Anda di halaman 1dari 74

Student CD for Commercial Refrigeration for A/C Technicians Chapter 5 Metering Devices

Learning Objectives
Understand TEVs and cap tubes How they meter refrigerant to the evaporator How to size metering devices How system pressures and temperatures affect metering devices How superheat is affected by TEVs and cap tubes Metering device problems and troubleshooting
Copyright 2006 Thomson Delmar Learning

Metering Devices
Feed refrigerant to evaporator Provide a pressure drop
From the condensing pressure to the evaporator pressure
From a condensing temperature higher than the ambient, to one lower than the box temperature

Provide a temperature drop

The following slide is a cut-away view of a Thermostatic Expansion Valve (TEV)


Copyright 2006 Thomson Delmar Learning

Valve Construction: Diaphragm, tube, and sensing bulb Valve body Needle and orifice Inlet Screen Spring, adjuster, and packing gland

Valve Construction

Copyright 2006 Thomson Delmar Learning

TEV Operation
Meters refrigerant Maintains superheat Opening force:
Bulb pressure

Closing forces:
1. Evaporator pressure

2. Adjustable spring

Copyright 2006 Thomson Delmar Learning

Expansion Valve Detail Typical Walk-in using R22

Copyright 2006 Thomson Delmar Learning

Review of How Evaporators Absorb Heat


Refrigerant enters as liquid droplets Warm air causes droplets to boil Heat is absorbed into refrigerant
Called latent heat

Refrigerant becomes saturated vapor Now it can only absorb sensible heat
Called superheat

Copyright 2006 Thomson Delmar Learning

Evaporator Section of R22 Reach-in Refrigerator

Evaporation Starts Total Superheat

Fully Evaporated (Saturated)

Coil Superheat

Copyright 2006 Thomson Delmar Learning

Measuring Superheat
Superheat =
Coil outlet temperature - Evaporator temperature Superheat too high :
Starving

Superheat too low:


Flooding

The following picture shows where to take the coil outlet temperature.

Copyright 2006 Thomson Delmar Learning

Schrader fitting on suction line

Suction line is about 18

Clamp-on thermistor at TEV bulb

Suction pressure is 36 psig

R404A at 36 psig is 3

18- 3 = 15 superheat
Taking superheat at the evaporator of a walk-in freezer
Copyright 2006 Thomson Delmar Learning

10

Adjusting Superheat
To lower superheat:
Decrease spring pressure Increases refrigerant in evaporator

Copyright 2006 Thomson Delmar Learning

11

Lower Superheat from 10 to 6

Superheat Adjustment

More refrigerant in the evaporator

Copyright 2006 Thomson Delmar Learning

12

Adjusting Superheat
Increase superheat:
Increase spring pressure Decreases refrigerant in evaporator

Copyright 2006 Thomson Delmar Learning

13

Raise Superheat from 6 to 14

Less refrigerant in the evaporator

Copyright 2006 Thomson Delmar Learning

14

Identifying the Valve


Connections:
Flare, sweat, and flanged

Evaporator Pressure Equalization:


Internal equalizer External equalizer

Copyright 2006 Thomson Delmar Learning

15

Expansion Valve Connections


Flanged Flare Sweat

External equalizer

Internal equalizer External equalizer

Copyright 2006 Thomson Delmar Learning

16

Multi-circuit Evaporator
Multiple circuits create a large pressure drop An external equalized TEV is required
It senses pressure at the evaporator outlet

What happens if an internal equalized TEV is used on a multi-circuit evaporator?


The following slides answer this question

Copyright 2006 Thomson Delmar Learning

17

Internal Equalized TEV on multi-circuited evaporator

External equalizer line

Distributor and tubes

Copyright 2006 Thomson Delmar Learning

18

Multi-Circuit Evaporator with an Internal Equalized TEV 35 Walk-in, R22


49 psig TEV senses normal pressure for 25 evap.

Bulb sensing 35 suction line thinks it is maintaining 10 superheat (35 - 25)

TEV is not fully feeding evaporator, superheat rises.

280 psig 49 psig 35 psig pressure drop in distributors 35

Hey, Im starvin here!

