Anda di halaman 1dari 2

INTERFACE Relay

CONTACTRON Power electronics Electronic reversing load relay with motor management The electronic load relays with motor management (ELR-MM) combine fast, wearfree semiconductor switches and state-ofthe-art measurement with evaluation electronics. Every 6.6 ms, the effective power consumed by the electric drives is calculated from the three currents, voltages and the phase angle. This allows continuous status monitoring. Message and switching thresholds for recognizing underload and overload can be freely parameterized and carry out functions that far exceed normal motor protection. All relevant electrical values such as apparent, effective and reactive power, currents, voltages and phase angles, as well as the values of the internal cycle and operating hour counter can be read off the display. The ELR-MM load relay switches actuating and regulating drives, pumps and tools and at the same time checks them for function, contamination or wear. The ELR-MM EX device is particularly suitable for use in the chemicals and petrochemicals industry. A corresponding Ex type-examination certificate has been issued. Alternatively, the devices can be coupled to fieldbus systems via a defined interface for online monitoring.
Notes: Type of housing: Polycarbonate PC, color: green. For marking systems and mounting material, see CLIPLINE catalog.

H W D

ELR W3/9-400 MM
Electronic reversing load relay, with motor management

P
Parameterization

24V DC UIN 1/L1 3/L2 5/L3 2/T1 4/T2 6/T3

Screw connection

stranded [mm2] AWG 0.2-6 0.2-4 24-10

solid

I [A]

U [V]

O1 O2 O3 O4
L 24V DC

Logic Feedback

24V DC
R

&
Alarm

Memory

RS232

Serial

Description Electronic reversing load relay, with motor management

Type

Order No.

Pcs. / Pkt.

ELR W3/ 9-400 MM Technical data Input data Supply nominal voltage UVN Supply voltage range with reference to UVN Quiescent current Control voltage UST right/left Control voltage range in reference to UST Typ. input current at UN Input circuit Operating voltage / status / error indicator Output data for confirmation contacts O1 - O4 in the case of 1 signal Output data load side Output voltage range Periodic peak reverse voltage Load current Surge current Min. load current Residual voltage Leakage current Output protection General data Test voltage input/output Reversing frequency Ambient temperature range Standards/regulations Power station requirements EMC regulations Degree of protection in acc. with IEC 60529/ EN 60529 Mounting position Assembly Dimensions Safety data EU type-examination certificate in acc. with ATEX Requirement class in acc. with DIN V 19251 Category in acc. with EN 954-1

2963514

24 V DC 0.8 ... 1.2 80 mA 24 V DC 0.8 ... 1.2 5 mA Polarity protection, surge protection LED green / LED yellow / LED red (U VN - 1 V) / Max. 50 mA 110 V AC ... 433 V AC 1000 V 8 A (see derating curve) 360 A (tp = 10 ms, @ 25C) 150 mA Typ. 1.4 V Typ. 4 mA RC element, surge protection 2.5 kV Max. 2.5 Hz (at cos = 0.5) -20C ... 60C DIN EN 50178 DWR 1300 / ZXX01/DD/7080.8d EN 61000-6-2 / EN 61000-6-4 IP20 Panel mounting on horizontal DIN rail Can be aligned with > 20 mm spacing 62 mm / 122 mm / 94 mm

Load current [A]

8 7 6 5 4 3 2 1 0 10 20 30 40 50 60

W/H/D

Ambient temperature [C] Load current as a function of the ambient temperature Operating time: 100% operating factor

160

PHOENIX CONTACT

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370 Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

INTERFACE Relay
CONTACTRON Power electronics
H W D H W D

ELR W3/...-500 MM
Electronic reversing load relay, with motor management

ELR W 3/9-500 MM EX
Electronic reversing load relays with motor management and ATEX approval

Ex: X p
Parameterization Parameterization

24V DC UIN 1/L1 3/L2 5/L3 2/T1 4/T2 6/T3

24V DC UIN 1/L1 3/L2 5/L3 2/T1 4/T2 6/T3

O1 O2 O3 O4
L

Logic Feedback

O1 O2 O3 O4
L

Logic Feedback

24V DC 24V DC
R

&
Alarm

24V DC
Memory

RS232

24V DC
Serial R

&
Alarm

Memory

RS232

Serial

Type

Order No.

Pcs. / Pkt.

Type

Order No.

Pcs. / Pkt.

ELR W3/ 2-500 MM ELR W3/ 9-500 MM

2982621 2963543

1 1

ELR W3/ 9-500 MM EX

2963695

ELR W3/ 2-500 MM ELR W3/ 9-500 MM 24 V DC 24 V DC 0.8 ... 1.2 0.8 ... 1.2 80 mA 80 mA 24 V DC 24 V DC 0.8 ... 1.2 0.8 ... 1.2 0.8 ... 1.2 0.8 ... 1.2 Polarity protection, Polarity protection, surge protection surge protection LED green / LED yellow / LED red (UVN - 1 V) / Max. 50 mA 110 V AC ... 550 V AC 1500 V 1.8 A (see derating curve) (UVN - 1 V) / Max. 50 mA 110 V AC ... 550 V AC 1500 V 8 A (see derating curve)

24 V DC 0.8 ... 1.2 80 mA 24 V DC 0.8 ... 1.2 0.8 ... 1.2 Polarity protection, surge protection LED green / LED yellow / LED red (UVN - 1 V) / Max. 50 mA 110 V AC ... 550 V AC 1500 V 8 A (see derating curve) 360 A (tp = 10 ms, @ 25C) 150 mA Typ. 1.4 V Typ. 7 mA RC element, surge protection 2.5 kV Max. 2.5 Hz (at cos = 0.5) -20C ... 60C DIN EN 50178 DWR 1300 / ZXX01/DD/7080.8d EN 61000-6-2 / EN 61000-6-4 IP20 Panel mounting on horizontal DIN rail Can be aligned with > 20 mm spacing 62 mm / 122 mm / 94 mm

360 A (tp = 10 ms, @ 25C) 360 A (tp = 10 ms, @ 25C) 150 mA 150 mA Typ. 1.4 V Typ. 1.4 V Typ. 7 mA Typ. 7 mA RC element, surge protection 2.5 kV Max. 2.5 Hz (at cos = 0.5) -20C ... 60C DIN EN 50178 DWR 1300 / ZXX01/DD/7080.8d EN 61000-6-2 / EN 61000-6-4 IP20 Panel mounting on horizontal DIN rail Can be aligned with > 20 mm spacing 62 mm / 122 mm / 94 mm

X II (2) GD
PTB 03 ATEX 3114 AK4 3

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370 Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PHOENIX CONTACT

161

Anda mungkin juga menyukai