Anda di halaman 1dari 144

MiCOM P132

Feeder Management and Bay Control


Version -306 415/416/417/418/419 612

Technical Manual
Volume 2 of 2
P132/EN M/Bc5 (AFSV.12.10091 D)

Appendix

A Glossary B Signal List C List of Bay Types D Overview of Changes

Terminal Connection Diagrams: See Volume 1, Chapter 5 Installation and Connection.

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

AN-1

Appendix
(continued)

A A1 A2 A3 A4 A5 B B1 B2 B 2.1 B 2.1.1 B 2.1.2 B 2.1.3 B 2.1.4 B 2.1.5 B3 B 3.1 B 3.1.1 B 3.1.1.1 B 3.1.1.2 B 3.1.1.3 B 3.1.2 B 3.1.3 B 3.1.3.1 B 3.1.3.2 B 3.1.3.3 B 3.1.3.3.1 B 3.1.3.3.2 B 3.1.3.3.3 B 3.1.3.3.4 B 3.1.3.3.5 B 3.1.3.3.6 B 3.1.3.3.7 B 3.1.3.3.8 B 3.1.3.4 B 3.1.3.4.1 B 3.1.3.4.2 B 3.1.3.4.3 B 3.1.3.5 B 3.1.3.6

Glossary Function Groups Modules Symbols Examples of Signal Names Symbols used List of Signals Internal Signal Names Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101 (Companion Standard) Interoperability Network Configuration (Network-Specific Parameters) Physical Layer (Network-Specific Parameters) Link Layer (Network-Specific Parameters) Application Layer Basic Application Functions Communication Interface per IEC 60870-5-103 Interoperability Physical Layer Electrical Interface Optical Interface Transmission Rate Link Layer Application Layer Transmission Mode for Application Data Common Address of ASDU Selection of Standard Information Numbers in Monitor Direction System Functions in Monitor Direction Status Indications in Monitor Direction Monitoring Signals (Supervision Indications) in Monitor Direction Earth Fault Indications in Monitor Direction Fault Indications in Monitor Direction Auto-Reclosure Indications in Monitor Direction Measurands in Monitor Direction Generic Functions in Monitor Direction Selection of Standard Information Numbers in Control Direction System Functions in Control Direction General Commands in Control Direction Generic Functions in Control Direction Basic Application Functions Miscellaneous

A-1 A-1 A-2 A-3 A-10 A-11 B-1 B-1 B-6 B-6 B-6 B-7 B-8 B-19 B-15 B-18 B-18 B-18 B-18 B-18 B-18 B-19 B-19 B-19 B-19 B-19 B-19 B-20 B-21 B-22 B-23 B-25 B-25 B-26 B-27 B-27 B-27 B-28 B-29 B-29

C D

List of Bay Types P132 Upgrade overview

C-1 D-1

AN-2

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix A - Glossary

A1

Function Groups
Fitting: (*: Frequency protection variant) O ( : Order option) 1) not available for P132 in 24TE case VTs & CTs with CTs only with VTs only (*)

ARC: ASC CBF: CBM: CMD_1: COMM1: COMM2: COMM3: DEV01 DEV02 DEV03 DTOC: DVICE: F_KEY: f<>: FT_DA: FT_RC: GF_DA: GF_RC: GFDSS: I2> IDMT1: IDMT2: ILOCK: INP: IRIGB LED: LIMIT: LOC: LOGIC: MAIN: MCMON: MEASI: MEASO: MP: MT_RC: OL_DA: OL_RC: OP_RC: OUTP: P<>: PC: PSIG: PSS: SCDD: SFMON: SIG_1 SOTF: TGFD: THERM: V<>:

Auto-reclosing control Automatic synchronism check Circuit breaker failure protection Circuit Breaker Monitoring Single-pole commands Communication interface 1 Communication interface 2 Communication interface 3 (InterMiCOM) External device 01 External device 02 External device 03 Definite-time overcurrent protection Device Configurable function keys Over-/underfrequency protection Fault data acquisition Fault recording Ground fault data acquisition Ground fault recording Ground fault direction determination using steady-state values Unbalance protection Inverse-time overcurrent protection 1 Inverse-time overcurrent protection 2 Interlocking logic Binary input IRIG-B interface LED indicators Limit value monitoring Local control panel Logic Main function Measuring-circuit monitoring Measured data input Measured data output Motor protection Monitoring signal recording Overload data acquisition Overload recording Operating data recording Binary outputs Power directional protection PC link Protective signaling Parameter subset selection Short-circuit direction determination Self-monitoring Single-pole signals Switch on to fault protection Transient ground fault direction determination Thermal overload protection Time-voltage protection

O 1) O O O 1) O 1) O 1) O 1)

O 1) O O O 1) O 1) O 1) O 1)

O 1) O O O 1) O 1) O 1) O 1)

6
1)

6 -

1)

1)

O 1)

O 1)

O 1)

O 1) O 1)

O 1) O 1)

O 1) O 1)

O 1) O 1)

O 1)

O 1)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

A-1

Appendix A - Glossary
(continued)

A2
A: B: L: N: P: T: V: X: Y:

Modules
Communication module Bus module Local control module Transient ground fault evaluation module Processor module Transformer module Power supply module Binary I/O module Analog I/O module

A-2

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix A - Glossary
(continued)

A3

Symbols

Graphic symbols for block diagrams Binary elements according to DIN 40900 Part 12, September 1992, IEC 617-12: amended 1991 Analog information processing according to DIN 40900 Part 13, January 1981 To document the linking of analog and binary signals, additional symbols have been used, taken from several DIN documents. As a rule, direction of the signal flow is from left to right and from top to bottom. Other flow directions are marked by an arrow. Input signals are listed on the left side of the signal flow, output signals on the right side. Symbol Description To obtain more space for representing a group of related elements, contours of the elements may be joined or cascaded if the following rules are met:

There is no functional linkage between elements whose common contour line is oriented in the signal flow direction. Note: This rule does not necessarily apply to configurations with two or more signal flow directions, such as for symbols with a control block and an output block. There exists at least one logical link between elements whose common contour line runs perpendicularly to the signal flow direction. Components of a symbol A symbol consists of a contour or contour combination and one or more qualifiers.

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

A-3

Appendix A - Glossary
(continued)

Symbol

Description Control block A control block contains an input function common to several symbols. It is used for the collective setting of several trigger elements, for example.

Output block An output block contains an output function common to several symbols.

MAIN: Inom Device [ 010 003 ] D5Z08X5B

Settable control block The 6 digits in square brackets represent the address under which the function shown in the text is implemented. Settable control block with function blocks The digits in the function block show the settings that are possible for this function. The text below the symbol assigns the corresponding unit or meaning to each setting.

MAIN: Inom Device [ 010 003 ] 1.0 5.0 1.0: 1.0 A 5.0: 5.0 A D5Z08X6B

A-4

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix A - Glossary
(continued)

Symbol

Description Static input Only the state of the binary input variable is effective.

Dynamic input Only the transition from value 0 to value 1 is effective.

Negation of an output The value up to the border line is negated at the output.

Negation of an input The input value is negated before the border line.

Dynamic input with negation Only the transition from value 1 to value 0 is effective.

AND element The output variable will be 1 only if all input variables are 1. OR element The output variable will be 1 only if at least one input variable is 1. Threshold element The output variable will be 1 only if at least two input variables are 1. The number in the symbol may be replaced by any other number. (m out of n) element The output variable will be 1 only if just one input variable is 1. The number in the symbol may be replaced by any other number if the number of inputs is increased or decreased accordingly.

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

A-5

Appendix A - Glossary
(continued)

Symbol

Description Delay element The transition from value 0 to 1 at the output occurs after a time delay of t1 relative to the corresponding transition at the input. The transition from value 1 to 0 at the output occurs after a time delay of t2 relative to the corresponding transition at the input. t1 and t2 may be replaced by the actual delay values (in seconds or strobe ticks). Monostable flip-flop The output variable will be 1 only if the input variable changes to 1. The output variable will remain 1 for 100 ms, independent of the duration of the input value 1 (non-retriggerable). Without a 1 in the function block the monostable flipflop is retriggerable. The time is 100 ms in this example, but it may be changed to any other duration. Analog-digital converter An analog input signal is converted to a binary signal.

Subtractor The output variable is the difference between the two input variables. A summing element is obtained by changing the minus sign to a plus sign at the symbol input. Schmitt Trigger with binary output signal The binary output variable will be 1 if the input signal exceeds a specific threshold. The output variable remains 1 until the input signal drops below the threshold again. Memory, general Storage of a binary or analog signal.

