The Ingress Protection (IP) for all low voltage enclosures up to 1000 V a.c. and 1500 V d.c. is defined in identical fashion by the standards EN 60529 IEC 529 it comprises the letters IP followed by two character numerals: The first character numeral indicates the degree of protection provided by the enclosure with respect to persons, also to the equipment inside the enclosure. The second character numeral indicates the degree of protection provided by the enclosure with respect to harmful ingress of water; a third character may be used to indicate mechanical strength. An x signifies that no test has been carried out.
The first character numeral Protection against solid substances. IP 0 1 Test Short description Non-Protected Protected against solid objects greater than 50mm 50 mm Definition No special protection. A large surface of the body, such as a hand (but no protection against deliberate access) solid objects exceeding 50mm in diameter Fingers or similar objects not exceeding 80mm in length; solid objects exceeding 12.5 mm in diameter
The second character numeral Protection against liquid substances. IP 0 1 Test Short description Non-Protected Protected against dripping water Definition No special protection. Dripping water (vertically falling drops) shall have no harmful effect
Vertically dripping water shall have no harmful effect when the enclosure is tilted at any angle up to 15 from its normal position Water falling as a spray at an angle up to 60 from the vertical shall have no harmful effect
3 3 Protected against solid objects greater than 2.5mm 2,5 mm Tools, wires, etc...., of diameter or thickness greater than 2.5mm; solid objects exceeding 2.5 mm in diameter 4 Protected against solid objects greater than 1.0mm 1 mm Wires or strips of thickness greater than 1.0mm; solid objects exceeding 1.0 mm in diameter
Water splashed against the enclosure from any direction shall have no harmful effect
Dust-protected
Ingress of dust is not totally prevented but dust does not enter in sufficient quantity to interfere with satisfactory operation of the equipment No ingress of dust
Water projected by a nozzle against the enclosure from any direction shall have no harmful effect Water from heavy seas or water projected in powerful jets shall not enter the enclosure in harmful quantities
Dust-tight
15 cm
Ingress of water in a harmful quantity shall not be possible when the enclosure is immersed in water under defined conditions of pressure and time The equipment is suitable for continuous submersion in water under conditions which shall be specified by the manufacturer
330
331
Invicta
Incoming -
Incoming -
Outgoing -
Outgoing -
H125 MCCBs 4 way 6 way 8 way 12 way Maximum Prospective Short-circuit level at point of application with
16 to 125A
H125 MCCBs 16 to 125A H250 MCCBs 160 to 250A 6 way 8 way 12 way 18 way Maximum Prospective Short-circuit level at point of application with Incomer Incomer Incomer Incomer Incomer Incomer Incomer main terminals - outgoing H125 main terminals - outgoing only H250 non-auto MCCB - outgoing H125 non-auto MCCB - outgoing only H250 H400 MCCB - outgoing H125 H400 MCCB - outgoing only H250 H800 MCCB - outgoing only H250 15kA 40kA 15kA 40kA 25kA 35kA 50kA
Incomer - main terminals - outgoing H125 Incomer - non-auto MCCB - outgoing H125 Incomer - H400 MCCB - outgoing H125 Table 1
332
All dimensions are in mm and exclude the handle. Add 70mm to the depth to allow for the handle (110mm for 630 / 800A) Table 4
Cable Extension Boxes for Fuse Combination Switches Cat Ref. JZA701 JZA702 JZA703 Rating 125 / 250A 315 / 400A 630 / 800A Height 200 250 300 Width 375 500 600 Depth 200 300 350
333
