Anda di halaman 1dari 68

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

Moeller GmbH
BU Circuit Breaker
ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 1

The new line of circuit breaker IZM

Part 1: The communicative hardware system


Part 2: Supplement to the communicative hardware
Part 3: IZM communication via PROFIBUS DP
Part 4: Further information about the additional modules
Part 5: Further inf. about the measurement modules

Moeller GmbH
BU Circuit Breaker

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 2

The new line of circuit breaker IZM

Part 1: The communicative hardware system


Communication interfaces on the IZM circuit-breaker

Modes of the IZM parameter assignment module


IZM-XEM-PG(E) with integrated web server

Moeller GmbH
BU Circuit Breaker

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 3

The new line of circuit breaker IZM

Overview of the IZM communication architecture


Data acquisition
and processing

XMP(H)

IZM-XEM-PG
IZM-XEM-PGE

Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Digital input module

Analog output module

XBSS
Trip unit

Digital output module


optocoupler, configurable

Parameter
assignment
module with
integral web
server

Digital output module


relay, configurable

XCOM-DP

Digital output module


optocoupler

Moeller IZM

Digital output module


relay

Circuit-breaker
internal system bus
ZSI module

Output device
e.g. Notebook
with Browser

Parameterization and
visualisation tool via
PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 4

The new line of circuit breaker IZM

Protective note to rule DIN ISO 16016 is to be considered

Structure of the internal system bus with communicative devices

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 5

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Parameter assignment module


with integrated web server

One unit for parameter setting, for


operation and for visualization of Moeller
circuit-breakers IZM based on html
technology

Moeller GmbH
BU Circuit Breaker

System software

PROFIBUS software,
which offers the same option
via the PROFIBUS-DP
(Moeller Software planed for 2004)

Part 1: The communicative hardware system

Protective note to rule DIN ISO 16016 is to be considered

Communication: Local, Ethernet, Internet or PROFIBUS

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 6

The new line of circuit breaker IZM

IZM communication via PROFIBUS DP

Necessary modules for communication via PROFIBUS DP:


XCOM-DP Profibus Module
(external)

Protective note to rule DIN ISO 16016 is to be considered

BSS Breaker Status Sensor


(internal)

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 7

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Parameterization, operation, observation


and diagnostics of IZM circuit breaker

IZM-XEM-PG(E) provides its data in html


format (Masks and data are transmitted together)

No add. software installation is necessary


(Java 2 VM is a premise, e.g. with Internet Explorer)

Data representation in a tree-structure enables


fast access to the requested information
IZM-XEM-PGE offers an additional Ethernet gateway
Remote control of the IZM circuit-breaker with
long-distance data transmission
Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Protective note to rule DIN ISO 16016 is to be considered

IZM parameter assignment module IZM-XEM-PG (E)


with integrated web server

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 8

The new line of circuit breaker IZM

Parameter data can be created and saved


on the PC
Opening, modification and saving of
parameter files which already exist
One IZM-XEM-PG for every Moeller
IZM circuit breaker in the power distribution
system
Application examples:

Preperation of the commissioning in the


office; e.g. paramerterization
No expert know-how required in the system
Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Protective note to rule DIN ISO 16016 is to be considered

IZM-XEM-PG in Offline Mode (no connection to an IZM trip unit)

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 9

The new line of circuit breaker IZM

Communication via RS485 (IZM),


RS232 (to the Notebook)
Parameterization, control and
diagnostics of the IZM with its
communicative modules

Circuit-breaker internal
system bus
Moeller IZM

Parameter settings can be saved


and printed as documentation
One IZM-XEM-PG for all IZM
in a power distribution system
Applications examples:
On-site parameterization and
diagnostics
Fault analysis via event history
Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Protective note to rule DIN ISO 16016 is to be considered

IZM-XEM-PG in Temporary Mode - Local

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 10

The new line of circuit breaker IZM

IZM-XEM-PGE is permanently
connected to a Moeller IZM trip unit

Circuit-breaker internal
system bus

One IZM-XEM-PGE per circuitbreaker


Remote access to the Moeller IZM
circuit-breaker via Ethernet
Application example:
Communication without
PROFIBUS DP
For a small number of circuitbreakers in industry or buildings
For Offshore applications
Moeller GmbH
BU Circuit Breaker