15 psig

2 psig drop in coil 13 psig R22 @ 13 psig = -15 35 - (-15) = 50 Actual Superheat

High superheat verifies starving evaporator

Copyright 2006 Thomson Delmar Learning

19

Install proper TEV


External equalized TEVs sense evaporator outlet pressure
Suction pressure rises as the evaporator is filled with refrigerant The TEV will remain open until the suction pressure rises at the evaporator outlet

Copyright 2006 Thomson Delmar Learning

20

Multi-Circuited Evaporator with External Equalized TEV


Only 13 psig under diaphragm allows TEV to open.
Valve opens until it senses 49 psig under diaphragm.

TEV properly feeds evaporator. 35

Thats more like it!

R22 @ 49 psig = 25

49 psig 13psig

35 - 25 = 10 Superheat

Copyright 2006 Thomson Delmar Learning

21

Sensing Bulb Placement


Must sense true suction temperature Not bottom of pipe Not top of pipe
Following are Sporlans recommendations

Copyright 2006 Thomson Delmar Learning

22

Factory Recommended TEV Bulb Placement

Copyright 2006 Thomson Delmar Learning

23

Factory Recommended TEV Bulb Placement

< 7/8

If pipe OD is less than (<) 7/8 then bulb can be placed anywhere between 8:00 and 4:00 . . . but never on the bottom!
Copyright 2006 Thomson Delmar Learning

24

Simplifying bulb location


The next slide shows a simple rule for bulb placement

Copyright 2006 Thomson Delmar Learning

25

Rule of Thumb TEV Bulb Placement


Warmer vapor on top

Oil insulates bottom Bulb mounted on side works well on all pipes

Copyright 2006 Thomson Delmar Learning

26

TEV Bulb Mounted on the Side of the Suction Line

Copyright 2006 Thomson Delmar Learning

27

More suggestions on bulbs


Make sure it is on a flat surface of pipe Use stainless steel hose clamps:
Easier to install Easy to service

Copyright 2006 Thomson Delmar Learning

28

Bulb cannot sense line temperature TEV Bulbs

Straps

Picture of bulbs and clamps


Coupling Braze Joints

No Bulb Contact

Radiato r Clamp Good Bulb Contact


Copyright 2006 Thomson Delmar Learning

29

More on Mounting TEV Bulbs


Best on horizontal line If you must put on vertical line:
Oil in line may affect operation Cap tube must come out top of bulb

Copyright 2006 Thomson Delmar Learning

30

TEV Bulb on Vertical Line


Mount bulb with tubing at the top.

Remember: Use vertical suction line only if no horizontal location is available.


Copyright 2006 Thomson Delmar Learning

SPORLAN
31

TEV Bulb on Vertical Line

Oil pushed up sides of pipe affects heat transfer.

SPORLAN

System Off Oil collects in P-trap


Copyright 2006 Thomson Delmar Learning

Start Up

32

TEV Bulb Mounted Upside Down


Liquid Flows to Head of Valve

No Liquid In Bulb to Boil Off

SPORLAN
Copyright 2006 Thomson Delmar Learning

33

How the System Affects TEVs


High pressure drop increases valve capacity High liquid temperature decreases valve capacity These factors offset each other to maintain a fairly consistent valve capacity

Copyright 2006 Thomson Delmar Learning

34

TEV Correction Factors


High pressure increases valve capacity But high liquid temperature decreases valve capacity

Outdoor Ambient A

Condensing Temperature

Head Pressure C

Evaporator Pressure D

Pressure Drop (C - D)

Correction Factor for Pressure Drop

Correction Factor for Liquid Temperature

Overall Correction Factor

(E x F)

100 70 50

130 100 80

300 psig 200 psig 150 psig

50 psig 50 psig 50 psig

250 psig 150 psig 100 psig

1.40 1.10 .90

.80 1.00 1.15

1.10 1.10 1.05

Copyright 2006 Thomson Delmar Learning

35

Reading a Valve

All TEV manufacturers have a specific numbering system. If you understand the numbering system you will know the valve. The following slide have examples of Sporlan valves:

Copyright 2006 Thomson Delmar Learning

36

Picture of SVE-2-GA valve

S style valve
V R22 E externally equalized

2 Two Tons (24,000 Btu)


G Air Conditioning
Copyright 2006 Thomson Delmar Learning

37

Picture of GV-1/2-C Valve

G type valve V R22

1/2 ton (6,000) Btu


C Commercial (medium temp.)
Copyright 2006 Thomson Delmar Learning

38

Sporlan Numbering System

Following is a chart that describes the more common Sporlan numbers

Copyright 2006 Thomson Delmar Learning

39

SPORLAN TEV NUMBERING SYSTEM


SPORLAN TEV NUMBERING SYSTEM

Body Flare/Sweat Style (Blank) = Flare F S or E = Sweat G BF Q "Others"

