Anda di halaman 1dari 4

Easy to Use

ERL
XR351

e ici Eff

Ele ga nt

Trip Circuit Supervision Relay

nt

Description
Type XR relay has been developed for specific applications, and suitable for use with type AR relay range. It is an electro mechanical relay with a consistent positive action, a long service life and complying with the appropriate requirements of IEC 60255. The XR351 has three attracted armature elements. It incorporates a time delay on de energisation, to keep the relay in an operated condition, during temporary reduction in the battery voltage

Features
Low burden Versatile design Preclose supervision Consistent positive action Epsilon drawout case

Applications
Supervision and ensuring the integrity of the trip circuit of a breaker Continuous supervision, during both, open and closed position of circuit breaker Preclosing supervision to prevent circuit breaker from being closed where the trip relay has not been reset

ERL

XR 351 Item code: XR_09448 Sl No: HR 1010534 Rating 110V DC

Trip Circuit Supervision Relay XR351

Wiring Diagram

LOOKING ON FRONT OF RELAY

3 5 7 9

R3
23

R4

6 8 10

B
24

27

R5
19

R6

A
20

C
28

R2

R1

Typical Wiring Diagram SCHEMATIC DIAGRAM CONTACTS (2M2B) SHOWN UNDER DE-ENERGISED CONDITION TRIP SUPPLY

86

52a

TC
52b

19
R5

20

23
R3 R4

24

ALARM SUPPLY

R6

A
27 8 7 4 3

B C
R2 R1

28 10 9 6 5

R DEPENDS UPON TRIP & ALARM SUPPLY VOLTAGE

Technical Information
Rated Voltage, Vn Temperature Operating Range Reset Time Burden Rated Voltage 30V DC 48V DC 110V DC 220V DC Thermal Withstand Trip Circuit Condition C.B. Open 1W 1W 1W 2W C.B. Closed 1W 1W 2W 4W Alarm Circuit 2W 2W 4W 9W 1.2Vn continuously 30V, 48V, 110V, 220V DC IEC60068-2-1&2 80% to 120% of Vn 400 ms when supply is switched form Vn to off

Environmental Temperature Storage Operating Humidity

IEC 60068- 2- 1 & 2 - 250 C to + 700 C - 100 C to + 550 C IEC 60068-2-3 56 days at 95% RH and 400 C

Vibration IEC 60255-21-1 Relay meets the requirements vibration of class 1 for response and endurance. Shock and Bump IEC 60255-21-2 Relay meets the requirements with respect to shock & bump testing for class 1 severity. Transient Over voltage IEC 60255-5 5KV 1.2/50s 0.5 joules between all terminals and earth or between any two terminals without damage or flashover. Insulation IEC 60255-5 2KV rms for 1 minute between all terminals and earth. 1KV rms for 1 minute across normally open contacts Operational / Mechanical life The relays will withstand in excess of 10,000 operations, within the maximum contact loading specified, at a rate of 600 operations per hour.

Indication Hand reset flag Contact Arrangement Alarm output, 4 in any combination of normally open and normally closed. Pre close supervision, 1 normally open. Contact Rating Make and carry continuously 1250VA AC or 1250W DC with limits of 660V and 5A Make and carry for 3 seconds 7500VA AC or 7500W DC with limits of 660V and 30A Break 1250VA AC or 100W DC (resistive) or 50W (inductive) (L/R=0.04) DC with limits of 250V and 5A

Cutout Details
+0.5 -0 4 - 4 HOLES

Ordering Information
Rated voltage Contact arrangement

Rating V DC A 30 48 110 220

Coil Resistance in Ohms B 400 400 4800 4800 C 450 1572 1572 1572 2000 2000 3100 R1 R2

Resistors value in Ohms R3 100 350 2300 2300 7000 R4 R5 100 350 2300 2300 7000 R6

400 400 4800 4800

These resistors are supplied loose with the relays for non drawout case. It is important to ensure that the resistors are correctly connected.

Qualification
CASE SIZE E4 W 9.50 DIMENSION X Y 97.00 78.00

ISO 9001 2008

Note : 1. All dimensions are in mm 2. All dimensions are measured equidistant from centre line 3. Maximum depth of equipment inside panel : 225mm
The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may differ slightly from that described and illustrated in the publication.

ERL Group Corporate Office #389, Rasukumaki, Hulimavu, Begur Hobli, Bannerghatta Road, Bangalore 560 076, India Tel: +91 80 6717 7000 Fax: +91 80 6717 7002 Email: cenmarket@easunreyrolle.net

Global Marketing Offices Germany, Canada, Hong Kong, Thailand, South Africa, UAE, Brazil, Peru & USA

Global Technology Centers India, Canada & Germany

Marketing Offices in India


Bangalore
Tel: +91 80 6717 7000/01 Fax: +91 80 6717 7002 Email: cenmarket@easunreyrolle.net

Chennai Bhopal
Fax: +91 755 2684221 Email: bhopal@easunreyrolle.net Tel: +91 44 2434 6425/7608 Fax: +91 44 2434 6435 Email: chennai@easunreyrolle.net

Kolkata
Tel: +91 33 2284 8320 Fax: +91 33 2284 8326 Email: kolkata@easunreyrolle.net

Mumbai

Noida

Tel: +91 22 2285 54415/ 2202 2270 Tel: +91 120 2405 741/42/43 Fax: +91 22 2285 5703 Fax: +91 120 2405 744 Email: mumbai@easunreyrolle.net Email: noida@easunreyrolle.net

Secunderabad
Tel: +91 40 2781 7847 Email: hyderabad@easunreyrolle.net

ERL

www.easunreyrolle.com

FACT/XR/09-10/REV1.0

Global Manufacturing Centers India, Canada & Germany

Anda mungkin juga menyukai