Part 1: The communicative hardware system

Moeller IZM

Protective note to rule DIN ISO 16016 is to be considered

IZM-XEM-PGE in fixed mounted mode with Ethernet communication

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 11

The new line of circuit breaker IZM

Part 2: Supplement to the communicative hardware


Circuit-breaker internal system bus

Overview electronic overcurrent releases


Power and Harmonic measurement functions
Intelligent, external expansion modules
Moeller GmbH
BU Circuit Breaker

IZM Communication Architecture

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 12

The new line of circuit breaker IZM

Overview of the IZM communication architecture


Data acquisition
and processing

IZM-XEM-PG
IZM-XEM-PGE

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Digital input module

Analog output module

Trip unit

Digital output module


optocoupler, configurable

Parameter
assignment
module with
integral web
server

Digital output module


relay, configurable

XCOM-DP

Digital output module


optocoupler

Moeller IZM

Digital output module


relay

Circuit-breaker
internal system bus
ZSI module

Output device
e.g. Notebook
with Browser

Parameterization and
visualisation tool via
PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 13

The new line of circuit breaker IZM

Protective note to rule DIN ISO 16016 is to be considered

The way of the internal system bus

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 14

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

The circuit breaker internal system bus connects all intelligent


modules within the IZM circuit-breaker with each other. In addition
it enables the connection of external additional modules to the
circuit-breaker.
Intelligent, internal modules:

External additional modules:

U, R, D electronic trip units


Power and Harmonic
measurement functions
BSS Breaker Status Sensor

Moeller GmbH
BU Circuit Breaker

XCOM-DP PROFIBUS module


Digital input + output modules
Analog output module
ZSI - module
Parameter assignment module
IZM-XEM-PG (E)

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Cicruit-breaker internal system bus

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 15

The new line of circuit breaker IZM

Maximum assignment on the internal system bus:


Module

Number

Remark

Analog output module


Digital output module with
rotary coding switch

varying coding positions

varying coding positions

Digital output module,


configurable

Digital input module

ZSI - module

Maximum length of the internal system bus:

varying coding positions

10 m

1x 24 V DC supply voltage, termination resistor on last additional module


Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Circuit-breaker internal system bus: System conditions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 16

The new line of circuit breaker IZM

integrated into the trip unit types U, R, D of the IZM without extra
charge
high levels of system availability and minimum installation effort via
safe and simple connection of the modules with RJ 45 jacks

fast reaction times of the entire system


retrofitting of all modules possible in a record time
considerable additional usage and potential for savings by use of the
external additional modules, which enables interfacing of further
peripheral devices to the IZM

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Advantages of the circuit-breaker internal system bus

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 17

The new line of circuit breaker IZM

XZMA

XZMV

XZMV+XT

XZMU (+XT)

XZMR (+XT)

XZMD (+XT)
XZMD

XZMV

XZMA

L-I

L-S-I

XZMV

L-S-I-N-G

XZMU

L-S-I (-N-G)

XZMR

L-S-I (-N-G)

L-S-I (-N-G)

Earth fault protection XT is optional and for type U, R and D even modular for
retrofitting.
Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Type overview of the electronic overcurrent releases

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 18

The new line of circuit breaker IZM

XZMA

Release for power distribution system protection

XZMV

Release for selective (discriminative) protection

XZMU

Release for universal protection

XZMR

Digital release, for external parameterization only

XZMD

Digital release

Circuit breaker with trip units type U, R and D are already equipped with
the internal system bus

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Type overview of the electronic overcurrent releases

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 19

The new line of circuit breaker IZM

IZM trip units:


L

Inverse time-delay overLoad range

A, V, V+XT, U, R, D

Short-time delay short-circuit tripping

V, V+XT, U, R, D

Instantaneous short-circuit tripping

A, V, V+XT, U, R, D

Neutral conductor overload tripping

V+XT, U, R, D

Earth fault tripping (Ground fault)

V+XT, U+XT(A), R+XT(A),


D+XT(A)
+XT = earth-fault release
additional equipment

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Trip units: The different protective ranges

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 20

The new line of circuit breaker IZM

Power
Currents
Voltages
Powers
Cos phi
Energy values
Frequency
The measurement
module is installed
in the IZM on the
rear side of the
trip unit
Moeller GmbH
BU Circuit Breaker

Harmonic
As with Power, with additional
Frequency analysis up to 29th
harmonic
Recording of currents and
voltages in waveform memory
(two ring buffers enable graphic
evaluation of current and
voltage waveshape)

Total harmonic
distortion, form
factor, peak factor

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Power and Harmonic Measurement Functions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 21