A-6

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix A - Glossary
(continued)

Symbol

Description Non-stable flip-flop When the input variable changes to 1, a pulse sequence is generated at the output. The ! to the left of the G indicates that the pulse sequence starts with the input variable transition (synchronized start). If there is a ! to the right of the G, the pulse sequence ends with the ending of the 1 signal at the input (synchronized stop). Amplifier The output variable is 1 only if the input variable is also 1. Band pass filter The output only transmits the 50 Hz component of the input signals. All other frequencies (above and below 50 Hz) are attenuated. Counter At the + input the input variable transitions from 0 to 1 are counted and stored in the function block. At the R(eset) input a transition of the input variable from 0 to 1 resets the counter to 0. Electromechanical drive in general, here a relay, for example.

Signal level converter with electrical isolation between input and output. L+ = pos. voltage input L- = neg. voltage input U1 = device identifier

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

A-7

Appendix A - Glossary
(continued)

Symbol

Description Input transformer with phase and item identifiers (according to DIN EN 60445) Phase identifiers for current inputs: for A: A1 and A2 for B: B1 and B2 for C: C1 and C2 for N: N1 and N2 Phase identifiers for voltage inputs via transformer 1: for A: 1U for B: 1V for C: 1W for N: 1N via transformer 2: for A: 2U for B: 2V Item identifiers for current transformers: for A: T1 for B: T2 for C: T3 for N: T4 for voltage transformer 1: for A: T5 for B: T6 for C: T7 for N: T8 for VG-N transformer: T90 for voltage transformer 2: for A: T15 Change-over contact with item identifier

Special symbol Output relay in normally-energized arrangement (closed-circuit operation).

A-8

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix A - Glossary
(continued)

Symbol

Description PC interface with pin connections

Multiplier The output variable is the result of the multiplication of the two input variables.

Divider The output variable is the result of the division of the two input variables.

Comparator The output variable becomes 1 only if the input variable(s) are equal to the function in the function block. Formula block The output variable becomes 1 only if the input variable(s) satisfy the equation in the function block

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

A-9

Appendix A - Glossary
(continued)

A4

Examples of Signal Names

All settings and signals relevant for protection are shown in the block diagrams of Chapter 3 as follows: Signal Name FT_RC: Fault recording n
305 100

Description Internal signal names are not coded by a data model address. In the block diagrams they are marked with a diamond. The small figure underneath the signal name represents a code that is irrelevant to the user. The internal signal names used and their origins are listed in Appendix B. Signal names coded by a data model address are represented by their address (shown in square brackets). Their origin is given in Chapters 7 and 8. A specific setting to be used later on is shown with its signal name, address, and the setting preceded by the setting arrow.

DIST: VNG>> triggered [ 036 015 ]

MAIN: General reset [ 003 002 ] 1: Execute

A-10

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix A - Glossary
(continued)

A5
Symbol t V V I I Z
Z

Symbols Used
Meaning Time duration Voltage, potential difference Complex voltage Electrical current Complex current Complex impedance Modulus of complex impedance Frequency Temperature in C Sum, result Unit of electrical resistance Angle Phase angle. With subscripts: specific angle between a defined current and a defined voltage. Time constant Temperature difference in K

f T

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

A-11

A-12

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals

B 1 Internal Signal Names Internal signal names are not coded by an external address. In the block diagrams they are marked with a diamond. Internal Signal Names ARC: Block/reset HSR ARC: Block/reset TDR ARC: Close request ARC: HSR not permitted ARC: HSR trip t. elapsed ARC: Starting GFDSS ARC: TDR not permitted ARC: TDR trip t. elapsed ASC: AC active for DEV01 ASC: Active ASC: Clos.rej. w. block ASC: Close enable DEV01 AC ASC: Close enable w. block ASC: Gen. close request ASC: Manual close request ASC: Sel. meas. loop PG ASC: Test ASC: VMeas CBM: Internal trip cmd. COMM1: Communication error COMM1: Debounced signal COMM1: Selected protocol DEV01: Close cmd. rejection DEV01: Close request DEV01: Enable BI Close DEV01: Enable BI Open DEV01: Enable SI Close DEV01: Enable SI Open DEV01: End close command DEV01: End open command DEV01: Latching time elaps. DEV01: Latching time runn.
P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Figure 3-163 3-163 3-165 3-165 3-157, 3-159, 3-160, 3-161, 3-162 3-160 3-165 3-158, 3-159, 3-160, 3-161, 3-162 3-180 3-173 3-173 3-180 3-173 3-174 3-174 3-171 3-174 3-171 3-262, 3-265 3-9, 3-10, 3-11, 3-12, 3-13, 3-14 3-42 3-8 3-293 3-292 3-294 3-294 3-293 3-293 3-297 3-297 3-292 3-292 B-1

Appendix B - List of Signals


(continued)

Internal Signal Names DEV01: Open cmd. rejection DEV01: Open request DEV01: Protect. close cmd. DEV01: Protection trip cmd. DEV01: Switch. device runn. DTOC: IN DTOC: Pulse prolong. runn. DTOC: Starting A DTOC: Starting B DTOC: Starting C DTOC: Starting N DTOC: t2 N f<>: fMeas f<>: No. periods reached f<>: VMeas FT_DA: IA-kG FT_DA: IB-kG FT_DA: IC-kG FT_DA: IkG FT_DA: Output fault locat. FT_DA: Output meas. values GFDSS: Direction BS GFDSS: Direction LS GFDSS: IN filtered GFDSS: IN> triggered GFDSS: Op. delay IN elapsed GFDSS: Oper.delay Y(N)> elaps GFDSS: P GFDSS: Q GFDSS: VNG GFDSS: VNG filtered GFDSS: VNG> triggered

Figure 3-293 3-292 3-295 3-295 3-297 3-119 3-122 3-115 3-115 3-115 3-120 3-122 3-233 3-233 3-232 3-106 3-106 3-106 3-106 3-105 3-105 3-185, 3-191 3-185, 3-191 3-189 3-189 3-189 3-195 3-185, 3-191 3-185, 3-191 3-184 3-185, 3-191 3-185

B-2

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

Internal Signal Names IDMT1: ARC Starting Iref,N> IDMT1: ARC Starting Iref,P> IDMT1: IN IDMT1: Starting A IDMT1: Starting B IDMT1: Starting C LOC: Remote & Local MAIN: Imeas MAIN: Block start. signal MAIN: Block tim.st. IN,neg MAIN: Block. 1 sel.functions MAIN: Block. 2 sel.functions MAIN: Customized bay type MAIN: General starting int. MAIN: Inrush stabil. trigg MAIN: Internal CB open MAIN: Protection active MAIN: Reset LED MAIN: Sel. meas. loop A-B MAIN: Sel. meas. loop A-G MAIN: Sel. meas. loop B-C MAIN: Sel. meas. loop B-G MAIN: Sel. meas. loop C-A MAIN: Sel. meas. loop C-G MAIN: Sel. meas. loop PG MAIN: Sel. meas. loop PP MAIN: Start. I>,kIref,P> MAIN: Starting A int. MAIN: Starting B int. MAIN: Starting C int. MAIN: Starting Ineg MAIN: Starting N int. MAIN: Time tag MAIN: Vmeas MEASO: Enable
P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Figure 3-135 3-131 3-133 3-130 3-130 3-130 3-6 3-107 3-71 3-71 3-64 3-64 3-45 3-72 3-62 3-263, 3-265 3-59 3-82 3-107 3-107 3-107 3-107 3-107 3-107 3-107 3-107 3-72 3-71 3-71 3-71 3-71 3-71 3-81 3-107 3-35 B-3

Appendix B - List of Signals


(continued)

Internal Signal Names MEASO: Reset meas.val.outp. MP: Block. replica THERM MP: IP,max r.m.s./Iref MP: IStUp> MP: Machine stopped MP: St. kP*Iref>/Istup> P<>: P P<>: PP<>: P+ P<>: Q P<>: QP<>: Q+ SCDD: Block. direct. tI> SCDD: Block. direct. tI>> SCDD: Block. direct. tIN> SCDD: Block. direct. tIN>> SCDD: Block. direct. tIref,N> SCDD: Block. direct. tIref,P> SCDD: Determin. N enabled SCDD: Determin. P enabled SCDD: Phase curr.stage bl. SCDD: Resid. curr.stage bl. SCDD: VNG SOTF: ARC block. by close cm

Figure 3-36 3-210 3-205 3-210 3-210 3-205 3-237 3-237 3-237 3-237 3-237 3-237 3-141 3-141 3-145 3-145 3-145 3-141 3-143 3-139 3-139 3-143 3-143b 3-147

B-4

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

Internal Signal Names TGFD: Direction BS TGFD: Direction LS TGFD: Hardware fault TGFD: IN,p> triggered TGFD: Reset signal TGFD: VNG TGFD: VNG> (f0) triggered TGFD: VNG> triggered THERM: Block. by CTA error THERM: I THERM: With CTA V<>: Vneg V<>: VNG V<>: Vpos

Figure 3-199 3-199 3-197 3-199 3-201 3-198 3-199 3-199 3-216, 3-217 3-218 3-216, 3-217 3-226 3-228 3-226

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-5

Appendix B - List of Signals


(continued)

B2

Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101 (Companion Standard)

This section incorporates Section 8 of EN 60870-5-101 (1996), which includes a general definition of the telecontrol interface for substation control systems. B 2.1 Interoperability This application-based standard (companion standard) specifies parameter sets and other options from which subsets are to be selected in order to implement specific telecontrol systems. Certain parameters such as the number of bytes (octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This means that only one value of the defined parameter is allowed per system. Other parameters, such as the listed set of different process information in the command and monitor direction, permit definition of the total number or of subsets that are suitable for the given application. This section combines the parameters given in the previous sections in order to facilitate an appropriate selection for a specific application. If a system is made up of several system components supplied by different manufacturers, then it is necessary for all partners to agree on the selected parameters. The boxes for the selected parameters should be checked. 1 Note: The overall definition of a system may also require individual selection of certain parameters for specific parts of a system such as individual selection of scaling factors for individually addressable measured values.

