In the early days of power System ,bus bar were regarded as intrinsically safe and left without specific protection. It was anticipated that system or back up protection would provide sufficient cover. Many feared that accident operation of bus bar protection , if fitted, would cause more disruption than that by a fault on unprotected bars. As power system developed and fault levels increased bus bar protection became essential since damage resulting from one uncleared fault may extend in magnitude up to the complete loss of station by fire. It is now usual to subdivide the bus bar into sections each protected separately. A fault in one section does not involved tripping the complete station. Important loads can be then fed from two or more sections, and will not suffer interruption of supply if one section is tripped.
Differential protection
Uses Merz-price circulating current principle . All current entering and leaving bus bar are compared. One set of CT,s for each circuit associated with a particular zone are all connected to a relay A single element relay gives earth fault protection only. A three element relay gives phase and earth fault protection.
aEffective settings
Since in each zone of protection there are sevaeral CT,s in the paralell with the relay and each other, the combined CT magnitising currents will increase the primary operating current. POC=CT ratio (Ir+INLR+NIm) Where Ir = relay setting current IM =CT magnetising current N = number of paralleled CT,s INLR = non linear resistor current at relay setting voltage.
Check feature
Usually provided by duplication of primary protection using second set of CTs on all circuits other than bus section and coupler units.Check system forms one zone only,covering whole of the busbar system and not discriminating between faults on various sections
Differential relays
Relays used for high impedence protection are high stabililty unbiased and tuned to nominal frequency. Two modular types are MFAC14/34
CT wiring supervision
Open circuit connections between CTs and relay circuits result in unbalanced currents whioch may operate the protection. Supervision is applied by voltage relay across differential relay circuit.supervision relays is time delayed gives alarm and also short out bus wires to protect differential relay circuit.typiucal effective setting is 25 primary amperes or 10% of lowest circuit rating which ever is greater.
Tripping circuits
One trip[ping rel;ay device is required for each feeder breaker and two far each bus section or bus coupler breakers.both ma8in and check relays must be energized before triiping relays trip all breakers assocaited with zones