FIRE EXTINGUISHING 111A Date Page ENGINE AND PUMPROOM FIXED SYSTEM 30.08.

06 1 of 6 Issued by Approved by
APPLICABILITY

Paul Jones Trevor Smith


ALL SHIPS

HIGH EXPANSION FOAM SYSTEM FOR THE ENGINE ROOM AND PUMP ROOM MODEL: KASHIWA COMPANY LIMITED a) b) High expansion Foam System makes full use of its extinguishing ability and has following effects:

Isolating Effect: the system will generate a large quantity of foam, isolate the area on fire from other areas to prevent fire from expanding and extinguish in short time. Cooling Effect: Water included in generated foam liquid can cool the heat in the area on fire and decrease the atmospheric temperature for better extinguishment. This system consists of following parts: a) Foam GENERATOR: This consists of a spray nozzle, body and generating net. When the system is running seawater and foam mix goes to the generator and is sprayed toward the net. Air is drawn in from the generator inlet and foam is produced at expansion ratio of 1:600.

FOAM GENERATOR IN PUMPROOM

b) MIXING UNIT: The foam liquid is mixed with the seawater in an eductor. The foam liquid is drawn through a Diaphragm Control valve placed in the piping of the foam liquid. This valve is used to obtain a constant flow and mixing ratio.

FIRE EXTINGUISHING 111A Date Page


c)

ENGINE AND PUMPROOM FIXED SYSTEM 30.08.06 2 of 6 CONTROL PANEL: This panel controls the remote operation of the system from Fire Control Station. Note: There is another same panel located in High Expansion Foam Room for starting the system, in case it fails to operate from Fire Control Station.

Issued by Approved by
APPLICABILITY

Paul Jones Trevor Smith


ALL SHIPS

AUTOMATIC OPERATION FOR AN ENGINE ROOM FIRE a) When fire is detected in Engine Room break acrylic plate and press the SYSTEM STANDBY button on the control panel at the ENGINE ROOM side. The emergency stop system will be operated with the sounding of alarm in the Engine Room. b) Start the Emergency Fire Pump from the start switch on the Control Panel.
c)

STANDBY BUTTON

Press the FOAM DISCHARGE button on the control panel. As soon as seawater pressure rises above 5Kg/cm2, the Foam Liquid pump

STARTING BUTTONS OF HIGH EXP FOAM SYSTEM FOR ENGINE ROOM LOCATED ON THE CONTROL PANEL

FOAM DISCHARGE BUTTON starts, the seawater valve AV1 and foam liquid suction valve AV2 are opened. As soon as foam liquid pressure rises above 5Kg/cm2, the discharge valve is opened and foam is discharged through the foam generators.

FIRE EXTINGUISHING 111A Date Page ENGINE AND PUMPROOM FIXED SYSTEM 30.08.06 3 of 6 Issued by Approved by
APPLICABILITY

Paul Jones Trevor Smith


ALL SHIPS

AUTOMATIC OPERATION FOR A PUMPROOM FIRE a) When fire is detected in Pump Room break the plastic cover and press the SYSTEM STANDBY button on the control panel at the PUMP ROOM side. The emergency stop system will be operated with the sounding of alarm in the Pump Room. b) Start the Emergency Fire Pump from the start switch on the Control Panel.
c)

Press the FOAM DISCHARGE button on the control panel. As soon as seawater pressure rises above 5Kg/cm2, the Foam Liquid Pump starts, the seawater valve AV1 and foam liquid suction valve AV2 are opened. As soon

STANDBY BUTTON STARTING BUTTONS OF HIGH EXP FOAM SYSTEM FOR PUMP ROOM LOCATED ON THE CONTROL PANEL

FOAM DISCHARGE BUTTON as foam liquid pressure rises above 5Kg/cm2, the discharge valve is opened and foam is discharged through the foam generators.

FIRE EXTINGUISHING 111A Date Page ENGINE AND PUMPROOM FIXED SYSTEM 30.08.06 4 of 6 Issued by Approved by
APPLICABILITY

Paul Jones Trevor Smith


ALL SHIPS

VIEW OF HIGH EXPANSION FOAM ROOM IN POOP DECK (PORT SIDE)

MANUAL OPERATION OF THE HIGH EXPANSION FOAM SYSTEM FROM FOAM ROOM Discharge To The Engine Room: a) Start the emergency fire pump. b) When the discharge pressure is 5 kg/cm manually open AV1 and AV2.

c) Start the foam pump. d) When the pressure on the foam discharge line is 5 kg/cm manually open AV3, AV4, AV5 and AV6. e) Foam will now be discharged to the engine room. Discharge To The Pump Room: a) Start the emergency fire pump. b) When the discharge pressure is 5 kg/cm manually open AV1 and AV2. c) Start the foam pump. d) When the pressure on the foam discharge line is 5 kg/cm manually open AV 7 and AV 8. e) Foam will now be discharged to the pump room.

FIRE EXTINGUISHING 111A Date Page ENGINE AND PUMPROOM FIXED SYSTEM 30.08.06 5 of 6 Issued by Approved by
APPLICABILITY

Paul Jones Trevor Smith


ALL SHIPS

CLOSE-UP VIEW OF AN AUTOMATIC VALVE


To Open Manually: Press the blue knob on top and turn in anticlockwise direction.

SHOWN ABOVE ARE AUTOMATIC VALVES -AV3, AV4, AV5, AV6, AV7 AND AV8 IN THE HIGH EXPANSION FOAM ROOM

FIRE EXTINGUISHING 111A Date Page ENGINE AND PUMPROOM FIXED SYSTEM 30.08.06 6 of 6 Issued by Approved by
APPLICABILITY

Paul Jones Trevor Smith


ALL SHIPS

HIGH EXPANSION FOAM PUMP SCHEMATIC DIAGRAM OF THE HIGH EXPANSION FOAM SYSTEM