B 2.1.1 Network Configuration (Network-Specific Parameters) x x Point-to-point configuration Multiple point-to-point configuration x Multipoint-party line configuration Multipoint-star configuration

See National Preface of EN 60870-5-101.


P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-6

Appendix B - List of Signals


(continued)

B 2.1.2

Physical Layer 2 (Network-Specific Parameters)

Transmission Rate (Control Direction) 3 Unbalanced interface V.24/V.28 Standardized 100 bit/s 200 bit/s 300 bit/s x x 600 bit/s 1,200 bit/s Unbalanced interface V.24/V.28 Recommended with > 1 200 bit/s x x x 2,400 bit/s 4,800 bit/s 9,600 bit/s 2,400 bit/s 4,800 bit/s 9,600 bit/s 19,200 bit/s 38,400 bit/s 56,000 bit/s 64,000 bit/s Balanced interface X.24/X.27

Transmission Rate (Monitor Direction) 2 Unbalanced interface V.24/V.28 Standardized 100 bit/s 200 bit/s 300 bit/s x x 600 bit/s 1,200 bit/s Unbalanced interface V.24/V.28 Recommended with > 1 200 bit/s x x x 2,400 bit/s 4,800 bit/s 9,600 bit/s 2,400 bit/s 4,800 bit/s 9,600 bit/s 19,200 bit/s 38 400 bit/s 56,000 bit/s 64,000 bit/s Balanced interface X.24/X.27

2 3

See National Preface of EN 60870-5-101. The transmission rates for control direction and monitor direction must be identical. B-7

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 2.1.3

Link Layer 4(Network-Specific Parameters)

Frame format FT 1.2, single character 1, and the fixed time-out interval are used exclusively in this companion standard. Link Transmission Procedure x Balanced transmission Address Field of the Link x Not present (balanced transmission only) x Unbalanced transmission x One octet x Two octets 5 Frame Length 240 Maximum length L (number of octets) x Structured x Unstructured

4 5

See National Preface of EN 60870-5-101. Balanced only.


P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-8

Appendix B - List of Signals


(continued)

B 2.1.4

Application Layer6

Transmission mode for application data Mode 1 (least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used exclusively in this companion standard. Common Address of ASDU (System-Specific Parameter) x One octet Information Object Address (System-Specific Parameter) x One octet x Two octets x Three octets Cause of Transmission (System-Specific Parameter) x One octet x Two octets (with originator address) x Structured x Unstructured x Two octets 1

See National Preface of EN 60870-5-101. B-9

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

Selection of Standard ASDUs Process Information in Monitor Direction (Station-Specific Parameter) x x x x x x x x x x x x <1> <2> <3> <4> <5> <6> <7> <8> <9> <10> <11> <12> <13> <14> x x <15> <16> = = = = = = = = = = = = = = = = Single-point information Single-point information with time tag Double-point information Double-point information with time tag Step position information Step position information with time tag Bit string of 32 bit Bit string of 32 bit with time tag Measured value, normalized value Measured value, normalized value with time tag Measured value, scaled value Measured value, scaled value with time tag Measured value, short floating point value Measured value, short floating point value with time tag Integrated totals Integrated totals with time tag M_SP_NA_1 M_SP_TA_1 M_DP_NA_1 M_DP_TA_1 M_ST_NA_1 M_ST_TA_1 M_BO_NA_1 M_BO_TA_1 M_ME_NA_1 M_ME_TA_1 M_ME_NB_1 M_ME_TB_1 M_ME_NC_1 M_ME_TC_1 M_IT_NA_1 M_IT_TA_1

B-10

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

x x x

<17> <18> <19> <20> <21>

= = = = =

Event of protection equipment with time tag Packed start events of protection equipment with time tag Packed output circuit information of protection equipment with time tag Packed single-point information with status change detection Measured value, normalized value without quality descriptor

M_EP_TA_1 ME_EP_TB_1 M_EP_TC_1 M_PS_NA_1 M_ME_ND_1

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-11

Appendix B - List of Signals


(continued)

Process Information in Monitor Direction 7 (Station-Specific Parameter) x x x <45> <46> <47> <48> <49> <50> <51> = = = = = = = Single command Double command Regulating step command Set point command, normalized value Set point command, scaled value Set point command, short floating point value Bit string of 32 bit C_SC_NA_1 C_DC_NA_1 C_IT_NA_1 C_RC_NA_1 C_SE_NB_1 C_SE_NC_1 C_BO_NA_1

System Information in Monitor Direction (Station-Specific Parameter) x <70> = End of initialization ME_EI_NA_1

Incorrectly identified with control direction in IEC 870-5-101.


P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-12

Appendix B - List of Signals


(continued)

System Information in Control Direction (Station-Specific Parameter) x x x x x <100> <101> <102> <103> <104> <105> <106> = = = = = = = Interrogation command Counter interrogation command Read command Clock synchronization command 8 Test command Reset process command Delay acquisition command 9 C_IC_NA_1 C_CI_NA_1 C_RD_NA_1 C_CS_NA_1 C_TS_NB_1 C_RP_NC_1 C_CD_NA_1

8 9

The command procedure is formally processed, but there is no change in the local time in the station. See National Preface of EN 60870-5-101. B-13

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

Parameter in Control Direction (Station-Specific Parameter) x x <110> <111> <112> <113> = = = = Parameter of measured value, normalized value Parameter of measured value, scaled value Parameter of measured value, short floating point value Parameter activation P_ME_NA_1 P_ME_NB_1 P_ME_NC_1 P_AC_NA_1

File Transfer (Station-Specific Parameter) <120> <121> <122> <123> <124> <125> <126> = = = = = = = File ready Section ready Call directory, select file, call file, call section Last section, last segment Ack file, ack section Segment Directory F_FR_NA_1 F_SR_NA_1 F_SC_NA_1 F_LS_NA_1 F_AF_NA_1 F_SG_NA_1 F_DR_TA_1

B-14

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 2.1.5

Basic Application Functions10

Station Initialization (Station-Specific Parameter) x Remote initialization

General Interrogation (System- or Station-Specific Parameter) x x x x x x x Global Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 x x x x x x Group 7 Group 8 Group 9 Group 10 Group 11 Group 12 Addresses per group have to be defined. x x x x Group 13 Group 14 Group 15 Group 16

Clock Synchronization (Station-Specific Parameter) x Clock synchronization

10

See National Preface of EN 60870-5-101. B-15

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

Command Transmission (Object-Specific Parameter) x Direct command transmission Direct set point command transmission Select and execute command Select and execute set point command C_SE ACTTERM used x No additional definition Short pulse duration (Execution duration determined by a system parameter in the outstation) Long pulse duration (Execution duration determined by a system parameter in the outstation) Persistent output Transmission of Integrated Totals (Station- or Object-Specific Parameter) Counter request x Counter freeze without reset Counter freeze with reset Counter reset Addresses per group have to be specified x x x x x General request counter Request counter group 1 Request counter group 2 Request counter group 3 Request counter group 4

B-16

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

Parameter Loading (Object-Specific Parameter) x Threshold value Smoothing value Low limit for transmission of measured value High limit for transmission of measured value

Parameter Activation (Object-Specific Parameter) Act/deact of persistent cyclic or periodic transmission of the addressed object

File Transfer (Station-Specific Parameter) File transfer in monitor direction File transfer in control direction F_FR_NA_1 F_FR_NA_1

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-17

Appendix B - List of Signals


(continued)

B3

Communication Interface per IEC 60870-5-103

This section incorporates Section 8 of IEC 60870-5-103, including definitions applicable to the P132. B 3.1 B 3.1.1 Interoperability Physical Layer

B 3.1.1.1 Electrical Interface x x EIA RS 485 No. of loads 32 for one device

Note: EIA RS 485 defines the loads in such a way that 32 of such loads can be operated on one line. For detailed information see EIA RS 485, Section 3. B 3.1.1.2 Optical Interface x x x Glass fiber Plastic fiber F-SMA connector BFOC/2.5 connector B 3.1.1.3 Transmission Rate x x 9,600 bit/s 19,200 bit/s

