No1 Killer: Dry out Undercharge No2 Killer: Grid Corrosion Deep discharge No3 Killer: Bulge Active material soften Possible Reasons leads to undercharge No equalization charge Wrong float voltage Too low charge current TP500 need 100A charge current Rectifier faults Examples from site visit, 2012/09/13 Rectifier is plug out to start the DG, thus caused battery charge current lower than 100A.
Can not conduct equalization charge as MCU faults GEM not installed caused deep discharge, and not sufficient charging for battery banks GEM is not Functional Aircon Breaker Found intentionally Switched Off to get longer backups
Rectifier Setting (Power One/Eltek) S.N Description Rectifier Setting 1 U1-Normal 54.5 2 U2-Boost 56.4 3 U3-Test 46 4 U4-Spare 54.5 5 AH Limit for Test 500 6 GEM alarm Voltage 47.3 7 Low V Alarm 46 8 Hi Battery 58.5 9 O V Shutdown 59.7 10 LVBD 44 11 LVLD 12 Current Limit 100 13 Automatic Boost Enable 14 Boost Time 12hr 15 Boost Interval 3 wk 16 Boost Factor 2
Rectifier Setting (Power One/Eltek) Parameter Default Value Value Range Description Changed Value Safe Free Save Float Voltage (V) 53.5 54.5 Equalized Voltage (V) 56.4 ok Equalized Enabled Enabled
ok Equalized Perioddays 90 0 to 365 Interval for the system to carry out the equalized 21 Pre.Equ.Chg.Dura.h 0 0 to 48 Duration for the system to carry out the 12 Chg.Curr.Coeff. (C10) 0.15 0.01 to 0.4 When the system carries out the 0.2 Test Stop Volt. (V) 46 42 to 50 When the system carries out the test 46.8 Test Stop Cap. (C10) 0.6 0.4 to 1 When the system carries out the test ok Test Period (days) 0 0 to 365 Interval for the system to carry out ok Test Start Time (X:00) 10 0 to 23 If the periodical tests are enabled, the Disconnect Mode Batt.Volt. Disabled BLVD Enabled Enabled ok BLVD Voltage (V) 44 46.5 LLTD Env.Temp. () -15 -40 to 10 When the environment temperature is Auto Manual Work Mode Safe The system automatically activates/deactivates rectifiers according to this parameter. ZTE Rectifier Setting for Battery ok Generator starting mode ok Auto Generator Mode Generator alam voltage Reports & Checks For PM , 4 times in a Year Voltage Reading of each Cell during charge and discharge Current Reading of each bank during charge and discharge Battery Surface Temperature in the middle of the Bank(Cabinet Temperature is not Sufficient) Battery Internal Resistance / Conductance for State of Health(SOH) Battery Capacity Test and recording of each cell voltage to find the weakest battery for boost charging going to site or by RMS Full Charging of Batteries is required quarterly, Need to work at rectifier side for this purpose Constant Current Charging if Required for reconditionning Rectifier Logs , Settings and Status Difference of voltage reading at rectifier side and the terminal of the battery string Setting of Float voltage, boost voltage and interval of boost charging Visual Inspection of Batteries for Sign of battery swelling , leekage or damage Float voltage temperature compensation setting Tightness of connectors, terminals etc DC Air Con Prventive Maintenance Quarterly Maintenance is the PM! Part of Preventive maintenance PM must be done each quarter.! During the PM actions, make sure the battery is fully recharged Battery is under float charge conditions The charge current is lower than 5A
The easy forgotten points Record the battery voltage and temperature, internal resistance and Clean the battery with wet cloths Visual inspection of battery if there is any sign of leakage from the container or post Measure DC power voltage output and compared with the displayed number on rectifier controller Verify the battery connection, if there is any signs of loosing connection, fasten it!
Trouble Shooting - Batteries No Phenomenon Possible Reasons Solutions 1 Leakage and / or bulge High temperature ; high float voltage; the seal of the battery failed DC aircon faulty. Contact with and prepare to replace the battery; repair the DC aircon. 2 Float voltage lower than 2.20Vpc Internal resistance is uniform or no proper maintenance Equalizing charge for 1224h retest the capacity and see the recovery status. 3 Low back up time/Capacity Undercharge and may be the battery over discharged for a long time. Equalizing charge for 1224h the retest the capacity. Otherwise replace it 4 High temperature on the surface of the case or around the polarity Screw loosed or internal damage;and high charge voltage(constant overcharge) Check the torque and/or the parameters settings of rectifier. 5 High voltage in float charging Screw loosed or undercharge Tighten the screws. Or equalize charge for 12~24 hours. 6 Impedance/resistance increase(compare to other normal cells) Short/open cells and/or plates/ electrolyte deterioration. Charge and retest battery or replace as required. Capacity Reconfirm Make sure fully recharged! Otherwise Boost charge with DG runs for 12- 24 hours Conduct capacity test with shut off the AC mains and drown 60% capacity out of the batteries, or the average voltage is lower than 1.95Vpc. Feedback the results to BSB.