Describe the Configuration of C200 Hardware and I/O

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Introduction

Honeywell

In this lesson you will learn to configure C200 hardware and I/O using Control Builder At the conclusion of this lesson, you will be able to:
Identify C200 hardware, slot numbers and addressing
Configure and download hardware configurations for these components

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics Hardware and Slot Numbers Configuring the FTEB, Controller, and CEE Configuring IOMs Loading the Controller, CEE, and IOMs Activating a CEE

Honeywell

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C200 Chassis Hardware Below is an example C200 chassis configured with:

Honeywell

1 2 3 4

10-slot chassis Power supply


ControlNet Interface (CNI) or FTE Bridge Control Processor (C200)

5 6 7 8

IO Link Interface Module Fieldbus Interface Module

Redundancy Module
CNI to Remote I/O

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C200 I/O Slot Numbers

Honeywell

To determine the slot location of C200 related hardware you must:


Start counting at zero (do not count the power supply) Count from left to right Count both spaces if the module occupies two spaces

0 Power Supply 1 2 3 4

5 6 7 8 9

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics Hardware and Slot Numbers

Honeywell

Configuring the FTEB, Controller, and CEE


Configuring IOMs Loading the Controller, CEE, and IOMs Activating a CEE

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Fault Tolerant Ethernet Bridge (FTEB) Single-wide chassis module Connects to FTE cable A and B Supports chassis redundancy Can only be used for Supervisory Control Network connection ControlNet and downlink CNIs required for all I/O communications including peer-to-peer to AB devices Rotary switch for FTE Node Number (1 to 99)

Honeywell

IP address of FTEB can be set to higher than 99 by configuring the Base IP address accordingly from System Preferences option
7

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Fault Tolerant Ethernet Bridge (FTEB), contd.

Honeywell

The FTEB can be used for FIM-only connections to the supervisory network In the Project and Monitoring tabs in Control Builder you will see the FTEB as the root for the CPM You will set up the FTEB using IP addresses An FTE community can only have 99 FTEBs so you are limited to 49 redundant pairs and 99 single FTEBs in one community The FTE connection to the FTEB is 10Mbps
10Mbps is only supported in FTE for connection from an FTEB to a switch and nowhere else

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a FTEB

Honeywell

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: FTEB Node Numbering Which of the following is not a valid FTEB node number?
A) 110
B) 99 C) 257 D) 1

Honeywell

The correct Your answer: answer is: No. '257' is not a valid FTEB node number. You must answer the question before FTEB IP address can be set to higher then 99 You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to to continue continue completely continuing by configuring the base IP address accordingly

in System Preferences in Control Builder.


Click anywhere to continue.

Submit

Clear

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

10

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a Controller

Honeywell

Follow these steps to add a new control processor module (CPM) from the pull-down menus

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

11

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a Controller CPM Main Tab Data entry details will be provided in the lab exercise
Driver Name MAC ID of CNI Card connected to server

Honeywell
Tag Name & Item Name ControlNet or Ethernet driver CNI slot # Slot number of CPM Alarm reporting by CEE

Check for the redundant controller and then enter its name

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

12

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a Controller CPM Main Tab, contd. Data entry details will be provided in the lab exercise

Honeywell

Ethernet Network

Driver Name Slot Number of CPM

Redundant Controller & Name

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

13

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a Controller Server History Tab

Honeywell

History parameters and control level required to operate this CPM

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

14

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a Controller Group and Trend Assignment

Honeywell

Point, group, trend and associated displays (that reside on the server) are defined on the Server Displays tab

Select OK to close and save the new controller

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

15

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 2: Supervisory MAC Address for a CPM While configuring a ControlNet connected control processor module (CPM) in Control Builder, which MAC address is entered as the Supervisory MAC address?
A) The device index of FTEB card B) The MAC address of the PCIC card C) The MAC address of CNI card connected to the I/O rack D) The MAC address of CNI card connected to server
Yourcorrect The answer: answer is: You must answer the question before Incorrect. Correct! The The Supervisory Supervisory MAC MAC address address is isthe theMAC MAC You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to to continue continue completely continuing address of the CNI card connected to the server. Click anywhere to continue.

Honeywell

Submit

Clear

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

16

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a CEE CPM/CEE Tree View

Honeywell

Click the + sign to expand the CPM in the Project tab

Double-click to open the configuration form

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

17

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring a CEE Main Tab

Honeywell

Data entry details will be provided in the Lab exercise

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

18

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring C200 Hardware

Honeywell

The Control Processor Module (CPM) and its Control Execution Environment (CEE) are configured but not yet downloaded

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

19

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics Hardware and Slot Numbers

Honeywell

Configuring the FTEB, Controller, and CEE


Configuring IOMs Loading the Controller, CEE, and IOMs Activating a CEE

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

20

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring Input/Output Modules (IOMs)

Honeywell

Menu method

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

21

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring IOMs

Honeywell

1 2
Control Builder Automatically Names the IOM

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

22

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Configuring IOMs, contd.