B-18

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.2

Link Layer

There are no selection options for the link layer. B 3.1.3 Application Layer

B 3.1.3.1 Transmission Mode for Application Data Mode 1 (least significant octet first) as defined in clause 4.10 of IEC 60870-5-4 is used exclusively in this companion standard. B 3.1.3.2 Common Address of ASDU x One COMMON ADDRESS of ASDU (identical to the station address) More than one COMMON ADDRESS of ASDU B 3.1.3.3 Selection of Standard Information Numbers in Monitor Direction

B 3.1.3.3.1 System Functions in Monitor Direction INF x x x x x <0> <0> <2> <3> <4> <5> Description End of general interrogation Time synchronization Reset FCB Reset CU Start / restart Power on

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-19

Appendix B - List of Signals


(continued)

B 3.1.3.3.2 Status Indications in Monitor Direction INF x x x x x x <16> <17> <18> <19> <20> <21> <22> x x x x x x x x <23> <24> <25> <26> <27> <28> <29> <30> Description Auto-recloser active Teleprotection active Protection active LED reset Blocking of monitor direction Test mode Local parameter setting Characteristic 1 Characteristic 2 Characteristic 3 Characteristic 4 Auxiliary input 1 Auxiliary input 2 Auxiliary input 3 Auxiliary input 4 036 090 036 091 036 092 036 093 034 000 034 001 034 002 034 003 PSS: PS 1 active PSS: PS 2 active PSS: PS 3 active PSS: PS 4 active LOGIC: Input 1 EXT LOGIC: Input 2 EXT LOGIC: Input 3 EXT LOGIC: Input 4 EXT AREVA Designations Address Description 015 064 015 008 003 030 021 010 037 075 037 071 ARC: Enabled PSIG: Enabled MAIN: Device on-line MAIN: Reset indicat. USER COMM1: Sig./meas.val.block. MAIN: Test mode

B-20

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.3.3 Monitoring Signals (Supervision Indications) in Monitor Direction AREVA Designations INF Description Address Description x x x x <32> <33> <35> <36>11 <37> x x x x <38> <39> <46> <47> Measurand supervision I Measurand supervision V Phase sequence supervision Trip circuit supervision I>> back-up operation VT fuse failure Teleprotection disturbed Group warning Group alarm 004 061 036 060 036 100 004 065 MAIN: M.c.b. trip V EXT PSIG: Telecom. faulty SFMON: Warning (relay) MAIN: Blocked/Faulty 040 087 038 023 038 049 041 200 MCMON: Meas. circ. I faulty MCMON: Meas. circ. V faulty MCMON: Phase sequ. V faulty SFMON: Relay Kxx faulty

11

The message content is formed from the OR operation of the individual signals. B-21

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.3.4 Earth Fault Indications in Monitor Direction INF x x x x x <48> <49> <50> <51> <52> Description Earth fault L1 Earth fault L2 Earth fault L3 Earth fault forward, i.e. line Earth fault reverse, i.e. busbar AREVA Designations Address Description 041 054 041 055 041 056 041 088 041 089 MAIN: Ground fault A MAIN: Ground fault B MAIN: Ground fault C MAIN: Gnd. fault forw./LS MAIN: Gnd. fault backw./BS

B-22

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.3.5 Fault Indications in Monitor Direction INF x x x x x <64> <65> <66> <67> <68> <69> <70> <71> <72> x x x x <73> <74> <75> <76> Description Start /pick-up L1 Start /pick-up L3 Start /pick-up L3 Start /pick-up N General trip Trip L1 Trip L2 Trip L3 Trip I>> (back-up operation) Fault location X in ohms Fault forward/line Fault reverse/busbar Teleprotection signal transmitted 004 029 036 018 036 019 036 035 FT_DA: Fault react., prim. SCDD: Fault P forward SCDD: Fault P backward PSIG: Send (signal) AREVA Designations Address Description 040 005 040 006 040 007 040 008 036 071 MAIN: Starting A MAIN: Starting B MAIN: Starting C MAIN: Starting GF MAIN: Gen. trip command 1

<77> <78> <79> <80> <81> <82> <83>

Teleprotection signal received Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6

037 029

PSIG: Receive (signal)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-23

Appendix B - List of Signals


(continued)

INF x x <84> <85> <86> <87> <88> <89> x x x x <90> <91> <92> <93>

Description General starting Breaker failure Trip measuring system L1 Trip measuring system L2 Trip measuring system L3 Trip measuring system E Trip I> Trip I>> Trip IN> Trip IN>>

AREVA Designations Address Description 040 000 036 017 MAIN: General starting CBF: CB failure

040 042 040 011 040 043 040 028

MAIN: TripSig. tI>/tIrefP> DTOC: Trip Signal tI>> MAIN: TripSig. tIN>/tIrefN> DTOC: Trip Signal tIN>>

B-24

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.3.6 Auto-Reclosure Indications in Monitor Direction INF x x x <128> <129> <130> Description CB on by AR CB on by long-time AR AR blocked AREVA Designations Address Description 037 007 037 006 037 008 ARC: (Re)close signal HSR ARC: (Re)close signal TDR ARC: Not ready

B 3.1.3.3.7 Measurands in Monitor Direction INF x x <144>12 <145>13 Description Measurand I Measurands I, V AREVA Designations Address Description 006 041 006 041 005 045 006 041 005 045 004 051 004 053 005 011 005 013 005 041 006 041 007 041 005 043 006 043 007 043 004 051 004 053 004 040 MAIN: Current B p.u. MAIN: Current B p.u. MAIN: Voltage A-B p.u. MAIN: Current B p.u. MAIN: Voltage A-B p.u. MAIN: Active power P p.u. MAIN: Reac. power Q p.u. MAIN: Current (IP) p.u. MAIN: Volt. (VPG)/3 p.u. MAIN: Current A p.u. MAIN: Current B p.u. MAIN: Current C p.u. MAIN: Voltage A-G p.u. MAIN: Voltage B-G p.u. MAIN: Voltage C-G p.u. MAIN: Active power P p.u. MAIN: Reac. power Q p.u. MAIN: Frequency f

<146>14

Measurands I, V, P, Q

<147>15

Measurands IN, VEN

<148>16

Measurands IA,B,C, VA,B,C, P, Q, f

12 13

only with setting only with setting 14 only with setting 15 only with setting 16 only with setting

COMM1: COMM1: COMM1: COMM1: COMM1:

Transm.enab.cycl.dat Transm.enab.cycl.dat Transm.enab.cycl.dat Transm.enab.cycl.dat Transm.enab.cycl.dat

to "ASDU 3.1 p. IEC" to "ASDU 3.2 p. IEC" to "ASDU 3.3 p. IEC" to "ASDU 3.4 p. IEC" to "ASDU 9 p. IEC" B-25

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.3.8 Generic Functions in Monitor Direction INF <240> <241> <243> <244> <245> <249> <250> <251> Description Read headings of all defined groups Read values or attributes of all entries of one group Read directory of a single entry Read value or attribute of a single entry General interrogation of generic data Write entry with confirmation Write entry with execution Write entry abort

B-26

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.4

Selection of Standard Information Numbers in Control Direction

B 3.1.3.4.1 System Functions in Control Direction INF x x <0> <0> Description Initiation of general interrogation Time synchronization

B 3.1.3.4.2 General Commands in Control Direction INF x x x x x x x x <16> <17> <18> <19> <23>17 <24>18 <25>19 <26>20 Description Auto-recloser on/off Teleprotection on/off Protection on/off LED reset Activate characteristic 1 Activate characteristic 2 Activate characteristic 3 Activate characteristic 4 AREVA Designations Address Description 015 060 015 004 003 030 021 010 003 060 003 060 003 060 003 060 ARC: General enable USER PSIG: General enable USER MAIN: Device on-line MAIN: Reset indicat. USER PSS: Param.subs.sel. USER PSS: Param.subs.sel. USER PSS: Param.subs.sel. USER PSS: Param.subs.sel. USER

17 18

Switches Switches 19 Switches 20 Switches

PSS: PSS: PSS: PSS:

Param.subs.sel.USER Param.subs.sel.USER Param.subs.sel.USER Param.subs.sel.USER

to "Parameter set 1" to "Parameter set 2" to "Parameter set 3" to "Parameter set 4" B-27

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.4.3 Generic Functions in Control Direction INF <240> <241> <243> <244> <245> <248> <249> <250> <251> Description Read headings of all defined groups Read values or attributes of all entries of one group Read directory of a single entry Read value or attribute of a single entry General interrogation of generic data Write entry Write entry with confirmation Write entry with execution Write entry abort

B-28

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix B - List of Signals


(continued)