Tonnage Refrigerant Equalized 12,000 btu/Ton F = R12 E = External 1/4 = 3,000 btu (Blank)=Internal 1/3 = 4,000 btu V = R22 R = R502 1/2 = 6,000 btu J = R134a 3/4 = 9,000 btu S = R404 1 = 12,000 btu

Application C = Medium Temp (Comm) Z = Low Temp (freeZer) P = Pressure Limiting Valve G = A/C

TYPE "F"
(No Letter)

Example: FJE-1-C
E External ?
1 12,000 ? btu C Medium ? Temp

Flare ?

J R134a ?

TYPE "G"
E
Extended ? Sweat

Example: EGVE-3/4-C
E External ? 3/4 9,000 ? btu C Medium ? Temp

V R22 ?

Copyright 2006 Thomson Delmar Learning

40

Sporlan Type F Chart


1. The first thing to determine is the type of valve (flare, solder, equalized, etc.) 2. Then the tonnage 3. Then the application (A/C, freezer, commercial temperature, etc.) 4. Sometimes there is a wide range between available TEVs (1/2 ton to 1 ton)

Copyright 2006 Thomson Delmar Learning

41

SPECIFICATIONS

ELEMENT SIZE NO. 43, KNIFE EDGE JOINT


TYPE EF ODF Solder

Sporlan Type F Chart

1
REFRIGERANT (Sporlan Code)

TYPE F SAE Flare External Equalizer FVE-1/5 FVE-1/3 FVE-1/2 FVE-1 FVE-1-1/2 FVE-2 FVE-3 FJE-1/8 FJE-1/6 FJE-1/4 FJE-1/2 FJE-1 FJE-1-1/2 FJE-2 FSE-1/8 FSE-1/6 FSE-1/4 FSE-1/2 FSE-1

Internal Equalizer FV-1/5 FV-1/3

Internal Equalizer EFV-1/5 EFV-1/3 EFV-1/2 EFV-1 EFV-1-1/2 EFV-2-1/2 EFJ-1/8 EFJ-1/6 EFJ-1/4 EFJ-1/2 EFJ-1 EFJ-1-1/2 EFS-1/8 EFS-1/6 EFS-1/4 EFS-1/2 EFS-1

External Equalizer EFVE-1/5 EFVE-1/3 EFVE-1/2 EFVE-1

2
TONS 1/5 1/3 1/2 1 1-1/2 2 2-1/2 3 1/8 1/6

Thermostatic Charges Available

Standard Tubing LengthInches

CONNECTIONS - Inches SAE Flare / ODF Solder Blue figures are standard and will be furnished unless otherwise specified

INLET

OUTLET

1/4 OR 3/8

3/8 OR 1/2

22 (V)
407C (N) 407A (V)

FV-1/2 FV-1 FV-1-1/2 FV-2-1/2 FJ-1/8

C Z ZP40 3/8 1/2

EFVE-1-1/2 EFVE-2 EFVE-3 EFJE-1/8 EFJE-1/6 EFJE-1/4 EFJE-1/2 EFJE-1 EFJE-1-1/2 EFJE-2 EFSE-1/8 EFSE-1/6 EFSE-1/4 EFSE-1/2 EFSE-1

134a (J)
12 (F) 401A (X) 409A (F)

FJ-1/6 FJ-1/4 FJ-1/2 FJ-1 FJ-1-1/2 FS-1/8

1/4 OR 3/8 1/4 30 1/2 1 1-1/2 2 1/8 1/6 1/4 OR 3/8 FS-1/4 FS-1/2 FS-1 FS-1-1/2 1/4 1/2 1 C Z ZP 3/8 C

3/8 OR 1/2

1/2

404A (S)
502 ( R ) 408A ( R )

FS-1/6

3/8 OR 1/2

FSE-1-1/2 EFS-1-1/2 EFSE-1-1/2 1-1/2 Copyright 2006 Thomson Delmar Learning

1/2

42

Sporlan Type G Chart

Very similar to the F chart. However, there is a ton valve available between the and 1 ton ratings.

