PENDAHULUAN
FUNGSI MINYAK TRAFO - Insulasi - Pendingin - Peredam busur api - Pelarut gas gas
TDCG
Total dissolved combustible gas
Gas yang timbul pada operasional trafo - H2, CH4, C2H2, C2H4, C2H6, CO - CO2 (bukan combustible gas) Akibat dari degradasi isolasi minyak dan isolasi kertas Gas Kromatografi : alat untuk menguji TDCG
Kondisi 2
Kondisi 3
721 1920
1.921 4630
TDCG normal, fault mungkin ada. Resampling dan hitung rate TDCG / hari
Dekomposisi tingkat tinggi isolasi minyak/ kertas, fault mungkin ada. Resampling dan hitung rate TDCG/ hari Dekomposisi minyak/ kertas berlebihan. Kemungkinan akan terjadi Failure bila meneruskan operasi trafo
Kondisi 4
> 4.630
Action Based
Sumber : IEEE C-57-104-1991
Rate
ppm/day
< 10 10 -30 > 30 < 10 10 -30 > 30 < 10 10 -30 > 30 < 10 10 -30 > 30
Sampling interval
Setiap tahun 3 bulanan bulanan 3 bulanan bulanan bulanan bulanan mingguan mingguan mingguan harian harian
Action
- Kontinyu normal operasi
- Hati-hati ,cek individu gas
-Hati-hati
gas
,cek individu
-Kondisi
-Kondisi
Kon disi 1
H2
CH4
C2H2
C2H4
C2H6
CO
CO2
TDCG
100
120
35
50
65
350
2500
720
101700
121400
35 50
51100
66 100
351 570
25014000
721 1920
701 1800
>1800
401 1000
>1000
51 80
>80
101 150
>200
101 150
>150
571 1400
>1400
4001 10000
>10000
1921 4630
>4630
FAULT TYPES
Key Gases Possible Faults Possible Findings
H2, possible trace of CH4 and C2H6. Possible CO. H2, CH4, (some CO if discharges Involve paper insulation). Possible trace amounts of C2H6. H2, CH4, C2 H6, C2H4, and the key gas for arcing C2H2 will be present perhaps in large amounts. If C2 H2 is being generated, arcing is still going on. CO will be present if paper is being heated. H2, CO.
Partial discharges (corona) Low energy discharges (sparking). (May be static discharges) High energy discharges (arcing)
Weakened insulation from aging and electrical stress. Pinhole punctures in paper Insulation with carbon and carbon tracking. Possible carbon particles in oil. Possible loose shield, poor grounding of metal objects Metal fusion, (poor contacts in tap changer or lead connections). Weakened insulation, from aging and electrical stress. Carbonized oil. Paper destruction if it is in the arc path or overheated. Discoloration of paper insulation. Overloading and or cooling problem. Bad connection in leads or tapchanger. Stray current path and/or stray magnetic flux.
Thermal fault less than 300 C in an area close to paper insulation (paper is being heated). Thermal fault between 300 C and 700 C High energy electrical arcing 700 C and above.
Paper insulation destroyed. Oil heavily carbonized. Same as above with metal discoloration. Arcing may have caused a thermal fault.
Sampling DGA
Example of a Reclamation transformer DGA: Example 1 Hydrogen (H2) 9 ppm Methane (CH4) 60 Ethane (C2H6) 53 Ethylene (C2H4) 368 Acetylene (C2H2) 3 Carbon Monoxide (CO) 7 Carbon Dioxide (CO2) 361 Nitrogen (N2) 86,027 Oxygen (O2) 1,177 TDCG 500
0 2 2
Sampling DGA
Syringe must be filled so that metering pin is completely outside of syringe cap.