B 3.1.3.5 x x x

Basic Application Functions

Test mode Blocking of monitor direction Disturbance data Generic services

Private data Miscellaneous

B 3.1.3.6

Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in Sec. 7.2.6.8, the maximum MVAL can be either 1.2 or 2.4 times the rated value. In ASDU 3 and ASDU 9, different ratings may not be used; in other words, there is only one choice for each measurand. Measured value Max. MVAL = nom. value multiplied by 1,2 Current A Current B Current C Voltage A-G Voltage B-G Voltage C-G Enabled power P Reactive power Q Frequency f Voltage A-B or 2,4 x x x x x x x x x x

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

B-29

B-30

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types

Key
Sorting the Bay Types The bay types are sorted by the criteria listed below. These criteria are encoded in the first three characters of the bay type code (example: A11.100.R01) given in brackets after the Bay Type No. (example: 2). Sorting is first by "Type of bay" in the order given below, then within each group by the second and third character in ascending order. Type of bay A - Feeder bays L - Bus sectionalizer bay Q - Bus coupler bay K - Bus coupler and sectionalizer bay M - Busbar measurement bay E - Busbar grounding bay X - Other bay type Number of busbars 1 - Single busbar 2 - Double busbar 9 - Without busbar / other configurations Equipment 1 - Bays with switch truck or withdrawable switchgear assembly 2 - Bays with two circuit breakers or switch disconnectors on switch trucks or withdrawable switchgear assembly 3 - Bays with stationary switchgear units 5 - Bays with stationary switchgear units and three-position disconnector 9 - Other bay types

Bay Type No.:

This number indicates the value to be set at M AIN : T yp e o f b a y (folder "Para/Conf") in order to configure the unit for the selected bay type.

Special Designations for External Devices: Mot.relay: Motor relay Shunt wd. Shunt winding

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-1

Appendix C - List of Bay Types


(Continued)

Table "Assignment of Binary Inputs and Output Relays" Column "Switchgear unit" This column begins with the designation for the external device (switchgear unit). The function group follows in brackets. The function group encompasses all setting options for monitoring the switchgear unit and its signals. "Open" and "Close(d)" indicate the signal message or control direction of the switchgear unit. The "Open" or "Closed" signal should be connected to the binary input U xxxx. The connection points of the binary input U xxxx are shown in the terminal connection diagrams. The "Open" or "Close" control of the switchgear unit is effected via output relay K xxxx. The connection points of the output relay K xxxx are shown in the terminal connection diagrams.

Column "Binary Input":

Column "Output relay"

Table "Bay Interlock Equations for Operation without Station Interlocking" Note! The interlock equations are stored at substation control level, not at unit level. Symbols used in the Boolean interlock equations: /: Negation 0: Switchgear unit "Open" I: Switchgear unit "Closed" X: Switchgear unit in intermediate position FctBl1: FctBl2: Function block 1, configuration at M A I N : F c t . a s g . f c t . b l o c k .1 (Folder "Para/Func/Ctrl") Function block 2, configuration at M A I N : F c t . a s g . f c t . b l o c k .2 (Folder "Para/Func/Ctrl")

C-2

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(Continued)

List of P132 Bay Panel types Bay Panel type (Identification): A Feeder Bay
2 (A11.100.R01) 3 (A11.100.R02) 4 (A11.101.R01) 5 (A11.101.R02) 6 (A11.101.R03) 523 (A11.108.R01) 7 (A11.200.R01) 8 (A11.200.R02) 9 (A11.201.R01) 10 (A11.201.R02) 11 (A11.201.R03) 12 (A11.400.R01) 13 (A11.400.R02) 14 (A11.401.R01) 15 (A11.401.R02) 16 (A11.401.R03) 17 (A11.900.R01) 504 (A11.901.R00) 541 (A13.104.R01) 19 (A13.105.R01) 20 (A13.105.R02) 21 (A13.105.R03) 557 (A13.106.R03) 26 (A13.200.R01) 28 (A13.201.R01) 29 (A13.201.R02) 31 (A13.205.R01) 32 (A13.205.R02) 33 (A13.205.R03) 34 (A13.400.R01) 36 (A13.401.R01) 37 (A13.401.R02) 39 (A13.405.R01) 40 (A13.405.R02) 41 (A13.405.R03) 503 (A13.432.R02) 507 (A13.433.R02) 43 (A15.105.R01) 221 (A15.105.R02) 44 (A15.105.R03) 87 (A23.104.R01) 88 (A23.104.R03) 101 (A23.204.R01) 102 (A23.204.R03) 115 (A23.404.R01) 116 (A23.404.R03)

L Bus Sectionalizer Bay


133 553 134 528 542 135 136 137 138 545 139 148 149 150 164 (L11.100.R01) (L11.100.R01.2) (L11.100.R02) (L11.102.R01) (L11.102.R01.2) (L11.104.R01) (L11.104.R02) (L11.104.R03) (L11.116.R01) (L11.116.R01.2) (L11.116.R03) (L11.200.R01) (L11.202.R01) (L11.202.R03) (L23.901.R02)

T Bus Coupler Bay


505 563 205 206 (Q21.100.R01) (Q21.133.R01) (Q23.101.R01) (Q23.101.R03)

M Busbar Measurement Bay


171 172 540 173 174 176 177 506 233 179 188 189 193 559 560 194 (M11.300.R00) (M11.300.R01) (M11.304.R02) (M11.900.R00) (M11.900.R01) (M13.312.R01) (M13.312.R02) (M13.902.R00) (M15.903.R01) (M15.903.R02) (M23.302.R02) (M23.312.R02) (M23.902.R02) (M23.904.R00) (M23.908.R00) (M23.912.R02)

E Busbar Grounding Bay


130 (E13.901.R01) 132 (E23.903.R02)

X Other Bay Type


1 (X99.901.R00)

Customized Bay
999 (User)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-3

Appendix C - List of Bay Types

Bay Type No. 2

(A11.100.R01)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

C-4

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 3

(A11.100.R02)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-5

Appendix C - List of Bay Types


(continued)

Bay Type No. 4

(A11.101.R01)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

C-6

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 5

(A11.101.R02)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-7

Appendix C - List of Bay Types


(continued)

Bay Type No. 6

(A11.101.R03)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8 X0

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (X0=0) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8 X0

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (X0=0) (Q0=0) (Q0=0) & (Q8=0)

C-8

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 523

(A11.108.R01)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q15 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-9

Appendix C - List of Bay Types


(continued)

Bay Type No. 7

(A11.200.R01)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

C-10

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 8

(A11.200.R02)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-11

Appendix C - List of Bay Types


(continued)

Bay Type No. 9

(A11.201.R01)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

C-12

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 10

(A11.201.R02)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-13

Appendix C - List of Bay Types


(continued)

Bay Type No. 11

(A11.201.R03)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8 X0

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (X0=0) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8 X0

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (X0=0) (Q0=0) (Q0=0) & (Q8=0)

C-14

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 12

(A11.400.R01)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K A01 K A02 / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-15

Appendix C - List of Bay Types


(continued)

Bay Type No. 13

(A11.400.R02)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

C-16

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 14

(A11.401.R01)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K A01 K A02 / / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-17

Appendix C - List of Bay Types


(continued)

Bay Type No. 15

(A11.401.R02)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K K K K / / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X0

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

C-18

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 16

(A11.401.R03)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K K K K K K / A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8 X0

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (X0=0) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8 X0

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I) (X0=0) (Q0=0) (Q0=0) & (Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-19

Appendix C - List of Bay Types


(continued)

Bay Type No. 17

(A11.900.R01)

Feeder bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
X0 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
K A01 K A02

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-20

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 504

(A11.901.R00)

Feeder bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
X0 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d)

Binary input
U U U U A03 A04 A05 A06

Output relay
/ / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-21

Appendix C - List of Bay Types


(continued)

Bay Type No. 541

(A13.104.R01)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(FctBl1=I) & /(FctBl2=I)

C-22

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 19

(A13.105.R01)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-23

Appendix C - List of Bay Types


(continued)

Bay Type No. 20

(A13.105.R02)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Close(d) Open Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Close(d) Open Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

C-24

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 21

(A13.105.R03)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Close(d) Open Close(d) Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=0) & (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Close(d) Open Close(d) Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=0) & (Q1=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-25

Appendix C - List of Bay Types


(continued)

Bay Type No. 557

(A13.106.R03)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q9 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q9

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q1=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1 Q9

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q1=X) & /(Q9=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=0) (Q0=0)

C-26

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 26

(A13.200.R01)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
K A01 K A02

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-27

Appendix C - List of Bay Types


(continued)

Bay Type No. 28

(A13.201.R01)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q8 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I)

C-28

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 29

(A13.201.R02)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q8 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-29

Appendix C - List of Bay Types


(continued)

Bay Type No. 31

(A13.205.R01)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

C-30

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 32

(A13.205.R02)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Close(d) Open Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Close(d) Open Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-31

Appendix C - List of Bay Types


(continued)

Bay Type No. 33

(A13.205.R03)

Feeder bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Close(d) Open Close(d) Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=0) & (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Close(d) Open Close(d) Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=0) & (Q1=0)