Copyright 2006 Thomson Delmar Learning

43

SPECIFICATIONS
TYPE G SAE Flare REFRIGERANT (Sporlan Code)

Sporlan Type G Chart ELEMENT SIZE NO. 53, KNIFE EDGE JOINT

Thermostatic Charges Available

Standard Tubing Length-Inches

TYPE EG ODF Solder

NORMAL CAPACITY Tons of Refrigeration

Internal Equalizer

External Equalizer

Internal Equalizer

External Equalizer

CONNECTIONS - Inches SAE Flare / ODF Solder Blue figures are standard and will be furnished unless otherwise specified INLET 1/4 OR 3/8 OUTLET 1/2

22 (V)
407C (N) 407A (V)

GV-1/5 GV-1/3 GV-1/2 GV-3/4 GV-1 GV-1-1/2 GV-2-1/2 GJ-1/8 GJ-1/6 GJ-1/4 GJ-1/2 GJ-1 GJ-1-1/2 GS-1/8 GS-1/6 GS-1/4 GS-1/2 GS-1 GS-1-1/2 -

GVE-1/5 GVE-1/3 GVE-1/2 GVE-3/4 GVE-1 GVE-1-1/2 GVE-2 GVE-3 GJE-1/8 GJE-1/6 GJE-1/4 GJE-1/2 GJE-1 GJE-1-1/2 GJE-2 GSE-1/8 GSE-1/6 GSE-1/4 GSE-1/2 GSE-1 GSE-1-1/2 GSE-2

EGV-1/5 EGV-1/3 EGV-1/2 EGV-3/4 EGV-1 EGV-1-1/2 EGV-2-1/2 EGJ-1/8 EGJ-1/6 EGJ-1/4 EGJ-1/2 EGJ-1 EGJ-1-1/2 EGS-1/8 EGS-1/6 EGS-1/4 EGS-1/2 EGS-1 EGS-1-1/2 -

EGVE-1/5 EGVE-1/3 EGVE-1/2 EGVE-3/4 EGVE-1 EGVE-1-1/2 EGVE-2 EGVE-3 EGJE-1/8 EGJE-1/6 EGJE-1/4 EGJE-1/2 EGJE-1 EGJE-1-1/2 EGJE-2 EGSE-1/8 EGSE-1/6 EGSE-1/4 EGSE-1/2 EGSE-1 EGSE-1-1/2 EGSE-2

1/5 1/3 1/2 3/4 1 1-1/2 2 2-1/2 3 1/8 1/6 1/4 1/2 1 1-1/2 2 1/8 1/6 1/4 1/2 1 1-1/2 2

C Z ZP40

3/8

1/2

134a (J)
12 (F) 401A (X) 409A (F)

1/4 OR 3/8 30 C 3/8

1/2

1/2

404A (S)
502 ( R ) 408A ( R )

1/4 OR 3/8 C Z ZP

1/2

3/8

1/2

Copyright 2006 Thomson Delmar Learning

44

Sporlan Balanced Port Valves

These valves have a tonnage range, rather than a single rating.

Copyright 2006 Thomson Delmar Learning

45

SPECIFICATIONS
TYPE REFRIGERANT (Sporlan Code) SAE Flare Internal Equalizer BFV-AAA External Equalizer BFVE-AAA BFVE-AA BFVE-A BFVE-B BFVE-C BFJE-AAA BFJE-AA BFJE-A BFJE-B BFJE-C BFSE-AAA BFSE-AA BFSE-A BFSE-B BFSE-C

Sporlan Balanced Port Valves ELEMENT SIZE NO. 43, KNIFE EDGE JOINT

Standard Tubing Length-Inches

Port Size

NORMAL CAPACITY Tons of Refrigeration

Thermostatic Charges Available

CONNECTIONS - Inches Blue figures are standard and will be furnished unless otherwise specified SAE Flare INLET OUTLET External Equalizer

AAA AA A B C AAA AA A B C AAA AA A B C

1/8 thru 1/3 1/2 thru 2/3 3/4 thru 1-1/2 1-3/4 thru 3 3-1/4 thru 5-1/2 1/8 thru 1/5 1/4 thru 1/3 1/2 thru 1 1-1/4 thru 1-3/4 2 thru 3 1/8 thru 1/5 1/4 thru 1/3 1/2 thru 1 1-1/4 thru 2 2-1/4 thru 3 C Z ZP C 30 C Z ZP40