The new line of circuit breaker IZM

Advantages of the measurement modules


High level of measurement accuracy of 1% for current and voltage
Communication interfaced via the XCOM-DP and circuit-breaker
Parameter assignment module
Space-saving internal installation in the circuit-breaker
Signalling of events in the network offer extended protective functions
and a higher level of power distribution system protection

Good alternative for external measurement devices


(reduced installation effort and space requirement)

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Power and Harmonic Measurement Functions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 22

The new line of circuit breaker IZM

Application possibilities

Offers connection features for max. 6 additional


potential free binary signals, 24 VDC
Enables the transfer of additional binary
information via the PROFIBUS DP to the field
bus level e.g.:
State of the control panel door
State of the MCCBs

State of the switch-disconnector


Overtemperature in the control panel
State of the control panel forced ventilation
Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Digital input module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 23

The new line of circuit breaker IZM

T-2

T-3
G

Application example:
For use in conjunction with the R or D
trip unit for switchover of the parameter
sets (A and B) saved in the trip unit.

Simple and fast switchover between the


regenerative and mains operation
possible
When used for parameter switchover, all
further inputs of the module cannot be
used

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Digital input module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 24

The new line of circuit breaker IZM

Relay outputs
Control of electromagnetic devices
Rotary coding switch
Configurable
Optocoupler outputs
Transfer of commands and messages
for electronic devices
Rotary coding switch
Configurable

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Variants of the digital output modules

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 25

The new line of circuit breaker IZM

Application possibilities (1)


6 digital outputs available for differentiated trip
causes signalling, warnings, threshold value
overshoots to external signalling devices (e.g.
lamps, horns)
Event controlled operation (switch on / off) of
non-Profibus capable power distribution lements,
e.g. fans, motors, heating or pumps
(which have a different supply and protection).

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Digital output module with rotary coding switch

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 26

The new line of circuit breaker IZM

Application possibilities (2)


Selective switch off of frequency inverters by
early-make overload tripping

Integration in process automation via


time-delayed control with e.g. load pick up
or load shedding
Simple setting of the assignment and the time
delay of the outputs via rotary coding switches

Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Digital output module with rotary coding switch

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 27

The new line of circuit breaker IZM

Application possibilities

All functions of the module with


rotary coding switch including
6 freely configurable digital outputs available
for all event messages, e.g. for
Status messages (on, off, tripped, ready-to-close)
Warnings (overload, load shedding, earth fault)
Trips (overload, short circuit, phase unbalance)
Threshold value overshoot (phase unbalance,
distortion factor)

Configuration possible with IZM-XEM-PG(E) or


remote controlled via PROFIBUS-DP
Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Digital, configurable output module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 28

The new line of circuit breaker IZM

Application possibilities

4 analog outputs, 4-20 mA or 0-10 V available


With the IZM measured values can be easily
output to external analog instruments:
Phase currents and neutral conductor current,
Phase unbalance of the current,
Active power of the individual phases and as
a sum total,

Power factors of the individual phases and as


average value
Frequency, etc.
Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

Analog output module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 29

The new line of circuit breaker IZM

Optimized selectivity in the range between Isd and Ii

Short delay time tZSI = 50 ms with full selectivity


independent of the number of group levels
ZSl locates the short-circuit
Only the next circuit-breaker in the direction of
power flow will be switched off with a short-circuit
and / or earth-fault
Reduces the stresses which occur and the damage
in the power distribution system during a shortcircuit
ZSI module can be retrofitted with minimum effort
at any time
Moeller GmbH
BU Circuit Breaker

Part 2: Supplement to the communicative hardware

Protective note to rule DIN ISO 16016 is to be considered

ZSI module (Zone Selective Interlocking)

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 30

The new line of circuit breaker IZM

Part 3: IZM communication via PROFIBUS DP


Modules for communication via PROFIBUS DP

The 3-step communication concept


The three basic types for cyclic data interchange
Classification of the signals to be processed
Moeller GmbH
BU Circuit Breaker

IZM Communication Architecture

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 31

The new line of circuit breaker IZM

IZM communication via PROFIBUS DP

Necessary modules for communication via PROFIBUS DP:


XCOM-DP Profibus Module
(external)

Protective note to rule DIN ISO 16016 is to be considered

BSS Breaker Status Sensor


internal

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 32

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

BSS Breaker Status Sensor = internal microswitch scanner unit

Internal circuit-breaker information:


1.
2.
3.
4.
5.
6.