C-32

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 34

(A13.400.R01)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) F (SIG_1: Signal S011) Open Close(d)

Binary input
U A01 U A02 U B05

Output relay
K A01 K A02 /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-33

Appendix C - List of Bay Types


(continued)

Bay Type No. 36

(A13.401.R01)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q8 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K A01 K A02 / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I)

C-34

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 37

(A13.401.R02)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q8 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-35

Appendix C - List of Bay Types


(continued)

Bay Type No. 39

(A13.405.R01)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K A01 K A02 / / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

C-36

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 40

(A13.405.R02)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K K K K / / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Close(d) Open Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Close(d) Open Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-37

Appendix C - List of Bay Types


(continued)

Bay Type No. 41

(A13.405.R03)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K K K K K K / A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Close(d) Open Close(d) Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=0) & (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Close(d) Open Close(d) Close(d)

Interlock equation
/(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=0) & (Q1=0)

C-38

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 503

(A13.432.R02)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q8 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-39

Appendix C - List of Bay Types


(continued)

Bay Type No. 507

(A13.433.R02)

Feeder bay with switch disconnector / fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q8 (DEV02) Q15 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K K K K / / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0)

C-40

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 43

(A15.105.R01)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Open Close(d)

Interlock equation
(Q8=0) /(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Open Close(d)

Interlock equation
(Q8=0) /(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-41

Appendix C - List of Bay Types


(continued)

Bay Type No. 221

(A15.105.R02)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Open Close(d) Open Close(d)

Interlock equation
(Q8=0) /(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1

Control O/C
Open Close(d) Open Close(d)

Interlock equation
(Q8=0) /(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

C-42

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 44

(A15.105.R03)

Feeder bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Open Close(d) Open Close(d) Open Close(d)

Interlock equation
(Q8=0) /(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0) (Q0=I) (Q0=0) & (Q1=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q1 Q8

Control O/C
Open Close(d) Open Close(d) Open Close(d)

Interlock equation
(Q8=0) /(Q1=X) & (Q8=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=I) (Q0=0) & (Q1=0) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-43

Appendix C - List of Bay Types


(continued)

Bay Type No. 87

(A23.104.R01)

Feeder bay with circuit breaker, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q2 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

C-44

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 88

(A23.104.R03)

Feeder bay with circuit breaker, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q2 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q2

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) & (Q2=0) (Q0=0) & (Q2=0) (Q0=0) & (Q1=0) (Q0=0) & (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-45

Appendix C - List of Bay Types


(continued)

Bay Type No. 101

(A23.204.R01)

Feeder bay with switch disconnector, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q2 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

C-46

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 102

(A23.204.R03)

Feeder bay with switch disconnector, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q2 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q2

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) & (Q2=0) (Q0=0) & (Q2=0) (Q0=0) & (Q1=0) (Q0=0) & (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-47

Appendix C - List of Bay Types


(continued)

Bay Type No. 115

(A23.404.R01)

Feeder bay with switch disconnector / fuse unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q2 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K A01 K A02 / / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

C-48

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 116

(A23.404.R03)

Feeder bay with switch disconnector / fuse unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q1 (DEV02) Q2 (DEV03) F (SIG_1: Signal S011) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U U A01 A02 A03 A04 A05 A06 B05

Output relay
K K K K K K / A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q1 Q2

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) & (Q2=0) (Q0=0) & (Q2=0) (Q0=0) & (Q1=0) (Q0=0) & (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q1=X) & /(Q2=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-49

Appendix C - List of Bay Types


(continued)

Bay Type No. 133

(L11.100.R01)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I)

C-50

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 553

(L11.100.R01.2)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-51

Appendix C - List of Bay Types


(continued)

Bay Type No. 134

(L11.100.R02)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X01

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X01

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

C-52

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 528

(L11.102.R01)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q15 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-53

Appendix C - List of Bay Types


(continued)

Bay Type No. 542

(L11.102.R01.2)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Q15 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & (Q15=0) & /(FctBl1=I) & /(FctBl2=I)

C-54

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 135

(L11.104.R01)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-55

Appendix C - List of Bay Types


(continued)

Bay Type No. 136

(L11.104.R02)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K / / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X01

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X01

Control O/C
Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) & (Q8=0)

C-56

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 137

(L11.104.R03)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) Q8 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q8 X01

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I) (X01=0) & (Q8=I) (Q0=0) (Q0=0) & (Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q8 X01

Control O/C
Close(d) Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(FctBl1=I) & /(FctBl2=I) (X01=0) (Q0=0) (Q0=0) & (Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-57

Appendix C - List of Bay Types


(continued)

Bay Type No. 138

(L11.116.R01)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) X02 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)

C-58

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 545

(L11.116.R01.2)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) X02 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-59

Appendix C - List of Bay Types


(continued)

Bay Type No. 139

(L11.116.R03)

Bus sectionalizer bay with circuit breaker, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) X02 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 X01 X02

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 X01 X02

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=0) (Q0=0)

C-60

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 148

(L13.200.R01)

Bus sectionalizer bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
K A01 K A02

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-61

Appendix C - List of Bay Types


(continued)

Bay Type No. 149

(L13.202.R01)

Bus sectionalizer bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q15 (DEV02) Q16 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
(Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
(Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I)

C-62

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 150

(L13.202.R03)

Bus sectionalizer bay with switch disconnector, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q15 (DEV02) Q16 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q15 Q16

Control O/C
Close(d) Close(d) Close(d)

Interlock equation
(Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) & (Q15=I) (Q0=0) & (Q16=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q15 Q16

Control O/C
Close(d) Close(d) Close(d)

Interlock equation
(Q15=0) & (Q16=0) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-63

Appendix C - List of Bay Types


(continued)

Bay Type No. 164

(L23.901.R02)

Bus sectionalizer bay with other switchgear unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q11 (DEV01) Q21 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q11 Q21

Control O/C
Open Close(d) Open Close(d)

Interlock equation
(Q11=0) (Q11=I) (Q21=0) (Q21=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-64

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 505

(Q21.100.R01)

Bus coupler bay with circuit breaker, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X0 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X0=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-65

Appendix C - List of Bay Types


(continued)

Bay Type No. 563

(Q21.133.R01)

Bus coupler bay with circuit breaker, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) X01 (DEV02) X02 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(X01=X) & /(X02=X) & /(FctBl1=I) & /(FctBl2=I)

C-66

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 205

(Q23.101.R01)

Bus coupler bay with circuit breaker, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q10 (DEV02) Q20 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K A01 K A02 / / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q10=X) & /(Q20=X) & /(FctBl1=I) & /(FctBl2=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0

Control O/C
Close(d)

Interlock equation
/(Q10=X) & /(Q20=X) & /(FctBl1=I) & /(FctBl2=I)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-67

Appendix C - List of Bay Types


(continued)

Bay Type No. 206

(Q23.101.R03)

Bus coupler bay with circuit breaker, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q0 (DEV01) Q10 (DEV02) Q20 (DEV03) Open Close(d) Open Close(d) Open Close(d)

Binary input
U U U U U U A01 A02 A03 A04 A05 A06

Output relay
K K K K K K A01 A02 A03 A04 A05 A06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q0 Q10 Q20

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q10=X) & /(Q20=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=0) (Q0=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q0 Q10 Q20

Control O/C
Close(d) Open Close(d) Open Close(d)

Interlock equation
/(Q10=X) & /(Q20=X) & /(FctBl1=I) & /(FctBl2=I) (Q0=0) (Q0=0) (Q0=0) (Q0=0)

C-68

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 171

(M11.300.R00)

Busbar measurement bay with fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
X0 (DEV01) F (SIG_1: Signal S011) Open Close(d)

Binary input
U A01 U A02 U B05

Output relay
/ / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-69

Appendix C - List of Bay Types


(continued)

Bay Type No. 172

(M11.300.R01)

Busbar measurement bay with fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
X0 (DEV01) F (SIG_1: Signal S011) Open Close(d)

Binary input
U A01 U A02 U B05

Output relay
K A01 K A02 /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-70

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 540

(M11.304.R02)

Busbar measurement bay with fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q15 (DEV01) X0 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q15

Control O/C
Close(d)

Interlock equation
(Q15=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-71

Appendix C - List of Bay Types


(continued)

Bay Type No. 173

(M11.900.R00)

Busbar measurement bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
X0 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
/ /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-72

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 174

(M11.900.R01)

Busbar measurement bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
X0 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
K A01 K A02

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-73

Appendix C - List of Bay Types


(continued)

Bay Type No. 176

(M13.312.R01)

Busbar measurement bay with fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Q15 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K A01 K A02 / / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-74

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 177

(M13.312.R02)

Busbar measurement bay with fuse unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Q15 (DEV02) F (SIG_1: Signal S011) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q15

Control O/C
Close(d)

Interlock equation
(Q15=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-75

Appendix C - List of Bay Types


(continued)

Bay Type No. 506

(M13.902.R00)

Busbar measurement bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
/ /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-76

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 233

(M15.903.R01)

