Operating values
8. Operating values
The operating values in this instruction apply to SF6 circuit-breaker LTB 72,5-245E1 with operating mechanism BLK 222.
8.1 Times
Closing times Opening time coil I Opening time coil II Close-Open time(1)
< 28 ms 17 2 ms 17 2 ms 26 3 ms
(1) The Close-Open time refers to the time the main contacts are closed during a closing operation when a tripping pulse is simultaneously connected via the auxiliary contact.
Charging time for motor Operating voltage opening coil I Operating voltage opening coil II Operating voltage closing coil I Operating voltage closing coil II
max 15 s V (according to the rated data plate) V (according to the rated data plate) V (according to the rated data plate) V (according to the rated data plate)
8.3 Resistance
Main circuit resistance per pole max 49 .
1HYB800001-044 Rev.B
31