TYPE OF LOAD RELIABILITY Climatic Load Condition : I 100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind. Climatic Load Condition : II 36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind. Normal Condition SECURITY Broken Wire Condition Normal Condition SAFETY Broken Wire Condition
Nil Component of Tensions for 50% conductor tension and 100% of ground wire tension at 320C + Nil Wind (i) Weight of all Components.
Nil Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all components. Design Weight Span : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.
Nil Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all components. Design Weight Span : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.
VERT.
(i) Weight of all components. Design Weight Span : 100% (ii) Weight of Structure.
(i) Weight of all components. Design Weight Span : 100% (ii) Weight of Structure.
Design Weight Span : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure.
WIND LONG. TENSION Nil Nil 50% of conductor tension and 100% of Ground Wire tension at 320C + Nil Wind
Nil
RELIABILITY Climatic Load Condition : I Climatic Load Condition : II Normal Condition Climatic Load Climatic Load Condition : I Condition : II 100% Wind on Structure and all other components.
SECURITY Broken Wire Condition Climatic Load Climatic Load Condition : I Condition : II Wind Span as : Broken condition : 60% Intact condition : 100% 100% Wind on 36% Wind on Structure and all Structure and all other components. other components. Component of Tensions at 320C + 100% Wind. Component of Tensions at 40C + 36% Wind Normal Condition
WIND TRANS.
Nil
Nil
TENSION
Load Case 23 : Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all Strings. Design Weight Span :
(i) Weight of all Strings. VERT. Design Weight Span : 100% (ii) Weight of Structure.
(i) Weight of all Strings . Design Weight Span : 100% (ii) Weight of Structure.
(i) Weight of all Strings. Design Weight Span : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. 100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind. 36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind
(i) 2 * Weight of Strings. Design Weight Span : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.
Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.
2 times 50% sagging tension of conductors under stringing and 1.5 times for conductors already stringed at 320C + Nil Wind
DIRN.
TYPE OF LOAD
RELIABILITY Climatic Load Condition : I Climatic Load Condition : II Normal Condition Climatic Load Condition : I 100% Wind on Structure and all other components.
SECURITY
SAFETY
Climatic Load Condition : II 36% Wind on Structure and all other components.
Broken Wire Condition Wind Span as : Broken condition : 60% Intact condition : 100% 100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind. 36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind
Normal Condition
WIND TRANS.
Nil
Nil
TENSION
Component of Tensions at 320C + Nil Wind (i) 2 * Weight of all Strings Design Weight Span as : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.
VERT.
(i) Weight of all Strings. Design Weight Span : 100% (ii) Weight of Structure.
(i) Weight of Strings etc. Design Weight Span : 100% (ii) Weight of Structure.
(i) Weight of all Strings etc. Design Weight Span as : Broken condition : 60% Intact condition : 100% (ii) Weight of Structure.
(i) 2 * Weight of all Strings Design Weight Span : 100% (ii) Weight of Structure. (iii) 150 Kg for Lineman (iv) 350 Kg at cross-arm tip.
100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind.
36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind
100% Wind on Structure and all other components. Component of Tensions at 320C + 100% Wind.
36% Wind on Structure and all other components. Component of Tensions at 40C + 36% Wind Nil Tensions at 320C + No Wind Nil