MS 930 CODE OF PRACTICE FOR THE INSTALLATION OF

FUEL GAS PIPING SYSTEM AND APPLIANCES

SKOP PEMAKAIAN MS 930


MS 930 adalah kod keselamatan yang digunapakai kepada perpasangan sistem perpaipan bahan api gas, peralatan penggunaan bahan api gas dan aksesori yang berkaitan.
Bahan api gas termasuklah Gas Asli,Gas Buatan,Gas Petroleum Cecair fasa wap, campuran Gas Petroleum Cecair dan udara serta campuran diantara gas-gas ini.

MS 930

SKOP PEMAKAIAN MS930


Dari titik penghantaran* ke penyambungan setiap peralatan penggunaan gas. *LPG keluaran daripada pengatur tekanan peringkat pertama. *Selain LPG keluaran daripada meter servis atau keluaran daripada pengatur tekanan servis atau injap penutupan servis. Tekanan operasi maksimum sistem perpaipan; 420 kPa (gauge) = 60 psig 70 kPa (gauge) = 10 psia. Hanya terpakai untuk campuran bahan api gas dan udara yang berada didalam julat kebolehbakaran

MS 930

SKOP PEMAKAIAN MS930


M Internal Piping > 20 psig
Equipment Appliances

Service Station

M T r a n s m i s s I o n L I n e

Internal Piping 20 psig

Equipment Appliances

Service Station
RESIDENTIAL

Odorizer City Gate Feeder Line 260 psig Distribution Line 60 psig Internal Piping M 300 Meter mmH Area Station 20 M

DS

District Station

M Multiple Endusers

M M M

MS 930

Internal Piping 3000 mmH20

Single Development

Service Station

COMMERCIAL

NAT. GAS DISTRIBUTION SYSTEM

Internal Piping 3000 mmH20 Regulating Station

SKOP PEMAKAIAN MS930


Premises Boundary

Public Road

Customers Premises

House Regulat or 2

Gas Meter 3 4 Gas Cock

Ground Level 1

Distribution Line

MS 930

SKOP PEMAKAIAN MS930


3

5st F

Pipe Shaft
3

4st F

Premises Boundary

3st F Public Road Customers Premises


3

2st F Service Regulator or 2 House Regulator Ground Level


3

Meter

1st F

Distribution Line

MS 930

SKOP PEMAKAIAN MS930 Sistem perpaipan termasuklah; design,materials,components,fabrication,assembly, installation,testing,operation and maintenance.

Perkakasan penggunaan gas dan aksesori termasuklah; installation,combustion and ventilation air and venting.

MS 930

SKOP PEMAKAIAN MS930


MS 930 tidak terpakai kepada: 1. Perkakasan LPG boleh ubah yang tidak disambung kepada sistem perpaipan bahan api. 2. Pemasangan peralatan ladang 3. Sistem kimpalan dan pemotongan Oxy-fuel

MS 930

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Piping Plan Sebelum memulakan perpasangan sistem perpaipan gas,kita harus menyediakan lakaran perpaipan atau plan perpaipan yang menunjukan cadangan lokasi perpaipan, saiz bagi cabang yang berbeza, jumlah gas yang perlu dihantar kesetiap peralatan dan lokasi pusat penghantaran. Sekiranya membuat penyambungan pada sistem perpaipan yang sedia ada, kita perlu memastikan sistem perpaipan sedia ada mampu menampung kapasiti kepada penyambungan yang dibuat.Sekiranya tidak mampu kita perlu membesarkan sistem perpaipan yang sedia ada atau membuat pepasangan baru yang lain. Provision for location of point of delivery Lokasi pusat penghantaran haruslah boleh diterima oleh pihak pembekal gas.