Main contacts ON / OFF


Spring charged
Ready-to-close
Tripped signal
Temperature in circuit-breaker
Signal switches on 1st & 2nd
voltage releases

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 33

The new line of circuit breaker IZM

Breaker Status Sensor BSS


- who signalises what?

Einschaltbereitschaft
Ready-to-close

Hauptkontakte (EIN/AUS)
Main contact (ON/OFF)

Federspeicherzustand
Spring charged

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 34

The new line of circuit breaker IZM

XCOM-DP PROFIBUS Modules


Functions:
enables remote operated
on/off switching, reset, etc.

setting and modification of all protection


parameters, measured value settings,
communication parameters, etc.
simple diagnostics by LED status display
support for DPV1 PROFIBUS expansion

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 35

The new line of circuit breaker IZM

Communication without DPV1 (with DPV 0):


Data are transferred exclusively during cyclic data exchange process
Data quantity cannot be changed during operation
Low performance if the quantity of data is too large (e.g. 100 Bytes)

IZM communication with DPV1:


Transfer of the data sets (DS) with up to 245 bytes in only
one additional acyclic telegram

DPV1 telegrams are initiated by an application program,


just transferred once (e.g. with the system software)
Cyclic data transfer runs in parallel
Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

DPV1 functionality supported

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 36

The new line of circuit breaker IZM

XCOM-DP PROFIBUS Module

Additional signals:
time stamp:
each event can be allocated to a time

micro switch on XCOM-DP - Module:


position of the withdrawable circuit-breakers
connected test disconnected
integrated temperature sensor:
temperature in the cubicle
free assignment: 1 input, 1 output

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 37

The new line of circuit breaker IZM

XCOM-DP PROFIBUS Module


System bus connection
(on rear side)

Connections and LEDs:


LED PROFIBUS:
Off:
No voltage on XCOM-DP
Red: Fault on Profibus or
Profibus not addressable
Green: Profibus communication OK
LED internal system bus:

PROFIBUS interface

Moeller GmbH
BU Circuit Breaker

Off:
No system station found
Red: Error on system bus
Green: System bus station found
& communication OK

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 38

The new line of circuit breaker IZM

Signalling switches:

(1) Spring charged S41


(2) Breaker ON/OFF S44
(3) Ready-to-close S40
(4) Tripped S45
(5) Status 1st shunt release S42
(6) Connected position S46
(7) Test position S47
(8) Disconnected position S48
(9) Status 2nd shunt release or
undervoltage release S43
Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Status signals for the communication

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 39

The new line of circuit breaker IZM

Communication
Concept:
1) fast, easy,
master class 1
2) adaption of the
three basic types
3) acyclic data
exchange,
master class
1 or 2

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

The 3-Step

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 40

The new line of circuit breaker IZM

Basic type 1
status + 4 values ( 2 byte)
= 14 byte
Basic type 2
status + 8 values ( 2 byte)
= 26 byte

Basic type 3
status + 14 values ( 2 byte)
= 44 byte
Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

3 Basic types
(choice out of more than
400 data points)

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 41

The new line of circuit breaker IZM

PROFIBUS User Organization Profile

1 Device Classes
1.1 Circuit-Breaker
1.2 Starters
1.3 Switches
1.4 Overload Relay
1.5 Contactor
1.6 Auxiliary Switching Devices
1.7 Control and Protective Switching
Devices (or Equipment)
Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Communication with reference to the

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 42

The new line of circuit breaker IZM

Protective note to rule DIN ISO 16016 is to be considered

Default assignment basic type 1 = Format 1 PNO Profil LVSG

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 43

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Default assignment basic type 2 = Format 2 PNO Profil LVSG

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 44

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Default assignment basic type 3 = Format 3 PNO Profil LVSG

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 45

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Binary Status Information in the Cyclic Message / 1

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 46

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Binary Status Information in the Cyclic Message / 2

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 47

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Control bytes to the IZM circuit-breaker / 1

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 48

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Control bytes to the IZM circuit-breaker / 2

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 49

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Group of data points


Data pionts with same source
Protection parameter set A
Protection parameter set B (not for XZMU)
Extended protection parameters
Parameter for setpoints
PROFIBUS communication parameters
Parameters for metering settings
Device identification data
Circuit-breaker position specifications
Status info. (circuit-breaker on/off, storage spring, etc.)
Alarms
Trips
Setpoint messages
Maintenance information
Circuit-breaker temperature
Temperature in the cubicle
3-phase currents
Current in N-conductor, ground-fault current; equip. spec.
3-phase voltage
Power P, Q, S, energy
cos phi
Frequency, total harm. distortion, form factor, crest factor
Harmonic analysis
Waveform buffer
Log book for events and trips
System time