Invicta
334 100A A4 800 8000 8000 A B 100 100 A B 250 250 ** ** 125 150 2x125 160 160 220 220 355 355 ** ** A B 315 315 A B 400 400 A B 630 630 A B 800 800 51 45 55 60 75 63 80 100 800 8000 8000 A B 125 125 800 800 12000 12000 A B A B 160 160 200 200 800 800 800 1000 1000 125A B1-B2 160A 200A B1-B2 B1-B2 B1-B3 250A B1-B3 315A B1-B4 400A C1-C2 630A* C1-C3 800A* 50 100 50 125 50 160 50 200 50 250 50 315 50 400 50 630 50 800 800 1000 1250 1600 2000 2500 3150 1000 1280 1600 2000 2520 3200 4000 ** ** ** ** 10,000 9 9 9 20 ** 10,000 10,000 10,000 10,000 10,000 10,000 20 8000 20 8000 ** 40 40 25 95 TCP100 95 TF125 95 TF160 35 50 70 240 TF200 70 240 TKF250 185 240 TKF315 185 240 TMF400 2x150 2x300 TTM630 2x150 2x300 TLM800
20A A1
32A A1
63A A2-A3
15
30
15
45
25
50 20
50 32
50 63
160
256
500
200
320
630
20,000
20,000
10,000
Thermal current Ith (40C) Fuse size: BS Rated insulated voltage Ui (V) Impulse voltages Uimp Operational current Ie (A) 415V ac AC-22A/AC-23B Motor power (kW) 400V ac Reactive power 400V ac (kVAR) Overload capacity Short-circuit with fuses (kA Rms) Fuse rating (A) BS88 Making & breaking Characteristics Breaking capacity 400V AC-23B (A Rms) Making capacity 400V AC-23B (A Rms) Withstand mechanical (Number of operations) Electrical (Number of operations) Tightening torque Connection Minimum Cu Cable section (mm2) Maximum Cu Cable section (mm2) Fuse types
2.5
2.5
10
16 NIT20
16 NIT32
25 TIS63
* 630A AC22B making and breaking * 800A ** Please call our technical support helpine for these details Table 5
Switch Disconnectors
Switch Disconnectors Cat Ref. JAB302 JAB303 JAB306 JAB310 JAC312 JAC316 JAE320 JAE325 JAG331 JAG340 JAH363 JAH380 JAB402 JAB403 JAB406 JAB410 JAC412 JAC416 JAE420 JAE425 JAG431 JAG440 JAH463 JAH480 Table 7 All dimensions are in mm and exclude the handle. Add 70mm to the depth to allow for the handle Description 20A TPN 32A TPN 63A TPN 100A TPN 125A TPN 160A TPN 200A TPN 250A TPN 315A TPN 400A TPN 630A TPN 800A TPN 20A TPSN 32A TPSN 63A TPSN 100A TPSN 125A TPSN 160A TPSN 200A TPSN 250A TPSN 315A TPSN 400A TPSN 630A TPSN 800A TPSN Height 250 250 250 250 300 300 400 400 500 500 650 650 250 250 250 250 300 300 400 400 500 500 650 650 Width 200 200 200 200 250 250 375 375 375 375 500 500 200 200 200 200 250 250 375 375 375 375 500 500 Depth 150 150 150 150 150 150 200 200 200 200 300 300 150 150 150 150 150 150 200 200 200 200 300 300 Cable Extension Boxes for Switch Disconnectors Cat Ref. JZA700 JZA701 JZA702 Rating 125 / 160A 315 / 400 630 / 800 Height 200 200 250 Width 250 375 500 Depth 200 300 300
335
Invicta
336 32 32 32 32 63 63 63 63 100 100 100 100 125 125 125 125 160 125 160 125 160 125 160 125 250 250 200 125 250 250 200 125 250 250 200 125 630 500 500 315 800 800 800 800 1.26 0.256 1.8 8 100,000 16 4 50 4 50 9 50 9 95 9 95 20 150 20 185 20 100,000 100,000 10,000 10,000 10,000 10,000 10,000 5,000 240 20 1.5 0.504 2.1 8 1.5 0.64 2.1 8 7 1 20 11.9 8 7 1.28 20 11.9 8 7 1.28 18 11.9 8 9 2 30 15.3 8 9 2 23 15.3 8 9 2 23 15.3 8 13 5.04 45 26 12 5,000 2x300 26 6.4 55 54.6 12 5,000 2x300
Enlosed thermal current lthe Rated insulation voltage Ui (V) Rated Thermal current Ithe (A)
20 800 20
32 800 32
63 800 63
500VAC
690VAC
20 20 20 20
Overload capacity Icw Rated Short time withstand value R.M.S. value Peak withstand value Rated short circuit making capacity Rated impulse withstand voltage Uimp
Mechanical endurance
100,000
16 2
Table 9
Switch Disconnectors
Description 10A TPN 16A TPN 25A TPN 40A TPN 63A TPN 80A TPN
All dimensions are in mm and exclude the handle. Add 27mm to the depth to allow for the handle on 10-25A products. Add 32mm to the depth to allow for the handle on 40-80A products.