Interconnection between gas piping system Apabila 2 atau lebih meter ATAU apabila 2 atau lebih pengatur tekanan servis ditempatkan pada premis yang sama DAN menghantar gas kepada pengguna yang berlainan, maka penyambungan tidak boleh dibuat pada sebelah hilir keluaran meter atau pengatur tekanan servis.
MS 930 8

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Piping system operating pressure limitations Tekanan rekabentuk operasi maksimum untuk sistem perpaipan yang ditempatkan di dalam bangunan harus tidak melebihi 35 kPa (gauge) [5 psig] MELAINKAN dibenarkan oleh ST dan memenuhi SATU atau LEBIH keadaan berikut: 1. sistem perpaipan adalah dikimpal 2. perpaipan adalah ditempatkan di dalam ventilated chase atau enclosed for protection againt accidential gas accumulation 3. The piping is located inside buildings or separate areas of buildings used exclusively for; a. industrial processing or heating b. research c. warehousing d. boiler or mechanical equipment rooms 4. perpaipan adalah perpasangan sementara untuk bangunan sedang dalam pembinaan
MS 930 9

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Sistem perpaipan untuk campuran gas dan udara yang berada didalam julat kebolehbakaran adalah dihadkan kepada tekanan maksimum 70 kPa (gauge) [10 psig] Tekanan rekabentuk operasi maksimum untuk sistem LPG [undiluted LPG] seharusnya tidak boleh melebihi 140 kPa (gauge) [20 gauge] except for buildings or separate areas of building used exclusively to house industrial processes, research and experimental laboratories, or equipment or processing having similar hazards.

MS 930

10

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Acceptable piping materials and joining methods Paip, gegasan, injap atau lain-lain bahan tidak harus diguna semula melainkan ianya bebas daripada bendasing. Lain-lain bahan yang spesifikasinya tidak dinyatakan dalam MS 930 hendaklah mendapat kelulusan ST setelah mendapat recommended tentang penggunaanya oleh pembuatnya. Cast-iron pipe shall not be used Steel and wrought-iron pipe shall be at least of standard weight (schedule 40) or equivalent and shall comply with one of the following standard; MS 862, MS 863, ANSI B36.10, ANSI/ASTM A53, ANSI/ASTM A106 and ANSI/ASTM A120

MS 930

11

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Gas pipe or tubing and fittings shall be clear and free from cutting burr and defects in structure or threading and shall be thoroughly brushed and chip and scale blown. Defects in pipe or tubing or fittings shall not be repaired. When defects in pipe,tubing or fittings are located in a system the defective material shall be replaced Metallic pipe and fitting threaded shall be taper pipe threads and shall comply with ANSI B2.1[standard for pipe threads] Threaded pipe in sizes larger than 100mm (4in) shall not be used unless acceptable by ST Pipe joint shall be threaded, flanged or welded

MS 930

12

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Table 1. Specifications for threading metallic pipe

Iron pipe size mm (inches)


15 (1/2) 20 (3/4) 25 (1) 32 (11/4) 40 (11/2) 50 (2) 65 (21/2) 80 (3) 100 (4)

Approximate length of threaded portion mm


20 20 22 25 25 25 40 40 42
MS 930

Approximate number of threads to be cut


10 10 10 11 11 11 12 12 13
13

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Gas meters - Gas meter shall be properly selected for the maximum expected pressure and permissible pressure drop. - Gas meter shall be located in ventilated spaces readily accessible for examination, reading, replacement or necessary maintenance. - Gas meter shall not be placed where they will be subjected to damage. - Gas meter shall not be located where they will be subjected to extreme temperature or sudden extreme change temperature. - Gas meter shall be protected against overpressure, backpressure and vacuum if necessary. - Gas meter shall be located at least 0.9 meter from the sources of ignition. - Gas meter shall be securely supported. - Gas piping at multiple meter installations shall be plainly marked by a metal tag or other permanent means attached by the installing agency, designating the building or the part of the building being supplied.

MS 930

14

SECTION 4 GAS PIPING SYSTEM DESIGN, MATERIAL AND COMPONENTS


Gas pressure regulators - The gas pressure regulator location shall be such that the connections are readily accessible for servicing. - Pressure regulator shall be protected or so located against accidental damage. - An adequately sized independent vent to the outside of the building shall be provided when the line pressure regulator at its location is such that a ruptured diaphragm will cause a hazard. - The vent shall be designed to prevent the entry of water, insects or other foreign materials that could cause blockage. - A line pressure regulator shall not be vented to the gas equipment flue or exhaust system. - Identification as meter identification. - LPG second stage regulator shall comply ANSI/UL 144.
MS 930 15

SECTION 6 GAS PIPING STALLATION


Piping under ground - Underground gas piping shall be installed with enough clearance from any other underground structure. - Piping shall be buried a sufficient depth or covered in a manner so as to protect the piping from physical damage. - underground piping shall be installed with at least 450 mm of cover. The cover may be reduced to 300 mm if external damage to the pipe not likely to result.If a minimum 300 mm of cover cannot be maintained, the pipe shall be installed in conduit or bridged (shielded) - Gas piping in contact with earth or other material which may corrode the piping, shall be protected against corrosion in an approved manner. - Connection between metallic and plastic pipe shall be made only outside, underground and with approved transition fitting.