22 (V)
407C (N) 407A (V)

1/4 OR 3/8 Elbow 1/4 OR 3/8 Elbow 3/8 Elbow

BFV-AA BFV-A BFV-B BFV-C BFJ-AAA

134a (J)
12 (F) 401A (X) 409A (F)

1/4 OR 3/8 Elbow 1/4 OR 3/8 Elbow 3/8 Elbow 3/8 or 1/2 1/4

BFJ-AA BFJ-A BFJ-B BFJ-C BFS-AAA

404A (S)
502 ( R ) 408A ( R )

1/4 OR 3/8 Elbow 1/4 OR 3/8 Elbow 3/8 Elbow

BFS-AA BFS-A BFS-B BFS-C

Copyright 2006 Thomson Delmar Learning

46

Preparing for TEV Troubleshooting

For a TEV to work properly it must: 1. Be sized properly. 2. The sensing bulb must be strapped correctly. 3. There must be a full column of liquid to the valve.

Copyright 2006 Thomson Delmar Learning

47

Causes for TEV Flooding


1. Ice in the valve
Use a warm rag or heat gun to thaw. Replace the filter drier. Clean bulb and pipe and re-strap. Insulate the bulb and pipe. Check proper mounting on vertical suction line.

2. Bulb not sensing suction line temperature.

3. Readjust valves superheat setting. 4. If still flooding, replace the TEV.


Copyright 2006 Thomson Delmar Learning

48

Causes for TEV Starving


1. Ice in the valve
Use a warm rag or heat gun to thaw. Replace the filter drier. Check for hole in bulb or broken cap tube.

2. Sensing bulb has lost its charge. 3. Check for a clogged inlet strainer. 4. Readjust valves superheat adjustment. 5. If still starving, replace the TEV.
Copyright 2006 Thomson Delmar Learning

49

Causes for TEV Hunting


1. Lower superheat.
Allowing more refrigerant through the valve usually settles its fluctuations.

2. If your are sure it is sized correctly and it is still hunting, replace the TEV.

Copyright 2006 Thomson Delmar Learning

50

Capillary Tubes (cap tubes)


A fixed metering device Regulates refrigerant flow by pressure drop Pressure drop is based on:
Cap tube length Internal diameter of tubing

Copyright 2006 Thomson Delmar Learning

51

Hose Pressure

100 psig 75 psig


25 psig 25 of hose

100 psig 200 of hose


Copyright 2006 Thomson Delmar Learning

52

Fixed Metering Device


Provides consistent pressure drop
Condensing pressure to evaporator pressure

Copyright 2006 Thomson Delmar Learning

53

Cap tube picture

Copyright 2006 Thomson Delmar Learning

54

Cap Tube Guidelines


The next slide is an information sheet from J/B Industries Interesting points are highlighted in yellow

Copyright 2006 Thomson Delmar Learning

55

J/ B
DIAMETER AND LENGTH

APPLICATION AND ENGINEERING DATA

Copper Capillary Tubing

For Refrigeration and Air-Conditioning

FACTORS AFFECTING REFRIGERANT FLOW


The size of the cap tube is fairly critical. Unlike orifices, such as capillary tubes depend on on their length as well expansion valve seats, capillary as their diameter to determine their total restriction. to determine their total restriction. The relationship between these two factors are shown in the following charts. A change in diameter on a percentage basis can change the flow more changing the Affecting diameter than an equal change in length. To illustrate, Factors by .005" as as between between .026" .026" I.D. I.D. and and .031" .031" I.D. I.D.can candouble doublethe theflow. flow. Restriction can also be changed by lengthening or shortening the longer the the tube, the slower the flow, cap tube. The longer flow; the shorter the tube, the faster the flow. tube, the faster the flow. The general flow curve graph (right) shows what happens to the flow of refrigerant through a cap tube as the length is changed. This curve is not meant to give specific flows but to simply illustrate what happens with all cap tubes so that the general flow pattern can be understood. By following the flow curve from left to right it can be seen that for the very longest length the flow is the smallest. Then as the cap tube length is decreased, the flow increases slowly until critical point "L" is reached. At this point the flow increases more rapidly with each reduction in length until critical point "S" is reached. From this point on, further decrease in length causes ever increasing flow. From the study of this typical curve, certain pertinent conclusions can be reached that directly affect the field application of capillary tubes. On the graph, that section above the critical point "L" is marked as extra long lengths. Attempting to increase restriction (i.e. reduce flow) by increasing length into this region is not only uneconomical but frequently hopeless. In addition, tubes in this range may not be responsive enough to changes in head pressures during operation. All in all, tube lengths in this range should be avoided where possible. Refrigerant Flow Continuing down the graph, that section below critical point "S" should be avoided like the plague. In this range, the tube is so short that even small changes in length will cause very large increases in flow. This is caused by the fact that the length no longer affects the flow and the tube now begins to act more like an orifice than a capillary tube. But, without the other components necessary to control an orifice, such as are present in an expansion valve or high side float, a very short cap tube will give wildly erratic operation under varying ambients and loads. All of this would be meaningless without some definite way to use this information. Although the critical points will vary depending on the I.D. of the cap tubing being used, a very safe operating rule-ofthumb can be offered. Keep the cap tube no shorter than 5 ft. and no longer than 16 ft.