Enclosed thermal current Ithe Rated insulation voltage Ui (V) Rated thermal current Ithe (A) Rated operational current AC-21 400V AC-22 230V AC-22 400V AC-23 230V AC-23 400V Rated operational power AC-23 230V AC-23 400V Rated fused short circuit current Back-up fuse (A) R.M.S. value Ik (kA) Peak value (kA) Rated short circuit making capacity (Icm) (kA) Rated short-time withstand current (Icm) (kA) Rated breaking capacity Icn (A) AC-23 400V Electrical endurance (number of operations) Mechanical endurance (number of operations) Terminals mm2 Max. thermal torque (Nm) Table 9a
16 690 25 Ie (A) cos phi 0.65 cos phi 0.35 (kW) 25 16 16 16 16 4 7.5 63 50 5.4 6.6 1 250 3000 50000 1.5-16 1.8
25 690 40 40 25 20 20 15 5.5 11 63 50 6.6 7.2 1.1 270 3000 50000 1.5-16 1.8
40 690 63 63 40 32 32 25 7.5 15 63 50 7.2 8.3 1.6 320 3000 50000 1.5-16 1.8
504
2.3-35 2.5
337
Invicta
Fuse-Switch
A switch in which one or more poles have a fuse carrier/link which forms the moving contact.
The definitions of these two basic types of fuse combination units have now been extended to include units suitable for making, breaking and isolation and units which are only suitable for providing isolation for maintenance work.
Symbol
Disconnector Fuse
Fuse Disconnector
However, in order to keep the selection of fuse-combination units as simple as possible, Hager offer a range of high performance double break switch-fuses, which also satisfy the isolating requirement of the European standard. These are correctly shown as and defined as a Fuse Combination Switch. Switch disconnectors - EN 60947-3. A range of switch disconnectors (isolators) are available for use on lower current ratings from 20A to 125A, these switches are rated at AC-22 and provide a cost effective alternative to the fuse combination switch especially where the utilisation category AC-23 is not required. ie; mixed resistive and inductive loads. These may be used at AC-23 providing they are derated in accordance with Table 9 page 336.
338
Cat Ref. JG25M JG26M JG27M JG27R JG28M JG29M JG30M JG31M JG32M JG33M JG33R JG34S JG35S JG36M JG37M JG37R JG40M JG41M JG41R JG42S JG43S JG44M JG45M JG45R JG46S JG47S JG48M JG49M JG50S JG51S All sizes are in mm Table 3
Description 63A SPN 63A TPN 63A 4P 63A 4P + RCCB 100A SPN 100A TPN 100A 4P 125A SPN 125A TPN 125A 4P 125A 4P + RCCB 125A TPN non auto MCCB 125A 4P non auto MCCB 160A TPN 160A 4P 160A 4P + RCCB 250A TPN 250A 4P 250A 4P + RCCB 250A TPN non auto MCCB 250A 4P non auto MCCB 400A TPN 400A 4P 400A 4P + RCCB 400A TPN non auto MCCB 400A 4P non auto MCCB 630A TPN 630A 4P 630A TPN non auto MCCB 630A 4P non auto MCCB
L 70mm 70mm 70mm 70mm 70mm 70mm 70mm 70mm 70mm 70mm 70mm 70mm 70mm 120mm 120mm 120mm 120mm 120mm 120mm 120mm 120mm 240mm 240mm 240mm 240mm 240mm 2x240mm 2x240mm 2x240mm 2x240mm
N M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10 M10
Height 420 420 420 420 420 420 420 420 420 420 420 420 420 660 660 768 660 660 768 660 660 870 870 1000 870 870 1130 1130 1130 1130