MS 930

16

SECTION 6 GAS PIPING STALLATION

Underground gas piping

150 mm

300 mm

Other buried facilities Cross layout distance

Parallel layout distance

MS 930

17

SECTION 6 GAS PIPING STALLATION

300 Warning Tape

150

Copper Gas Sand


450

FIG. 8

PIPING BURIED IN GROUND OR UNDER CONCRETE EXTERNAL OF BUILDING

MS 930

18

SECTION 6 GAS PIPING STALLATION


PIPE PENETRATING THROUGH SOLID WALL OR FLOOR

Non-Metallic Pipe Sleeve

Gas Bare Copper Pipe

Brick/ R.C. Wall

FIG. 5 PIPE PENETRATING THROUGH SOLID WALL OR FLOOR

MS 930

19

SECTION 6 GAS PIPING STALLATION


PIPING EMBEDDED IN CONCRETE FLOOR
R.C. Slab Reinforcement Bars Copper Pipe Gas

MIN. 40 mm

FIG. 7 PIPING EMBEDDED IN CONCRETE FLOOR


MS 930 20

SECTION 6 GAS PIPING STALLATION


Above ground piping outside - Piping installed above ground shall be securely supported and located where it will be protected from physical damage. - When passing through an outside wall, the piping shall also be protected against corrosion by coating or wrapping with an inner material. - When piping is encased in a protective pipe sleeve, the annular space between the gas piping and the sleeve shall be sealed at the wall to prevent the entry of water, insects or rodents.

MS 930

21

SECTION 6 GAS PIPING STALLATION


Above ceiling location. Gas piping may be installed in accessible above ceiling space. The gas pipe must be welded.Valve shall not be located in such space. Prohibited location Gas piping inside any building shall not be run in or through a circulating air duct, clothes chute, chimney, gas vent, ventilating duct, enclosed staircase, elevator shaft.

MS 930

22

SECTION 6 GAS PIPING STALLATION


Hanger, support and anchors pipe support example: pipe hook, metal pipe straps, brackets.
Steel Pipe Nominal Size of Pipe (Inches) 1/2 Spacing of Supports (Feet) 6 Nominal Size of Tubing (Inch OD) 1/2 Spacing of Supports (Feet) 4

3/4 or 1 1 1/4 or larger (horizontal) 1 1/4 or larger (vertical)

8 10

5/8 or 3/4 7/8 or 1 (Horizontal)

6 8

Every floor lavel

1 or larger ( verical)

Every floor lavel

MS 930

23

SECTION 6 GAS PIPING STALLATION


Outlet The outlet shall not be place behind doors. The unthreaded portion of gas piping outlets shall extend not less than 25mm through finished ceiling or indoor or outdoor walls. The unthreaded portion of gas piping outlets shall extend not less than 50mm above the surface of floors or outdoor patios or slabs.

MS 930

24

SECTION 7 INSPECTION, TESTING AND PURGING


A piping system may be tested as a complete unit or in sections as the construction progresses. Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, unless two valves are installed in series with a valve tell-tale located between these valves. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve closing mechanism, is design to withstand the test pressure.

MS 930

25

SECTION 7 INSPECTION, TESTING AND PURGING Test Medium The test medium shall be air or inert das (e.g nitrogen, carbon dioxide). OXYGEN SHALL NEVER BE USED. Fuel gas may be used in piping systems, operating at pressure of 3.5 kPa gauge (0.5 psig) or less. Test pressure Pressure shall be measured with pressure measuring device and calibrated as to read,record and indicated pressure loss due to leakage during the pressure test period.The source of pressure shall be isolated before the pressure tests are made.
MS 930 26