Copyright 2006 Thomson Delmar Learning

56

Cap Tube Sizing


Check with the equipment manufacturer for proper cap tube size. However, if the manufacturer information is not available J/B has charts for sizing cap tubes.
The following example is a 1/3 H.P. unit Operating at a 15 evaporator The cap tube size is .036 I.D., 6 long

Copyright 2006 Thomson Delmar Learning

57

REFRIGERATION APPLICATION CHART (R-12 AND R-22)


NORMAL EVAPORATING TEMPERATURE DEGREES F
H.P. H.P. REF REF.
NOTE -10 to +5
TC-26 TC-26 TC-26 TC-26 TC-26 TC-31 TC-31 TC-31 TC-31 TC-36 TC-36 TC-36 TC-42 TC-36 TC-54 TC-54 TC-54 TC-64 TC-70 TC-54 (2 pcs)

+5 +20 +5 to +20
10 Ft 12 Ft 12 Ft 10 Ft 10 Ft 12 Ft 10 Ft 10 Ft 8 Ft 6 Ft 6 Ft 6 Ft Ft 6 Ft 9 Ft 9 Ft 9 Ft 12 Ft 12 Ft 11 Ft 7-1/2 Ft 9 Ft 10 Ft 9 Ft 10 Ft 8 Ft 10 Ft 10 Ft 10 Ft TC-26 TC-31 TC-31 TC-31 TC-31 TC-36 TC-36 TC-36 TC-36 TC-36 TC-36 TC-36 TC-42 TC-42 TC-49 TC-54 TC-70 TC-70 TC-54 TC-54 (2 pcs) TC-64 (2 pcs) TC-70 (2 pcs) TC-75 (2 pcs) TC-70 (3 pcs) TC-64 (4 pcs) TC-70 (4 pcs) TC-70 (5 pcs) TC-80 (5 pcs)

+20 to +35

+35 to +50

1/20 R-12 1/12 R-12 1/9 R-12 1/9 R-12 1/8 R-12 1/6 R-12 1/6 R-12 1/5 R-12 1/5 R-12 1/4 R-22 1/4 R-12 1/3 R-22 1/3 R-22 1/3 1/3 R-12 1/2 R-22 1/2 R-12 3/4 R-22 3/4 R-12 1 R-22 1 R-12 1-1/2 R-22 1-1/2 R-12 2 R-22 2 R-12 3 R-22 3 R-12 4 R-22 4 R-12 5 R-12 Note: Condenser Type:

S-F 16 Ft. S-F 12 Ft. S 12 Ft. S 10 Ft. S-F 10 Ft. S 12 Ft. F 10 Ft. S 10 Ft. F 8 Ft. S-F 12 Ft. F 10 Ft. F 10 Ft. F 12 Ft. F 6 Ft. F 11 Ft. F 11 Ft. F 7-1/2 Ft. F 10 Ft. F 10 Ft. F 7-1/2 Ft. F F F 10 Ft. F F 10 Ft. F F F S = Static, F = FAN

Copyright 2006 Thomson Delmar Learning

Refrigeration Application Chart (R-12 & R-22)


