PERSONAL INFORMATION
NAME: Engr. Wilfred Amen Asonmwonriri (MNSE) DATE OF BIRTH: September 1970 Married Protection Engineer FORMAL EDUCATION M.ENG(POWER AND MACHINES) B.ENG(ELECTRICAL AND ELECTRONICS) PROFESSIONAL AND TECHNICAL EDUCATION Travelling waves systems: QUALITROL Power System Engineering: Power System Training Institute: - New Delhi Protective Relay Testing using Omicron Test set :OMICRON
To keep the power system in operation continually adequate protection must be provided. Protective relays detect abnormalities or faults and eliminate such abnormalities by isolating the smallest portion of the system.
RELAYS
Relays are the devices, which monitor the conditions of a circuit/device and give instructions to isolate it under unhealthy conditions. The conditions of a circuit or equipment are monitored from the electric power system parameters, the most basic of which are voltage, current, frequency and power. The power system parameters have predetermined values under healthy conditions. . Any shift from this normal behaviour therefore, could be the result of a fault condition.
4 Master Contactor
5 Stopping device 6 Starting Circuit breaker 7 Anode Circuit breaker 8 Control Power Disconnecting Device
9 Reversing Device 10 Unit Sequence Switch 11 RESERVED FOR FUTURE APPLICATION 12 Over Speed device 13 Synchronous Speed device
16 RESERVED FOR FUTURE APPLICATION 17 Shunting or Discharge switch 18 Accelerating or Decelerating device 19 Starting to Running Transition Contactor 20 Electrically Operated Valve
21 Distance Relay
22 Equalizer Circuit breaker
37 Undercurrent or under power relay 40 Field relay 50 Instantaneous over current or rate of rise relay 51 A.C. Time Over current relay 52 A.C. Circuit breaker
Power system protection is realized by protecting the different primary equipment that variously constitute the power system.
A faulted component needs to be isolated from the entire grid as quickly as possible to prevent the fault from spreading to other parts of the grid and to prevent damage to equipment and personnel.
(c) Selectivity The relay must be able to discriminate between faults and abnormal conditions. (d) Simple For a relay to be effectively used, its construction and operation has to be simple in nature.
(e) Speed of Operation To be able to prevent damage to the associated equipment the relay is protecting, it must act fast before the damage is done. (f) Cost The relay should not be so expensive as to outweigh the benefit of using it to protect the associated equipment.
CATEGORIES OF FAULTS
Single phase to ground fault Double phase to ground fault Three phase to ground fault Phase to phase fault Three phase fault.
The commonest, in occurrence, of the above fault conditions, is the single phase to ground fault which is about 70%.
Protective relaying was introduced in practice as early as the first power systems were invented to make sure that faults are detected and damaged or faulted components are taken out of service quickly. Faults occur randomly and may be associated with any component of the power system. The longer the fault duration, the larger is the extent of damage.
For the faults and abnormal conditions enumerated above protective relays are designed to isolate and reduce damage to the system equipment.
RELAY PERFORMANCE
Performance of relays can be classified as: Correct Incorrect Inconclusive. Incorrect Operation This can be due to the following factors: Incorrect Relay Setting Personnel Error Equipment Malfunction
Incorrect tripping may be either failure to trip or false tripping. Failure to trip can be caused by faulty associated instrument transformer, circuit breakers, control cables and wiring and station batteries. Inconclusive Operation This is the last resort when no evidence is available either for a correct or incorrect operation. Quite often, this is a personal involvement.
CONTACTORS
DC BATERRY BANKS
TELE COM
PROTECTION EQUIPMENT
DC SYSTEM
ZONES OF PROTECTION
For effective protection of the system with minimum part disconnected during fault, protection zones are mapped out. Motor Protection Zone Generator Protection Zone Transformer Protection Zone Bus bar Protection Zone Lines Protection Zone
Zones of Protection
a fault occurs, protection is arranged in zones Zones of protection should overlap, so that no part of the power system is left unprotected Location of the CT connection to the protection usually defines the zone Unit type protections have clear zones reach e.g Diff. Relay, REF relay
SUFFIX NUMBERS
If two or more devices with the same function number and suffix letter (if
used) are present in the same equipment then these are distinguished as
follows 52x-1, 52x-2, 52x-3 etc SUFFIX LETTERS Suffix letters are used with device numbers for various purposes. The meaning of each suffix letter or combination of letters should be clearly indicated in the legend on the drawings or publications accompanying the equipment. Example: 52 TC Tripping coil of the breaker
It is obviously a great field as it forces you to fully understand the technical aspects of the power industry.
A deep understanding of the operation of all the elements of the power system is required as one cannot protect an equipment which operation he does not know. He requires a solid understanding of many technical features of the power system including:machine design parameters,bus configuration, trip circuits, symmetrical components,fault currents, unbalanced power flow and much more
For an early success in the protection engineering career the young engineer should undergo the following: He should be made to pass through training courses that are tailored specifically for protective relaying.
He should place himself on a continous professional development program by accessing power system references and training materials which include textbooks,relay manuals, standards and technical papers. He should place himself on a continous professional development program by accessing power system references and training materials which include textbooks,relay manuals, standards and technical papers.
The young engineer needs to develop good hands-on-the job skills with ability to stay on the job untill he gets result.
The young engineer should be passionate about his work as he requires the positive mental attitude that goes with love for work to succeed. He needs to be quick and able to learn new things all the time
He needs a mentor for guidance as he progresses in his career. He needs to develop or join an existing professional network or peer group in the industry.
This is quite a lot to ask of any one person but the professional and psychological reward can be very great.I cannot imagine a better field to begin a power engineering career than protective relaying as the challenges it provides are endless and the learning process a life- long one.