Width 267 267 267 369 267 267 267 267 267 267 369 267 267 334 334 334 334 334 334 334 334 384 384 384 384 384 509 509 509 509
Depth 83 83 83 83 83 83 83 83 83 83 83 83 83 97 97 97 97 97 97 97 97 117 117 117 117 117 157 157 157 157
339
Invicta
Invicta Enclosures
1 row boxes 1-5 modules This range is ideally suited for the installation of individual modular devices. (RCCBs, MCBs, RCBOs switch disconnectors etc). The range is available without door, with plain door or with glazed door. Where larger cables need to be accommodated for switch disconnectors etc extra cabling space is provided in the extended height versions. All boxes from 2-5 modules are fitted with an earth bar as standard and for those with doors the catch can be replaced with the optional key locking facility. Enclosures 8-66 modules One, two or three row enclosures, fitted with DIN rails to accept any combination of Hager modular devices from the simplest switch and MCB arrangements to the more sophisticated control and protection system. These enclosures feature: Ample wiring space Full complement of earth and neutral bars fitted as standard Significant knockout provision Plain or glazed doors Optional key lock For dimensional information see 342
Description
1 1 1 1 1 1 1
1 2 2 3 4 4 5
T T T T T T T
extended height extended height 1 x 100A Isolator, AC22A Connection capacity: 50mm2 rigid conductor 35mm2 flexible conductor 1 x 63A Fuse 1 x 100A Isolator, AC22A Connection capacity: 50mm2 rigid conductor 35mm2 flexible conductor 1 x 100A Fuse
IU2/GD
*IU44/GD
IU4-16
IU41
IU44-11
Note: Recommended maximum cable capacity * extended height = 35mm2 all other references = 6mm2 IU41-11 1 row 8 T with knockouts 1 row 12 T with knockouts 1 row 16 T with knockouts 1 row 22 T with knockouts JK016G 2 row 24 T (2 x 12) with knockouts 2 row 32 T (2 x 16) with knockouts 2 row 44 T (2 x 22) with knockouts JK024 JK032 JK044 JK024G JK032G JK044G JK008 JK012 JK016 JK022 JK008G JK012G JK016G JK022G
JK066
JK066G
340
Invicta Enclosures
Versatile modular design The modern design of Invicta enclosures, allows great versatility in circuit design. This coupled with the extensive range of modular circuit protection control and energy management devices available from Hager offers the circuit designer the facility to match the distribution board precisely to the installation requirements without compromise.
Description
Cat. Ref.
Accessories keylock with 2 keys suitable for all enclosures fitted with door - IU enclosure JK enclosure
IKL1 JK222A
100A 2 pole switch disconnector JK222A 63A 30mA 2 pole RCCB 100A 30mA 2 pole RCCB 100A single module terminal block (MCB profile)
CDC263U
341
Invicta
115mm 61.5mm earth only 115mm 87.5mm earth only 125mm 73.5mm earth only 125mm 99.5mm earth only 80mm 80mm 125mm 115mm 61.5mm 100mm 99.5mm 61.5mm earth earth earth earth only only only only
342