8 Ft. 7-1/2 Ft. 10 Ft. 8-1/2 Ft. 8 Ft. 11 Ft. 9 Ft. 7-1/2 Ft. TC-36 TC-42 TC-42 TC-42 TC-42 TC-49 TC-49 TC-54 10 Ft. 7-1/2 Ft. 6 Ft. 6 Ft. 6 Ft. 6 Ft. 10 Ft. TC-42 TC-49 TC-42 TC-49 TC-49 TC-54 TC-64 10 Ft. 7-1/2 Ft. 8 Ft. 10 Ft. 9 Ft. 10 Ft. 9 Ft. 10 Ft. 9 Ft. 9 Ft. 9 Ft. TC-80 TC-54 (2 pcs) TC-64 (2 pcs) TC-80 (2 pcs) TC-75 (2 pcs) TC-85 (2 pcs) TC-75 (3 pcs) TC-80 (4 pcs) TC-75 (4 pcs) TC-75 (5 pcs) TC-85 (5 pcs) TC-70 (2 pcs) TC-70 (2 pcs)

58

Cap Tube Conversion Chart


Sometimes you do not have the cap tube size recommended by the manufacturer. The following J/B conversion chart shows how much longer or shorter the replacement cap tube must be.
Assume 9 feet of .040 cap tube is needed. How long would a .036 tube need to be to give the same amount of refrigerant and pressure drop? What if all you had was a .042 cap tube?
Copyright 2006 Thomson Delmar Learning

59

CAPILLARY TUBE LENGTH CONVERSION CHART


This conversion chart enables the user to translate the (4) The resultant length (Min. 5 feet/Max. 16 feet) of copper cap tube will give the same flow Capillary Tube Length recommended length of tube diameter into sizesConversion stocked by Chart characteristics as the original recommended cap tube. J/B. In using the chart it is recommended that conversions be EXAMPLE made using factors within the unshaded area. Recommended cap tube: 9'-.040 I.D. TO USE CHART (1) Locate recommended cap tube I.D. in left hand column. Locate .040 in left hand column and reading across gives the following conversion factor: No. TC-36 (.62) and TC-42 (1.25). (2) Read across and find conversion factor under copper cap tube size. Multiplying the recommended cap tube length of 9' by the conversion factor gives the following results: (3) Multiply the given length of the recommended cap tube by 5-1/2' (5'6") TC-36 and 11-1/4' (11'3") TC-42. Either of these two cap tubes will give the same results as the original cap tube of 9'-.040 I.D. the conversion factor.
Part No. Tube I.D.

9 x .62 = 5

.024 .025 .026 .028 .030 .031 .032 .033 .034 .035 .036 .037 .038 .039 .040 .041 .042 .043 .044 .045 .046 .047

TC-26 .026 1.44 1.20 1.00 .72 .52 .45

TC-31 .031

TC-36 TC-36

TC-42 TC-42

.036

.042

TC-44 .044

TC-49 .049

TC-50 .050

TC-54 .054

TC-55 .055

2.24 1.59 1.16 1.00 .86 .75 .65 .58 .50 .45 .39 .35 .31 .28 .25 .23 .20

2.00 1.75 1.54 1.35 1.16 1.00 .90 .80 .71 .62 .62 .56 .50 .45 .39 .35 .32

9 x 1.25 = 11
2.31 2.10 1.79 1.59 1.41 1.25 1.12 1.00 .87 .81 .73 .67 .59 2.22 1.92 1.75 1.55 1.38 1.24 1.11 1.00 .90 .82 .74 2.51 2.26 2.03 1.83 1.62 1.47 1.34 1.20

2.50 2.23 1.98 1.79 1.60 1.47 1.31

2.32 2.08 1.89

2.27 2.06

Copyright 2006 Thomson Delmar Learning

60

T.R.O.T. for Replacement Cap Tubes


Larger must be longer, smaller must be shorter. This rule of thumb is helpful to keep in mind when using a chart for replacing cap tubes. Assume the replacement cap tube has a larger I.D. than the original:
The replacement must be longer than the original to increase the pressure drop to match the original.

If the replacement is smaller than the original:


The replacement must be shorter to reduce the pressure drop to match the original cap tube.

Copyright 2006 Thomson Delmar Learning

61

Cap Tube Comparisons Inside Diameter(ID) X Length


.031
10x.50=5 Smaller ID = Shorter length

If you used a .031 cap tube, how long would it have to be?

