Anda di halaman 1dari 4

ITD Inline Tension Disconnect Switch

15-38 kV Hookstick Switches


Product Bulletin 1VAG201901-DB

Design Features
Insulators Silicone insulator provides extra leakage distance and BIL ratings to ensure inline switches are not the flashover point Blade Design Copper blades with stainless steel shoulder pins. Standard blade opening is 90; 160 with stop pin removed Loadbreak Hooks Galvanized steel for corrosion protection, to be used with loadbreak tool Terminal Options 1. Standard two-hole NEMA tin-plated pad 2. Optional two-piece parallel groove terminal Mounting Inline

Application
The ABB ITD Inline Tension Disconnect Switch is a single-phase, hookstick-operated switch used to manually switch de-energized or parallel circuits of overhead distribution lines rated 15 through 38 kV, 150/200 kV BIL. The ITDs are installed directly in the line and are used to sectionalize the circuit. Switches are selected by continuous current and voltage ratings.

Operation
All ABB ITD disconnect switches include loadbreak hooks. Use the appropriate loadbreak device to open the switch under load. The pullring can be utilized for easy opening and ice breaking. The hook portion of the contact-casting matches the blade latch for positive closure.

Ordering Instructions
Choose one character from each description. There should be a total of 10 characters. Description
SWITCH TYPE

Code
T 3

Definition
Type ITD Switch 38 kV, 200 kV BIL Non-Loadbreak 27 kV, 150 kV BIL Non-Loadbreak No stop 90 stop 160 stop 90 latch *** Not yet available, Call factory Two-piece tinned parallel groove clamshell (#2-500 MCM) Double eyebolt terminal (#2-350 MCM) Two-hole NEMA pad - standard Space holder for future options Space holder for future options 600 amperes 900 amperes First Design

MAX kV, BIL 5 N A BLADE STOP B C C TERMINAL CONNECTORS D N UNUSED UNUSED N N 6 CONTINUOUS CURRENT 9 DESIGN SUB 000

Example: To purchase a standard non-loadbreak ITD Inline Tension Disconnect Switch, the catalog code would be: T1NNNN6000

-2-

Type ITD Unit Dimensions

A B
.630 DIA CLEVIS PIN COTTER KEY

INSULATOR SHED DESIGN WILL VARY, SHED MAX DIA WILL BE 3.75

.62 [16]

.63 [16] 1.25 [32]

1.75 [44]

.690 DIA HOLE

3.16 [80]

ACCEPTS 1/2" BOLTS

.63 [16]

.56 [14]

C D

kV Class
15 & 27 15 & 27 38

BIL (kV)
150 200 200

A
17.0 21.7 21.7

Unit Dimensions (in) B C


12.5 17.2 17.2 17.0 21.7 21.7

D
28.0 32.7 32.7

Dry Arc
11.4 min 15.2 min 15.2 min

kV Class
15 & 27 15 & 27 38

BIL (kV)
150 200 200

Metric Unit Dimensions (mm) A B C D


432 551 551 318 437 437 432 551 551 711 831 831

Dry Arc
11.4 min 15.2 min 15.2 min

AVAILABLE RATINGS Description


Non-loadbreak

Maximum Voltage
15 38 kV

BIL (kV)
150/200

Continuous Current
600, 900 A

Peak Withstand Current


65 kA

Description
Non-loadbreak Non-loadbreak Non-loadbreak

Maximum Voltage
15 kV 27 kV 38 kV

BIL (kV)
150 150 200

Creep (in)
23.2 23.2 33.5

Strike (in)
10.5 10.5 15.0

-3-

ABB Inc. 406 Banner Ave. Greensboro, NC 27401 Tel: +1-336-275-7310 www.abb.com/mediumvoltage

1VAG201901-DB Rev. B October 2005 Copyright 2005 ABB. All rights reserved.