1 pole, 1I step brown insulation (phase) KB 063P blue insulation (neutral) without insulation KB 163N insulated 10 10 10 20 20 2 poles, 2I step insulated KB 263A 10 10 16 63A 63A 80A 12I 24I 56I 10 10 10 KB 263A KB 263C KB 280B 63A 63A 63A 100A 100A 13I 13I 13I 57I 24I 50 50 50 10 10 KB 063P KB 163N KB 163I KB 190B KB 190C
KB 190C
3 poles, 3I step insulated 10 10 KB 363A 10 16 16 4 poles, 4I step insulated KB 463A 16 16 80A 80A 12I 56I 25 10 KB 480A KB 480B 10 10 63A 63A 12I 24I 10 10 KB 463A KB 463C 63A 80A 80A 24I 12I 57I 10 25 10 KB 363C KB 380A KB 380B 63A 63A 12I 57I 10 20 KB 363A KB 363B
Cable connectors connection from top In 63A for cables : 25 mm for cables : 2 x 16 mm connection from side In 63A KF 81A KF 82A for cables : 25 mm 10 10 10 KF 81A KF 82A KF 83A
End cap cover for single pole busbars KB 163P and KB 163N KF 83A for double pole busbars, 10mm for triple pole busbars 10 or 16mm KZ 021 KZ 023 343 for four pole busbars 10 or 16mm 1 set KZ 021
Connection Systems
10 10 16 16 20
12 T 56 T 12 T 56 T 56 T
100 50 100 50 10
2 pole, 2 T step KDN 263A insulated 10 10 16 3 pole, 3 T step KDN 363A insulated 10 10 10 16 16 4 pole, 4 T step KDN 463A insulated 10 10 16 16 Cable connectors connection from top In 63A for cables : 25 mm for cables : 2 x 16 mm connection from side In 63A KF 81A KF 82A End cap cover for double pole busbars, 10mm for triple pole busbars 10 or 16mm KZN 023 for four pole busbars 10 or 16mm 1 set KZ 024 1 set 1 set KZ 022 KZ 023 for cables : 25 mm 10 KF 83A 10 10 KF 81A KF 82A 63A 63A 80A 80A 12 T 24 T 12 T 56 T 10 10 25 10 KDN 463A KDN 463C KDN 480A KDN 480B 63A 63A 63A 80A 80A 12 T 57 T 24 T 12 T 57 T 10 20 10 25 10 KDN 363A KDN 363B KDN 363C KDN 380A KDN 380B 63A 63A 80A 12 T 24 T 56 T 10 10 10 KDN 263A KDN 263C KDN 280B
344
2x16 + 2x10 4 connections length 30mm 4x16 + 4x10 8 connections length 30mm 3x16 + 4x10 7 connections length 49mm 5x16 + 5x10 10 connections length 67mm KM 07N 5x16 + 6x10 11 connections length 73mm 2x16 (double drive) + 8x10 10 connections length 69mm 6x16 +7x10 13 connections length 85mm
KM 04L
20
KM 08L
50
KM 07N
KM 07E
KM 07L
10
K 142
KM 08L
20
KM 10A
KM 10B
KM 10C
10
K 143
20
KM 11N
KM 11E
KM 11L
10
K 144
20
KM 10N
KM 10E
KM 10L
10
K 145
KM 10E
20
KM 13N
KM 13E
10
K 148
KM 13N
KM 11B
1x25 +5x16 + 5x10 11 connections length 85mm 1x25 +8x16 + 8x10 17 connections length 121mm 1x25 +11x16 + 13x10 25 connections length 169mm 1x25 +8x16 + 29x10
20
KM 11B
10
K 151
20
KM 17N
KM 17E
10
K 156
KM 25N
20
KM 25E
10
K 158
K 151
K 158 1x25 + 3x16 + 129x10 supports for K140 to K162 terminals insulating material M4 x 8 fixing screws
long length length 242mm terminals (without support) fixing on the length 482mm flat bar 12 x 2 with supports (see below) length 992mm blue support for neutral green / yellow support for earth beige supports (see below)
10
K 159
10
K 160
10 10 10 10 50
K 159
KZ 014 KZ 060
KZ 012 Rail clip for fixing terminals on DIN rail not for : KM 08L KM 10A, KM 10B, KM 10C, KM 10N, KM 10E, KM 10L mounting on DIN rail
KZ 060
horizontally 345
Designation
Characteristics
Width in 17.5mm
Pack qty.
Cat. ref.
