Anda di halaman 1dari 23

June 2006

Eltek

Scaleable and flexible control module for the entire Eltek product range
2

Eltek

Small but powerful

< 300g

44mm
144 mm

109 mm
3

Eltek

Front Panel
Standard

2x16 character display

CAN Bus ID DIP switches

USB Port Traffic Light LEDs


4

3 button Keypad

Eltek

Rear Panel
CAN Bus

CAN bus
120 ohm term. required at each end ID based serial bus communications Max 8 Smartpack

Part No : 242100.110
(RoHS compliant)

Max 50 Rectifiers

Eltek

Rear Panel

Battery Monitoring

Battery Monitoring
Con 4 : Standard Con 3 : Extended

Symmetry measurement

Part No : 242100.110
(RoHS compliant)

8 strings mid point or 2 strings 12V block Temp sense


6

Eltek

Rear Panel
Internal System

Internal System
System measurements Unit Power 2xLVD control (Latched)

Part No : 242100.110
(RoHS compliant)

Battery fuse fail

Eltek

Rear Panel
Alarm I/O

Alarm I/O
Con 1 (standard):2 + 2 relay input / output Con 2 (extended):4 + 4 relay input / output

Part No : 242100.110
(RoHS compliant)

Eltek

RS-232 Option
RS-232 mounted
Enables connection of Standalone Webpower or modem

Part No : 242100.112 (RoHS compliant)

Rear position : Replaces extended Battery symmetry card

Part No : 242100.111 (RoHS compliant)

Eltek

Opening the Smartpack

1. 2. 3.

Remove 4 chassis screws Remove top D-Sub fixings (CON 2 & 3). Lift top cover from the front.
10

(Re-assemble in reverse order)

Eltek

Rear Panel

Embedded Webpower

Embedded
WebPower

Part No : 242100.113
(RoHS compliant)

Ethernet interface of remote monitoring of Smartpack Is possible to tunnel Powersuite remotely also.

11

Eltek

Functionality
Battery monitoring and testing Temperature compensated charging Battery lifetime indication Alarm/event log (1000) with time and date And much more .
12

Eltek

Scalability
CAN/Power bus

Smartpack Master

Smartpack Slave 1

Smartpack Slave n

System functionality
Voltage input Symmetry inputs Current inputs Temperature inputs 1 8 (2x4x12V) 2 2

System functionality
Voltage inputs Symmetry inputs Current inputs Temperature inputs 2 16 (4x4x12V) 4 4

System functionality with 8 modules


Voltage inputs Symmetry inputs Current inputs Temperature inputs 8 64 (16x4x12V) 2x8 2x8

General purpose inputs 6 Load fuse input Batt fuse input Relay outputs Contactor control 1 2 6 2+

General purpose inputs 12 Load fuse input Batt fuse input Relay outputs Contactor control 2 4 12 4+

General purpose inputs 6x8 Load fuse input Batt fuse input Relay outputs Contactor control 1x8 2x8 6x8 2+x8

13

Eltek

Connectivity
Battery

CON3 & CON4 Battery Connections


Pin
1

Function
Symmetry I/P 1

2
3 4 Temp Sense Cable 5 6 7 8 9-10 11 - 14

Symmetry I/P 2
Symmetry I/P 3 Symmetry I/P 4 Symmetry I/P 5 Symmetry I/P 6 Symmetry I/P 7 Symmetry I/P 8 Con 3 : Temp sense 2 Con 4 : Temp sense 1 Con 3 2nd batt current, batt fuse Con 4 : Not used

14

Eltek

Connectivity
Symmetry

Symmetry measurement options

15

Eltek

Connectivity
System

CON5 System Connections


Pin
1

Function
Positive Input

2
3 4 5 6 7 8 9 10 System Connection Card. Art 200625 11

Negative Input
Batt Current +ve Batt Current -ve Batt Fuse +ve Batt Fuse -ve Load Fuse Fail LVD1 Active LVD1 Common LVD2 Active LVD2 Common
16

Eltek

Connectivity
System

System card configuration


JP1 -48v system = 1-2 +24v system = 2-3 JP2 -48v system = Neg +24v system = Pos

17

Eltek

Connectivity

Latched Contactors

A latching contactor changes state only when a reversed pulse voltage is applied to the coil.

Protection Diode

18

Eltek

Connectivity

External Alarm I/O

CON1 & CON2 I/O Connections


Pin
1-2 34 5-7 8 - 10

Function
Alarm input 1 ( + / -) Alarm input 2 ( + / -) Alarm output 1 Alarm output 2
( NO /C / NC) ( NO /C / NC)

1-2
3-4 5-6 7-8 9 - 11 12 - 14 Alarm Output & Input Card Art 105954 15 - 17 18 - 20

Alarm input 3 ( + / -)
Alarm input 4 ( + / -) Alarm input 5 ( + / -) Alarm input 6 ( + / -) Alarm output 3 Alarm output 4 Alarm output 5 Alarm output 6
( NO /C / NC) ( NO /C / NC) ( NO /C / NC) ( NO /C / NC)

19

Eltek

Smartnode
Smartpack Extended Master
CAN/Power bus

Smartnode
Customer equipment Customer bus (RS 485)

Convert PCOMM to Customer specific Protocol

Part no: 242100.200


Communicating with Smartpack on CAN bus RS232 and RS485 serial interface as standard

Smartpack has only PCOMM protocol


20

Eltek

PowerSuite
Explorer oriented easy to use PC SW

USB gives simple access.


Wide functionality with clear graphic presentation.
21

Eltek

PowerSuite

Live Demo

22

Eltek

End of Presentation

Lets us know if you found this presentation useful or would like more information. Eltek values your feedback.

Thank you
mahmood.sheikh@eltekenergy.com
29

Anda mungkin juga menyukai