Moeller GmbH
BU Circuit Breaker

Trip unit
XZMU
XZMR
XZMD
X
X

Breaker
Status
Sensor
XBSS

Comm.
module
XCOM-DP

Measurm.
function
XMP

Measurm.
function
XMH

X
X

X
X

X
X

X
X

X
X
X
X

X
X
X
X
X
X

X
X

X
X
X

X
X
X

X
X
X

X
X

X
X

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

Which is the source for requested information?

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 50

The new line of circuit breaker IZM

Protective note to rule DIN ISO 16016 is to be considered

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 51

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

IZM communication via PROFIBUS DP

Classification of the signals to be processed

Warning

Trip

Parameters / Thresholds

Protective note to rule DIN ISO 16016 is to be considered

Status

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 52

The new line of circuit breaker IZM

Moeller GmbH
BU Circuit Breaker

Part 3: IZM communication via PROFIBUS DP

Signals processed for:


1.
2.
3.
4.
5.
6.
7.
8.
9.
Moeller GmbH
BU Circuit Breaker

Status

Circuit-breaker on
Circuit-breaker off
Stored-energy mechanism
Operation readiness
Voltage release status
Collective warnings
Group trip messages
PROFIBUS write protection
PROFIBUS communication OK

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 53

The new line of circuit breaker IZM

Signals processed for:


1.
2.
3.
4.
5.
6.
7.
8.

Moeller GmbH
BU Circuit Breaker

Warning

Overload
N-conductor overload
Load shedding
Earth-fault
Over temperature
Microprocessor fault
Current phase unbalance
Load acceptance

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 54

The new line of circuit breaker IZM

Signals processed for:

Trip

Overload

Delayed short-circuit

Instantaneous short-circuit

Current phase unbalance

Earth-fault

N-conductor overload

Current phase unbalance (5-50%)


Under-frequency

Voltage phase unbalance


Over-frequency

Undervoltage

Overvoltage

Active power in normal direction

Moeller GmbH
Part 3: IZM
BU
Circuit Breaker
Voltage
harmonic distortion

Active power reverse direction


communication via PROFIBUS DP
Current harmonic distortion

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 55

The new line of circuit breaker IZM

Signals processed for:


Overcurrent
Earth fault overcurrent
Voltage phase unbalance
Undervoltage
Current harmonic distortion
Peak factor
Under-frequency
Active power in normal direction
Apparent power
Reactive power reverse direction
Inductive power factor
Long-time average reactive power
Moeller GmbH
BU Circuit Breaker

Parameters / Thresholds
N-conductor overcurrent
Current phase unbalance
Current long-time average value
Overvoltage
Voltage harmonic distortion
Form factor
Over-frequency
Active power reverse direction
Reactive power in normal direction
Capacitive power factor
Long-time active average power
Long-time average apparent power

Part 3: IZM communication via PROFIBUS DP

Protective note to rule DIN ISO 16016 is to be considered

IZM communication via PROFIBUS DP

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 56

The new line of circuit breaker IZM

Part 4:
Further information

about the additional modules

Moeller GmbH
BU Circuit Breaker

IZM Communication Architecture

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 57

The new line of circuit breaker IZM

Parameter set
switchover

Status display
System bus,
module and inputs

with two stage


rotary coding switch
(no further inputs
can be assigned)

Systembus

or
PROFIBUS Input
6 digital inputs
possible

Moeller GmbH
BU Circuit Breaker

Max. 2 inputmodules per IZM

Part 4: Further inf. about the additional modules

Protective note to rule DIN ISO 16016 is to be considered

Digital input module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 58

The new line of circuit breaker IZM

Status display
System bus,
module and
outputs
Output assignment 1
Trips, e.g. overload
tripping, short-delayed
short-circuit tripping,
instantaneous
short-circuit tripping,
earth-fault trip,
earth-fault alarm,
neutral conductor trip

Moeller GmbH
BU Circuit Breaker

Systembus

Part 4: Further inf. about the additional modules

Selection of the delay


time
(0; 0,2; 0,5; 1, 2s)
and the
output assignment via
10 stage rotary coding
switch
Output assignment 2
Alarms, e.g. early-make
trip indication, trip unit
fault, load shedding,
load acceptance,
temperature alarm,
phase unbalance