.036

Length = 10

Original cap tube according to the manufacturer.

If you used a .042 cap tube, how long would it have to be?

.042

Length = 10 x 2.10 = 21
Larger ID = Longer length
Copyright 2006 Thomson Delmar Learning

62

Preparing for Capillary Tube Troubleshooting


For a cap tube to work properly: 1. It must be sized properly. 2. The evaporator load must be at designed conditions. 3. The refrigerant charge must be correct. 4. There must be a full column of liquid to the cap tube.

Copyright 2006 Thomson Delmar Learning

63

Causes for Evaporator Flooding on a Cap Tube System


1. Too much high side pressure
Dirty condenser Refrigerant overcharge

2. Incorrectly sized cap tube (low pressure drop)


Inside diameter (I.D.) too large Cap tube length too short Box temperature too low Blocked evaporator (dirt or ice) Fan motor bad
Copyright 2006 Thomson Delmar Learning

3. Low evaporator load

64

Causes for Evaporator Starving on a Cap Tube System


1. High evaporator load (quickly vaporizing refrigerant)
Door open or not sealing High product load
Initial start up Hot product in the box

2. High side pressure too low.


Low on refrigerant. Low ambient. Inside diameter (I.D.) too small Cap tube length too long.
Copyright 2006 Thomson Delmar Learning

3. Incorrectly sized cap tube (high pressure drop).

65

Causes for Plugged Cap Tubes


Dirt or ice blocking the cap tube
Filter desiccant can also plug cap tube

Solution:
Cut off some cap tube Replace filter drier

Copyright 2006 Thomson Delmar Learning

66

Correcting a Plugged Cap Tube


1. Powder can flake off beads 2. It clogs the inlet of the cap tube

Beaded Desiccant

4. Replace the Filter Drier

3. Cut off an inch or two of cap tube to remove the restriction

Copyright 2006 Thomson Delmar Learning

67

Cutting Cap Tubes

Do not use tubing cutters Use a file to score it, then snap it J/B also makes special cutters

Copyright 2006 Thomson Delmar Learning

68

Cap tube file and Cutter


A10972 CAP TUBE FILE
Specially designed to cut and open tube. File notch around tubing at desired cutting point. Snap tube by bending at notch. Clean burrs by reaming out with special file tip. In cleaning or deburring, always hold tube downward to keep small particles from entering tube. WORKING WITH CAPILLARY TUBING Every precaution possible should be taken to prevent chips, dirt, flux, moisture, filings, etc. from entering the system when changing the cap tube. Cap tube is sealed and dehydrated from the factory.

Remember, most cap tubes have A10973 CAP CUTTING TOOL very small holes . . . it doesn't take much to plug them. The Specially designed to cut all A10972 Cap Tube File and sizes of soft and many sizes of A10973 Cap Tube Cutter are hard drawn cap tubes. specifically designed tools for working with cap tube.

Copyright 2006 Thomson Delmar Learning

69

Determining Cap Tube Size


J/B has a tool to determine the size of a capillary tube.

Copyright 2006 Thomson Delmar Learning

70

DETERMINING CAP TUBE SIZE


The A10971 Cap Tube Gauge accurately measures a full range of capillary tube sizes. Correct tube size is determined by using both the I.D. and O.D. dimensions.

.026 12MM .031 7/16 10MM 3/8 8MM 3/16 .044 1/4 6MM .049 5MM 3/15 .054
O.D. TUBE GAUGE

.036

.042

Check OD of tube in "V" slot. Compare OD with reference chart printed on back of gauge to determine probable ID. Use pin gauge to confirm actual size of ID. This same means of cross referencing can be used whenever two standard I.D.'s are very close or OD's are the same.

.059
CAP. TUBE GAUGE

5/32 .064 .072

.070

.083 .087 .093

.075

.099 .106 .109 .112 .114

.080

.085

.125

.090 .145

Copyright 2006 Thomson Delmar Learning

71

Automatic Expansion Valves


AEVs are adjusted to maintain a minimum evaporator pressure This prevents the evaporator from getting too cold Used in units that have a fairly constant load

Copyright 2006 Thomson Delmar Learning

72

Pressure Adjuster

Automatic Expansion Valve (AEV)

Copyright 2006 Thomson Delmar Learning

73

Copyright 2006 Thomson Delmar Learning

74

Anda mungkin juga menyukai