20
K 018
10
K 023
K 024
K 018
l. 121 x h. 50 x w. 62mm 5 poles l. 150 x h. 50 x w. 62mm Connection blocks connection : incoming : 2 x 35 4 separate outgoing ways : 25 1 pole l. 37 x h. 30 x w. 47mm 2 10 K 037 8 5 K 025
K 025
K 037
346
Terminal blocks fixing by clip on DIN rail delivered with : insulated back plate transparent protection front cover KJ 01B In : by 40C
In 100A two poles Icc : 29KA connectors on each terminal : incoming : 1x35 flexible, outgoing : 1x25 + 10x16 flexible w. 129 (7.5 T) x h. 86 x d. 44 mm
In 80A four poles Icc : 21KA connectors on each terminal : incoming : 1x16 flexible, outgoing : 8x10 flexible w. 88 (5 T) x h. 86 x d. 44 mm In 125A four poles Icc : 29KA connectors on each terminal : incoming : 1x35 flexible, outgoing : 1x25 + 10x16 flexible w. 129 (7.5 T) x h. 86 x d. 44 mm
KJ 01B
KJ 01C
KJ 01C
In 125A four pole Icc : 29KA connectors on each terminal : incoming : 1x35 flexible, outgoing : 1x25 + 10x16 flexible KJ 02E w. 129 (7.5 T) x h. 86 x d. 44 mm connection capacity per block : 125 A : (width 27mm) incoming : 1x35 outgoing : 6x16 + 1x165 ,
KJ 02E
KJ 02D
modular distribution blocks monobloc, insulated protection for each phase terminal. Cover removable with a tool.
KJ 01D modular Distribution blocks single pole monobloc, insulated, grey colour fixing by clip on DIN rail
In 160A four poles Icc : 20KA connectors on each terminal : incoming : 4x50 flexible, outgoing : 3x35 , 8x16 flexible w. 162 (9.5 T) x h. 87 x d. 60 mm (modular shoulder measurement 45mm) connection capacity per block 160A (width 35mm) incoming : 1x70 , outgoing 6x16 250 A : incoming : 1x95, outgoing :2x25, 5x16, 4x10 35 mm
KJ 01D
KJ 02C
45 mm
KJ 02A
45 mm
KJ 02B
25 mm
KR 95P
KR 95P
KR 15P 347
Connection Systems
31 mm
KR 15P
Connections of the distribution blocks : terminals q.connect screw in 1.5 at 25 mm2 1.5 at 4 mm2 5 8 KN 06P 11 14 17 KN 22N 20 1 2 3 4 5 6
Pack. qty
Ref Neutral KN 06N KN 10N KN 14N KN 18N KN 22N KN 26N Phase KN 06P KN 10P KN 14P KN 18P KN 22P KN 26P Earth PE KN 06E KN 10E KN 14E KN 18E KN 22E KN 26E
KN 26E
Designation
Caracteristics
Ref.
Cables for tap-off between 2 Quick Connect Terminals To connect 2 terminals each other.
for
KN 99P/N/E
Earth terminals
VZ 711
VZ 710
Quick connect for terminal supports. The supports are suitable for all the terminals range (neutral, phase and earth) Choice of the support according to the enclosure range.
GZ 30A Terminals universal support Support fixing on 12x2 mm bars on horizontal or vertical DIN rail KN 00A length : 105 mm Pre-cut support to fit with the terminal size KN 00A
KN 04N KN 07N
KN 07N
Phase terminals : Clip on the terminals support (VZ 711, VZ 710, GZ 30A et KN 00A) KN 04P 348
4 x 25 mm2 7 x 25 mm2
KN 04P KN 07P
Terminals
B Terminals dim. in mm 44.5 58 76 dim. in mm 48.5 51.5 79 Connecting terminals from 0.5 to 70 mm2 great resistance to leakage current KC >600 mounting on DIN rail uniform dimensions reduce number of accessories complies to IEC 60947-1 good tightening capacity, also suitable for two conductors conductor guilded directly into terminals connector guiding of screwdriver via embedded screws screws run idle when untightening, very important with electric screwdrivers all parts located in the terminal fixed
0.5 at 6 1.5 at 50 70 A
Designation
In / A
Width in mm
Ref. Phase
Neutral
Earth PE
Phase terminals grey Neutral terminals blue Earth PE terminals green / yellow automatic earthing of the rail
24 32 57 76 125 192
5 6 10 12 16 24
KX 04F
KX 04H
Caracteristics
Width in mm
Ref.
for the terminals: 1.5 KX 04F/N KX 06F/N 1.5 KX 16F/N KX 25F/N 2 KX 50F/N KW 031 KW 026 KW 025
KW 033
10
KW 034
KW 033
KW 035
KX 06F/N
KW 036
KX 16F/N
KW 037
Connection Systems
KW 001
KW 001 349