 kA
Function

b The circuit-breakers combine the following functions:


v protection of circuits against short-circuit currents
v protection of circuits against overload currents
v control
v isolation
v protection of persons against indirect contact with TN and IT neutral systems.
C60N circuit breakers are used in the tertiary and industrial sectors.

Tripping curves
24409

B curve

When the short-circuit currents are weak (generators, long cables).


b Power circuit:
v ratings: 1 to 63 A set at 30 C
v tripping curve: the magnetic trip units operate between 3 and 5 In.

C curve

Cables feeding conventional loads.


b Power circuit:
v ratings: 0.5 to 63 A set at 30 C
v tripping curve: the magnetic trip units operate between 5 and 10 In.

D curve

24591

Loads with high inrush currents (motors, transformers).


b Power circuit:
v ratings: 0.5 to 63 A set at 40 C
v tripping curve: the magnetic trip units operate between 10 and 14 In.

Technical data according to IEC 60898

b
v
v
-

Power circuit:
voltage rating (Ue): 440 V AC
breaking capacity:
according to IEC 60898, Icn ultimate breaking capacity (O-CO cycle):

Rating (A)
0.5...63
24094

Type
1P
2P, 3P, 3P+N, 4P

Voltage (V)
230/400
400

Breaking capacity Icn (A)


6000
6000

v limitation class (IEC 60898): 3.

Technical data according to IEC 60947-2


b
v
v
v
v
-

Power circuit:
voltage rating (Ue): 440 V AC
impulse voltage (Uimp): 6 kV
insulation voltage (Ui): 500 V AC
breaking capacity:
according to IEC 60947-2, Icu ultimate breaking capacity (O-CO cycle):

Rating (A)
0.5...63
24027

Type
1P

Voltage (V)
230...240
400...415
230...240
400...415

Breaking capacity Icu (kA)


10
3 (1)
2P, 3P, 3P+N, 4P
20
10
(1) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).

Generals technical data

24631

b Fast closing: allows the high inrush currents of some loads to be better held.
b Isolation with positive break indication: opening is indicated by a green strip on the
device operating handle. This indicator shows opening contacts of all the poles.
b Number of cycles (O-C): 20000.
b Environment:
v tropicalisation: treatment 2 (relative humidity: 95 % at 55 C) according to
IEC 60068-1
v weight (g):
Type

1P
120

2P
240

3P
360

4P
480

b Connection: tunnel terminals for the following cables:


v 16 mm2 flexible or 25 mm2 rigid up to 25 A ratings
v 25 mm2 flexible or 35 mm2 rigid for 32 to 63 A ratings.

version: 4.1

90078E.indd

Protect
Circuit protection

C60N circuit breakers

B, C and D curves
IEC 60898: 6000 A , IEC 60947-2: 10 kA
Catalogue numbers
Type
1P

2P

3P

3P + N

4P

90078E.indd

version: 4.1

Rating (A)

Width
in mod.
of 9 mm

Quantity
per batch

Catalogue number
B curve

C curve

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

2
2
2
2
2
2
2
2
2
2
2
2
2
2

12
12
12
12
12
12
12
12
12
12
12
12
12
12

24045
24046
24047
24048
24049
24050
24051
24052
24053
24054
24055
24056
24057

24067
24395
24396
24397
24398
24399
24401
24403
24404
24405
24406
24407
24408
24409

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

4
4
4
4
4
4
4
4
4
4
4
4
4
4

6
6
6
6
6
6
6
6
6
6
6
6
6
6

24071
24072
24073
24074
24075
24076
24077
24078
24079
24080
24081
24082
24083

24068
24331
24332
24333
24334
24335
24336
24337
24338
24339
24340
24341
24342
24343

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

6
6
6
6
6
6
6
6
6
6
6
6
6
6

4
4
4
4
4
4
4
4
4
4
4
4
4
4

24084
24085
24086
24087
24088
24089
24090
24091
24092
24093
24094
24095
24096

24069
24344
24345
24346
24347
24348
24349
24350
24351
24352
24353
24354
24355
24356

4
6
10
13
15
16
20
25
32
40
50
63

8
8
8
8
8
8
8
8
8
8
8
8

3
3
3
3
3
3
3
3
3
3
3
3

24383
24384
24386
24387
24415
24388
24389
24390
24391
24392
24393
24394

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

8
8
8
8
8
8
8
8
8
8
8
8
8
8

3
3
3
3
3
3
3
3
3
3
3
3
3
3

24097
24098
24099
24100
24101
24102
24103
24104
24105
24106
24107
24108
24109

24070
24357
24358
24359
24360
24361
24362
24363
24364
24365
24366
24367
24368
24369

Protect
Circuit protection

C60N circuit breakers

B, C and D curves
IEC 60898: 6000 A , IEC 60947-2: 10 kA
Connection
1

1P

2P

3P + N

version: 4.1

3P

4P

90078E.indd

Protect
Circuit protection

C60N circuit breakers

D curve
IEC 60947-2: 10 kA
Catalogue numbers
Type

1P

2P

3P

4P

90078E.indd

version: 4.1

Rating (A)

Width
in mod.
of 9 mm

Quantity
per batch

Catalogue
number
D curve

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

2
2
2
2
2
2
2
2
2
2
2
2
2
2

12
12
12
12
12
12
12
12
12
12
12
12
12
12

24493
24565
24566
24567
24568
24569
24571
24572
24573
24574
24575
24576
24578
24579

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

4
4
4
4
4
4
4
4
4
4
4
4
4
4

6
6
6
6
6
6
6
6
6
6
6
6
6
6

24494
24580
24581
24582
24583
24584
24586
24587
24588
24589
24590
24591
24593
24594

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

6
6
6
6
6
6
6
6
6
6
6
6
6
6

4
4
4
4
4
4
4
4
4
4
4
4
4
4

24495
24595
24596
24597
24598
24599
24601
24602
24603
24604
24605
24606
24608
24609

0.5
1
2
3
4
6
10
16
20
25
32
40
50
63

8
8
8
8
8
8
8
8
8
8
8
8
8
8

3
3
3
3
3
3
3
3
3
3
3
3
3
3

24496
24610
24611
24612
24613
24614
24616
24617
24618
24619
24620
24621
24623
24624

Protect
Circuit protection

C60N circuit breakers

D curve
IEC 60947-2: 10 kA
Connection
1

1P

2P

3P

4P

Additional information
Vigi modules: page 90116
Electrical auxiliaries: page 90142
Accessories: page 91903
Dimensions: page 90148
Curves: page 90180

version: 4.1

90078E.indd