Doc. No.

Ver: 4.03 Rev: 1

Modbus RTU & Modbus ASCII

FS-8700-01 FS-8700-08

DESCRIPTION

The Modbus RTU and Modbus ASCII drivers allow the FieldServer to transfer data to and from devices using Modbus RTU or Modbus ASCII protocol respectively. Data can be transferred over either RS-232 or RS-485. The driver was developed for Modbus Application Protocol Specification V1.1a" from Modbus-IDA. The specification can be found at www.modbus.org. The FieldServer can emulate either a Server or Client. There are various register mapping models being followed by various vendors To cover all these models FieldServer uses the following three Models Modicon_5digit Use this format where addresses are defined in 0xxxx, 1xxxx, 3xxxx or 4xxxx format. A maximum of 9999 registers can be mapped of each type. This is FieldServer drivers default format. ADU Application Data Unit address. Use this format where addresses of each type are defined in the range 1-65536 PDU Protocol Data unit address. Use this format where addresses of each type are defined in the range 0-65535.

The key difference between ADU and PDU is for example if Address_Type is ADU and address is 1, the driver will poll for register 0. If Address_Type is PDU, the driver will poll for address 1. Note 1: If vendor document shows addresses in extended Modicon (i.e. 6 digit) format like 4xxxxx then consider these addresses as xxxxx (just omit the first digit) and use either ADU or PDU Note 2: The purpose of providing 3 different ways of addressing the Modbus registers is to allow the user to choose the addressing system most compatible with the address list being used. At the protocol level, the same protocol specification is used for all three with the exception of the limited address range for Modicon_5digit.

FieldServer Mode Client Server

Nodes 1 255

Comments Only 1 client node allowed on Multidrop systems Actual electrical loading may reduce number of usable server nodes

FORMAL DRIVER TYPE

Serial Client or Server

COMPATIBILITY MATRIX
Compatible with this driver Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoNode QuickServer FS-QS-1010 QuickServer FS-QS-1011 ProtoCessor FPC-FO2 ProtoCessor FPC-FD2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 4

Doc. No.

Ver: 4.03 Rev: 1

Modbus RTU & Modbus ASCII

FS-8700-01 FS-8700-08

CONNECTION INFORMATION
Connection type: Baud Rate: Data Bits Parity Multidrop Capability: RS-232 or RS-485 (Two wire, Half-Duplex) 110 115200, standard baud rates only 7, 8 Even, Odd, None Yes

DEVICES TESTED
Tested (FACTORY, SITE) Factory Factory Customer Customer Customer Factory Factory Customer Factory Factory Customer Customer Customer Factory Customer

Device Modbus RTU Devices Modbus ASCII Devices Liebert Sitelink Square D Activar 58 Triatek WonderWare InTouch Fix Intellution GE Cimplicity Modscan GE PLEPM ABB Extrel Andover Controls Eurotherm Chessel Sierra Monitor Sentry Magnatek Many more

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 4

Doc. No.

Ver: 4.03 Rev: 1

Modbus RTU & Modbus ASCII

FS-8700-01 FS-8700-08

CONNECTION CONFIGURATIONS

8917-01 WIRE LIST DB25M FUNCTION RX CTS DSR GND GND DTR RTS TX FROM RJ45-01 RJ45-02 RJ45-03 RJ45-04 RJ45-05 RJ45-06 RJ45-07 RJ45-08 TO COLOUR DB25M-03 WHITE DB25M-05 BROWN YELLOW DB25M-07 GREEN RED BLACK DB25M-04 ORANGE DB25M-02 BLUE

8917-04 WIRE LIST DB25F Typical DB9/DB25 kit assemblies are shown here. Refer to the third party device literature for exact configuration required. FUNCTION RX CTS DSR GND GND DTR RTS TX FROM RJ45-01 RJ45-02 RJ45-03 RJ45-04 RJ45-05 RJ45-06 RJ45-07 RJ45-08 TO COLOUR DB25F-02 WHITE DB25F-04 BROWN YELLOW DB25F-07 GREEN RED BLACK DB25F-05 ORANGE DB25F-03 BLUE

8917-03 WIRE LIST DB9M FUNCTION RX CTS DSR GND GND DTR RTS TX FROM RJ45-01 RJ45-02 RJ45-03 RJ45-04 RJ45-05 RJ45-06 RJ45-07 RJ45-08 TO DB9M-02 DB9M08 DB9M-06 DB9M-05 DB9M-04 DB9M-07 DB9M-03 COLOUR GREY BROWN YELLOW GREEN RED BLACK ORANGE BLUE

DB9F

8917-02 WIRE LIST FUNCTION FROM Rx RJ45-01 GND RJ45-04 Tx RJ45-08 TO DB9F-03 DB9F-05 DB9F-02 COLOUR WHITE GREEN BLUE

RJ45 Connector

Connect to 2-wire RS-485 network

OR

RJ45 to EIA232 Connector

(408)-262-2299

FIELDSERVER MODBUS RTU or MODBUS ASCII CONNECTION DIAGRAM


BASE NAME: FILE NAME: DATE: 2/5/07 BY: MC

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 4

Doc. No.

Ver: 4.03 Rev: 1

Modbus RTU & Modbus ASCII

FS-8700-01 FS-8700-08

7 7.1

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: Function Codes Supported:


Description Read Discrete Output Status (0xxxx) Read Discrete Input Status (1xxxx) Read Output Registers (4xxxx) Read Input Registers (3xxxx) Force Single Coil (0xxxx) Preset Single Register (4xxxx) Force Multiple Coils (0xxxx) Preset Multiple Registers (4xxxx)

Function Codes 01 02 03 04 05 06 15 16

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 4