Busbar measurement bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Q8 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K A01 K A02 / /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q1

Control O/C
Close(d)

Interlock equation
(Q8=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q1

Control O/C
Close(d)

Interlock equation
(Q8=0)

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-77

Appendix C - List of Bay Types


(continued)

Bay Type No. 179

(M15.903.R02)

Busbar measurement bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Q8 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q1 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) (Q1=0)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit
Q1 Q8

Control O/C
Close(d) Close(d)

Interlock equation
(Q8=0) (Q1=0)

C-78

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 188

(M23.302.R02)

Busbar measurement bay with fuse unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Q2 (DEV02) F1 (SIG_1: Signal S011) F2 (SIG_1: Signal S012) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / / A01 A02 A03 A04

U B06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-79

Appendix C - List of Bay Types


(continued)

Bay Type No. 189

(M23.312.R02)

Busbar measurement bay with fuse unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q15 (DEV01) Q25 (DEV02) F1 (SIG_1: Signal S011) F2 (SIG_1: Signal S012) Open Close(d) Open Close(d)

Binary input
U U U U U A01 A02 A03 A04 B05

Output relay
K K K K / / A01 A02 A03 A04

U B06

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q15 Q25

Control O/C
Close(d) Close(d)

Interlock equation
(Q15=I) (Q25=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-80

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 193

(M23.902.R02)

Busbar measurement bay with other switchgear unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q1 (DEV01) Q2 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-81

Appendix C - List of Bay Types


(continued)

Bay Type No. 559

(M23.904.R00)

Busbar measurement bay with other switchgear unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q15 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
/ /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-82

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 560

(M23.908.R00)

Busbar measurement bay with other switchgear unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q25 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
/ /

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-83

Appendix C - List of Bay Types


(continued)

Bay Type No. 194

(M23.912.R02)

Busbar measurement bay with other switchgear unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q15 (DEV01) Q25 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q15 Q25

Control O/C
Close(d) Close(d)

Interlock equation
(Q15=I) (Q25=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-84

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 130

(E13.901.R01)

Busbar grounding bay with other switchgear unit, single busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q15 (DEV01) Open Close(d)

Binary input
U A01 U A02

Output relay
K A01 K A02

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q15

Control O/C
Close(d)

Interlock equation
(Q15=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-85

Appendix C - List of Bay Types


(continued)

Bay Type No. 132

(E23.903.R02)

Busbar grounding bay with other switchgear unit, double busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit
Q15 (DEV01) Q25 (DEV02) Open Close(d) Open Close(d)

Binary input
U U U U A01 A02 A03 A04

Output relay
K K K K A01 A02 A03 A04

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit
Q15 Q25

Control O/C
Close(d) Close(d)

Interlock equation
(Q15=I) (Q25=I)

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

C-86

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix C - List of Bay Types


(continued)

Bay Type No. 1

(X99.901.R00)

Other bay type with other switchgear unit, without busbar

Assignment of Binary Inputs and Output Relays


Switchgear unit Binary input Output relay

Bay Interlock Equations for Operation without Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

Bay Interlock Equations for Operation with Station Interlocking


Switchgear unit Control O/C Interlock equation
Interlock equations not defined

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

C-87

Appendix C - List of Bay Types


(continued)

C-88

P132/EN M/Bc5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix D - Version History P132

D1

Version History P132 Changes Initial product release

Version P132-301-401/402/403-601 Release: 20.04.2004 P132-302-404/405/406-602 Release: 16.03.2005 Hardware

The 4-pole voltage transformer module (without current inputs for the over-/underfrequency protection variant) can now be fitted in slot 4 as an alternative. For the binary signal inputs, variants with a higher operate threshold are now available. Installation is only recommended if the application specifically requires the higher operate threshold. The new terminal connection diagrams include the new 4-pole voltage transformer module (without current inputs for the over-/underfrequency protection variant): P132.404 (for 40 TE case, pin-terminal connection) P132.405 (for 40 TE case, transformer module: ring-terminal connection; other modules: pin-terminal connection) P132.406 (for 84 TE case, ring-terminal connection)

Diagram

Software COMM1 With the IEC 60870-5-101 protocol, time stamping of signals with 7 bytes is now possible. With the IEC 60870-5-103 protocol, function types of external devices (DEVxx) are now supported as of 240 instead of 242. Time stamping of status signals from external devices has been adapted to the DNP3 protocol. Bug fixing: With the Courier protocol, a change of a communication parameter will no longer lead to a sporadic warm restart of the device. COMM1/ COMM2 COMM3 With the IEC 60870-5-103 protocol, the selection of measured operating values has been extended for the cyclic ILS telegram. Bug fixing: After a warm restart with COMM3 activated, the entry at S F M O N : H a r d w a r e e r r o r C O M M 3 (093 143) will now only occur if appropriate. The "memory function" of the monitoring signal memory can now be set. After the associated timer stage has elapsed, a renewed occurrence of a warning is processed as if it were a first occurrence. The recording duration for binary channels is now limited to 1 minute in order to prevent recording of endless events. Open-circuit monitoring of the 20 mA input and the PT 100 input has been improved.

SFMON

FT_RC MEASI

P132/EN M/Aa5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

D-1

Appendix D - Version History P132


(continued)

Version MAIN

Changes Parameters, which could previously only be set in the branch "General Functions" of the menu tree, have been transferred to the parameter subsets. MAIN: Neutr.pt. treat P S x (010 048) M A I N : H l d . t i m e d y n . p a r a m . P S x (018 009) MAIN: Bl.tim.st.IN,neg P S x (017 015) MAIN: Gen. Start. Mode P S x (017 027) MAIN: Op- rush restr. P S x (017 097) MAIN: Rush I(2*fn)/I(fn) P S x (017 098) MAIN: I> lift rush restr P S x (017 095) M A I N : S u p p r e s s s t a r t . s i g . P S x (017 054) MAIN: tGS P S x (017 005) With this enhancement it is now possible to take into account operational changes by selecting the appropriate parameter subset. The following per unit measured operating values have been added: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: MAIN: Curr. Ipos p.u. Curr. Ineg p.u. Voltage Vpos p.u. Voltage Vneg p.u. Frequency f p.u. Angle VPG/IN p.u. Load angle phi A p.u. Load angle phi B p.u. Load angle phi C p.u. Load angle phi N p.u. (009 016) (009 015) (009 018) (009 017) (004 070) (005 072) (005 073) (005 074) (005 075) (005 076)

The primary source for synchronizing the date and time can now be selected from COMM1, COMM3/PC, IRIG-B or a binary input for minute signal pulses. A backup source may additionally be selected. MAIN: Prim.Source TimeSync (103 210) MAIN: BackupSourceTimeSync (103 211) For the control functions, the user may select if a time tag is set only after debouncing (or when the first edge is detected). MAIN: TimeTagAfterDebounce (221 083) Bug fixing: The enabling or disabling of the ground protection via a binary signal input was incorrectly inverted. DTOC A fourth overcurrent stage (residual current stage) IN>>>> with an extended setting range has been integrated. Because of its extended setting range this stage always uses the residual current calculated from the three phase currents. A voltage memory has been added to the Short-Circuit Direction Determination function. In general SCDD will operate as previously with the non-faulted voltages. Now the device offers a voltage memory from which the SCDD function can obtain necessary voltage information for direction determination when 3-pole faults with a large 3-phase voltage drop have occurred. Bug fixing: The enabling or disabling of the protective signaling via a binary signal input was incorrectly inverted.

SCDD

PSIG

D-2

P132/EN M/Aa5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix D - Version History P132


(continued)

Version ARC

Changes Bug fixing: The enabling or disabling of the ARC via a binary signal input was incorrectly inverted. The DTOC negative-sequence current stage started the ARC by triggering the ARC trip time of the IDMT negative-sequence current stage. Selecting the CB assignment to an external device has been adapted to the maximum possible number of external devices. Bug fixing: The enabling or disabling of the ASC via a binary signal input was incorrectly inverted. GFDSS The setting parameters for function group GFDSS are now included in the parameter subsets and can be changed, according to operating conditions, by selecting the appropriate parameter subset. It is also possible to individually enable this function in each parameter subset. Processing of function group GFDSS now occurs with a higher priority in order to obtain reduced reaction times with less fluctuation. This is a response to the increased application of ground fault direction signaling as a tripping condition. Bug fixing: The cause for faulty or unstable directional decisions with the operate delay tVNG> set below 60 ms has been removed. Bug fixing: The operate delays LS and BS are now accurate, even with set values > 65 ms. TGFD The setting parameters for function group TGFD are now included in the parameter subsets and can be changed, according to operating conditions, by selecting the appropriate parameter subset. It is also possible to individually enable this function in each parameter subset. Bug fixing: With a sensitive setting of the current stage T G F D : I N , p > P S x it could previously occur that the self-monitoring function was triggered and would then issue the warning signal S F M O N : M o d u l e N D A C faulty. Bug fixing: When function group TGFD was enabled, TGFD decisions were issued that had previously been stored. MP The motor protection function has been extended by these per unit measured operating values: MP: Therm. Repl. MP p.u. MP: St-ups st. perm.p.u. V<> (005 071) (005 086)