Honeywell

Module slot number

MAC address of the remote racks CNI card Slot number of the CNI in the processor rack through which this card will communicate

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

23

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Assigning IOMs

Honeywell

2 3

Assigned to CEE

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

24

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 3: Configuring an IOM Before loading an IOM, it must be:


A) Activated B) Assigned

Honeywell

C) Renamed D) Validated

Yourcorrect The answer: answer is: You must answer the question before Incorrect. Correct! Before Before you you can can load load IOMs, IOMs, they theymust mustbe be You Incorrect Correct did You not answer answered -Click Click anywhere anywhere this this question correctly! to to continue continue completely continuing assigned to the Control Execution Environment. Click anywhere to continue.

Submit

Clear

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

25

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics Hardware and Slot Numbers

Honeywell

Configuring the FTEB, Controller, and CEE


Configuring IOMs Loading the Controller, CEE, and IOMs Activating a CEE

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

26

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Loading the Controller, CEE, and IOMs

Honeywell

Not yet loaded

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

27

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Loading the Controller, CEE, and IOMs, contd.

Honeywell

Verify that the items to load are checked


Note: You can decide to have the modules go to the active state automatically by clicking this checkbox, with the Post Load State selected, to be Active

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

28

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics Hardware and Slot Numbers

Honeywell

Configuring the FTEB, Controller and CEE


Configuring IOMs Loading the Controller, CEE and IOMs Activating a CEE

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

29

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Activating a Control Strategy

Honeywell

Double-click CEE

Select Cold Start

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

30

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Activating a Control Strategy, contd.

Honeywell

Click Yes

Blue: The object is not running (inactive) Green: The object is running (active) Red: Communication failure
31

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary

Honeywell

When configuring and loading C200 hardware and I/O in Control Builder, remember:
To determine the IOM slot number of hardware in the C200 chassis, start counting at zero, but do not count the power supply, count from left to right and count both spaces, if the module occupies two spaces An FTEB node number can be set to higher than 99 The Supervisory MAC address of the CPM is the MAC address of the CNI card connected to the server Before loading the Control Processor Module (CPM), its Control Execution Environment (CEE), and I/O modules (IOMs): Configure the CPM, its CEE and I/O modules (IOMs)

Assign the IOMs to the CEE

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

32

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the Configuration of C200 Hardware and I/O

Completion Certificate

Proceed to the next lesson in your course material


C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

33

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell

This page intentionally left blank

C200 Hardware Configuration Describe the Configuration of C200 Hardware and I/O

34

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe the Import/Export Procedure in Control Builder

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

35

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Introduction In this lesson you will learn to import and export control strategy configurations from one server to another At the conclusion of this lesson, you will be able to:
Describe how to export control strategy configurations from a Control Builder project Describe how to import control strategy configurations into a Control Builder project

Honeywell

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

36

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Control Builder - Export The Export function lets you export all or a portion of the ERDB viewed in the Project Tree to the Ixport folder or a user-defined location

Honeywell The exported portions or all of the ERDB are stored in the Ixport folder at directory location
C:\Program Files\Honeywell\Experion PKS\Engineering Tools (by default)

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

37

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Control Builder Import/Export

Honeywell

CM, SCM and hardware configurations can be moved between servers using the Import/Export function
Control Builder (Server 1)
Control Strategy Configuration
Project Tree

Control Builder (Server 2)


Control Strategy Configuration
Project Tree

Export Data

Import Data

Ixport Directory

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

38

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Control Builder Export

Honeywell

In Control Builder, select File > Export to call up the dialog box shown:
All items in current project use selection buttons (or use <Ctl> + mouse select or <Shift> + mouse select to export specific CMs from the point window)
List of items to Export based on selections from window (Export.sl)
EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

All items in Current project

Import\Export text files target location

Select to start export

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

39

Control Builder Export, contd.


Exporting Data Dialog Box

Honeywell

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

40

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Control Builder Import

Honeywell

In Control Builder, select File > Import to call up the dialog box shown:
Use selection buttons (or use <Ctl> + mouse select or <Shift> + mouse select to import specific CMs from the Point window) List of items to Import based on Selections from Window (Import.sl) When enabled, Your own list of items to import (Filename.sl)
41
EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

All items in Current Import/Export text Files location

Import\Export text Files target location

Import and Assign Select to start Import

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

Question 1: Importing and Exporting


A) Only the hardware configuration can be moved between servers B) CMs, SCMs, and the hardware configuration can be copied and restored to another server C) Only CMs can be moved between servers

Honeywell

Which of the following statements best describes the import/export function?

D) None of the above

Yourcorrect answer: The answer is: You mustCMs, answer theand question before Incorrect. Correct! CMs, SCMs SCMs and the the hardware hardware Correct anywhere to Incorrect -Click Click anywhere tocontinue continue You did You not answer answered this this question correctly! completely continuing configuration can be copied and restored to another server. Click anywhere to continue.

Submit

Clear

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

42

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary The Import/Export function in Control Builder:

Honeywell

Allows you to copy CM, SCM, and hardware configurations from one servers ERDB to another servers ERDB

C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

43

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the Import/Export Procedure in Control Builder

Completion Certificate

Proceed to the Configure C200 Hardware in a Simulation Control


Environment (SCE) and Import the Remaining I/O Modules into the SCE

lab exercises
C200 Hardware Configuration Describe the Import/Export Procedure in Control Builder

44

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013