ASC

The over-/undervoltage function may now be optionally operated with an enable threshold based on the minimum current monitor for the undervoltage stage V<. There are two new setting parameters to activate the operating mode for minimum current monitoring and to set the enable threshold: V<>: I enable V< PSx V<>: Op. Mode V< mon. PSx (001 155) (001 162) D-3

P132/EN M/Aa5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix D - Version History P132


(continued)

Version P<>

Changes Bug fixing: When setting a high operate value as well as a high disengaging ratio for the P< or Q< stages, an internal overflow was possible that led to a lower disengaging ratio than that which had been set. No modifications No modifications Bug fixing: When a binary I/O module (6 binary inputs & 8 output relays) was fitted in slot 12 of an 84TE case the configuration parameters for the last two output relays were hidden. Bug fixing: With the parameter L O C : L a n g u a g e set to Reference language (Am. English), the selection texts for parameter M A I N : N e u t r . p t . t r e a t . P S x (010 048) were nevertheless displayed in the Regional Language (German, French or Spanish depending on the order option). No modifications

P132-302-404/405/406-603 Release: 26.10.2005

Hardware Diagram Software OUTP

MAIN

P132-302-404/405/406-603 -701 Release: 01.03.2006

Hardware

Diagram Software DEVx (x=1 to 10) P132-303-407/408/409-610 Release: 17.07.2006 Hardware

No modifications The electric control of external devices has now received a higher priority. This results in greatly decreased triggering times with default switch control commands via the electric control. The new Ethernet communications module for communication per IEC 61850 is now available and may be fitted in slot 2 as an alternative to communication module A. For the optical interface (100 Mbit/s) on the Ethernet communications module the user may either select the ordering option ST connector or SC connector. The updated connection diagrams now include the interfaces on the Ethernet communication module. P132.407 (for 40 TE case, pin-terminal connection) P132.408 (for 40 TE case, transformer module: ring-terminal connection; other modules: pin-terminal connection) P132.409 (for 84 TE case, ring-terminal connection)

Diagram

Software DVICE Implementation of editable device identification data: D V I C E : PCS Order No. DVICE: Location LOC (001 200) (001 201)

The selection for the Operation Panel was extended by the addition of the the measured operating value M E A S I : S c a l e d v a l u e I D C , l i n (004 180).

D-4

P132/EN M/Aa5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix D - Version History P132


(continued)

Version COMM3

Changes Bug fixing: The input signal MAIN : M a n . T r i p c m d . E X T (037 018) did not operate when it was set as a receive signal for COMM3 and triggered via this communication link. Implementation of the IEC 61850 communication protocol. In conjunction with the IEC 61850 communication protocol the IECGOOSE communication procedure for the exchange of binary information within an Ethernet network section has been implemented. In conjunction with the IEC 61850 communication protocol a communication procedure has been implemented that is compatible with previous UCA2 GOOSE for the exchange of binary information within an Ethernet network section. When transmitting determined energy output values via address readout, the values "Overflow" and "Not measured" are now hidden. Designations of HSR and TDR trip times for IDMT phase, ground and negative sequence current stages have been changed to read: ARC: HSRtrip.t.Iref,P PSx ARC: HSRtrip.t.Iref,N PSx ARC: HSRtr.t.Iref,neg PSx ARC: TDRtrip.t.Iref,P PSx ARC: TDRtrip.t.Iref,N PSx ARC: TDRtr.t.Iref,neg PSx The new signal F T _ R C : R e c o r d . t r i g a c t i v e (002 002) to display a present trigger criterion has been added to the disturbance recording. Function group Circuit Breaker Monitoring (CBM) has been added. As an ordering option for the 40TE and 84TE model versions there is now a variant available with a detachable HMI. The detachable HMI is always supplied with a case width of 40TE. The detachable HMI provides 6 additional keys and LED indicators. The freely configurable LED indicators (H 4 H 16, H 18 H 23) are provided as multi-color LEDs and, depending on the trigger signal, will show red, green or amber (superpositon of red and green) light. The updated connection diagrams now include the interfaces to connect the detachable HMI and the additional LED indicators. The reset functions have been expanded: Now there are two group reset parameters available, each of which will "simultaneously" reset several memories. The assignment of eligible memories to the two group reset parameters is configurable. The group reset is now issued by a manual reset from the local control panel, and may also be created by linking it to a binary signal input or a function key. In similar fashion a selection of memories to be reset may be assigned to the CLEAR key situated on the local control panel. Now each time the CLEAR key is pressed not only the LED indicators and the display are reset but the selected memory is also reset immediately.

IEC GOOSE

GSSE

MAIN ARC

FT_RC CBM P132-304/305-412/413/414-611 Hardware Release: 16.05.2007

Diagram Software

P132/EN M/Aa5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

D-5

Appendix D - Version History P132


(continued)

Version DVICE

Changes These parameters are available in conjunction with the option "detachable HMI": DVICE: SW version DHMI DVICE: SW version DHMI DM LOC (002 131) (002 132)

This parameter is available in conjunction with the option "detachable HMI": LOC: Local HMI exists (221 099)

Six additional function keys are freely configurable. These function keys may be used to control switchgear units. Various functions may be assigned to the two colors, red and green, available with the multi-color LEDs. (Should both assigned functions be simultaneously present then the third color amber is generated.) IEC Implementation of active monitoring of the communications data links to logged-on clients with the parameter I E C : T C P k e e p - a l i v e t i m e r (104 062). This active monitoring now replaces previous passive monitoring by parameter I E C : I n a c t i v i t y t i m e r (104 050). Implementation of an automatic switchover to daylight saving time, activated by parameter I E C : S w i t c h . d a y l . s a v . t i m e (104 219). Switchover times for the automatic switch to daylight saving time are governed by the following settings: IEC: IEC: IEC: IEC: IEC: IEC: IEC: IEC: Dayl.sav.time start Dayl.sav.time st. d Dayl.sav.time st. m Dayl.sav.t.st.0:00 + Dayl.sav.time end Dayl.sav.time end d Dayl.sav.time end m Dayl.sav.t.end 0:00+ (104 220) (104 221) (104 222) (104 223) (104 225) (104 226) (104 227) (104 228)

Instead of setting a router address and target network so as to establish a communication link to a client situated exterior to the local network, only the setting of the gateway address is now required via IEC: Gateway address (104 011).

Now 'unbuffered reports' are available for all logical nodes. CBF F_KEY The complete revision of the circuit breaker failure protection function now includes a current reset criterion. The feature "Configurable Function Keys (Function Group F_KEY)" has been added.

D-6

P132/EN M/Aa5 // AFSV.12.10090 D /// P132-306-415/416/417/418/419-612

Appendix D - Version History P132


(continued)

Version P132-306 -415/416/417/418/419 -612 Release: 26.11.2007 Hardware

Changes The P132 is now available as a 24T case variant. This variant does not offer a detachable HMI, includes no function keys and is fitted with only 10 single color LED indicators (five of which are permanently assigned). In addition there is only a reduced selection of hardware modules and function groups available as compared to the larger case variants. For all three cases there is now the option of a binary output module with 4 high-break contacts. The updated terminal connection diagrams now include the connections of the new binary output module fitted with 4 high-break contacts. Also added are the terminal connection diagrams for the new 24T case variant. LOC: LOC: and LOC: LOC: F c t . a s s i g n . r e s e t (005 251) was renamed to Fct. reset key A s s i g n m e n t r e a d k e y (080 110) was renamed to Fct. read key.

Diagram

Software

IEC

I E C : D e a d b a n d v a l u e (104 051) was divided into several individual settings: IEC: Update Measurements (104 229) IEC: Dead band IP (104 230) IEC: Dead band IN (104 231) IEC: Dead band VPP (104 232) IEC: Dead band VPG (104 233) IEC: Dead band f (104 234) IEC: Dead band P (104 235) IEC: Dead band phi (104 236) IEC: Dead band Z (104 237) IEC: Dead band min/max (104 238) IEC: Dead band ASC (104 239) IEC: Dead band temp. (104 240) IEC: Dead band 20 mA (104 241) The setting I N P : F i l t e r (010 220) is now available for conformity with standard IEC 60255-22-7, class A. The setting M A I N : M e a s . d i r e c t i o n P , Q (006 096) now permits sign inversion for the display of the following measured operating values: MAIN: MAIN: MAIN: MAIN: Active Reac. Active Reac. power power power power P Q P Q prim. prim. p.u. p.u. (004 050) (004 052) (004 051) (004 053)

INP MAIN

MP CMD_1

Now the device features an hours run counter and this includes a comparison to the corresponding set upper limit. The function group Single-Pole Commands has been added.