Protective note to rule DIN ISO 16016 is to be considered

Digital output module with rotary coding switch

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 59

The new line of circuit breaker IZM

Assignment of the 6 outputs


via software

Status display
System bus,
module and
outputs

e.g. with:
Systembus

Status
Warnings
Trips
PROFIBUS output bits

Active parameter set


Threshold values

Moeller GmbH
BU Circuit Breaker

Part 4: Further inf. about the additional modules

Max. 2 analog
output modules
per IZM

Protective note to rule DIN ISO 16016 is to be considered

Digital, configurable output module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 60

The new line of circuit breaker IZM

Status display
System bus,
module and
outputs

Max. 2 analog
output modules
per IZM

Systembus

1st module

Output assignment
via 10 stage
rotary coding switch

Output

AO1

AO2

AO3

AO4

Switch position
I
U
P
cos phi

I L1
U L1-L2
P L1
cos phi L1

I L2
U L2-L3
P L2
cos phi L2

I L3
U L3-L1
P L3
cos phi L3

IN
U L1-N
S total
I phase unbalance
cos phi

Moeller GmbH
BU Circuit Breaker

Part 4: Further inf. about the additional modules

2nd module

Protective note to rule DIN ISO 16016 is to be considered

Analog output module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 61

The new line of circuit breaker IZM

Function selection via


rotary coding switch
OFF

ZSI Module deactivated

ZSI Module only effective for


short-delayed short-circuit

ZSI Module only effective for


earth-fault protection

S+G

ZSI Module only effective for


short-delayed short-circuit
and earth-fault protection

Test

Test position for verifying


the ZSI functionality

Systembus

Moeller GmbH
BU Circuit Breaker

Part 4: Further inf. about the additional modules

Protective note to rule DIN ISO 16016 is to be considered

ZSI module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 62

The new line of circuit breaker IZM

Inhibit signal - output for tie switch


Systembus

Inhibit signal - input


Inhibit signal - output
Inhibit signal for the medium voltage
range (transformer protection)

Moeller GmbH
BU Circuit Breaker

Part 4: Further inf. about the additional modules

Protective note to rule DIN ISO 16016 is to be considered

ZSI module

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 63

The new line of circuit breaker IZM

Part 5:
Further information

about the measurement modules

Moeller GmbH
BU Circuit Breaker

IZM Communication Architecture

Protective note to rule DIN ISO 16016 is to be considered

IZM Communication Architecture

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 64

The new line of circuit breaker IZM

Current measurement :

1. Currents of

L1 / L2 / L3 / N / G

2. Thresholds

*
*
*
*
*

overcurrent in phase
earth-fault
overcurrent in N conductor
phase unbalance of the current
current long-time average value

3. Extended protective functions


* phase unbalance
* long-time average value
* distortion factor

Moeller GmbH
BU Circuit Breaker

Part 5: Further inf. about the measurement modules

Protective note to rule DIN ISO 16016 is to be considered

Power and Harmonic measurement functions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 65

The new line of circuit breaker IZM

Current measurement :

4. Measurement accuracy
with the use of highly accurate Rogovski coils (measurement transformer):
+/- 1%
+/- 20%

in a range from
in a range from

0A

if < 0.01 x In

0.1 - 1.25 x In
0.01 - 0.1 x In
1.25 - 40 x In

Current evaluation values as rms values

Moeller GmbH
BU Circuit Breaker

Part 5: Further inf. about the measurement modules

Protective note to rule DIN ISO 16016 is to be considered

Power and Harmonic measurement functions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 66

The new line of circuit breaker IZM

Voltage measurement :

1. Phase and main pole voltage


2. Thresholds

3.

* undervoltage
* phase unbalance of the voltage
* overvoltage

Extended protective functions


* phase unbalance
* under voltage
* overvoltage

Moeller GmbH
BU Circuit Breaker

Part 5: Further inf. about the measurement modules

Protective note to rule DIN ISO 16016 is to be considered

Power and Harmonic measurement functions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 67

The new line of circuit breaker IZM

Voltage measurement :

4.

Measurement accuracy
An external voltage transformer kit is required. It measures the
conductor voltages between the phases L1 / L2 / L3 .
These values are isolated and handled by the Analog-Digital converter (ADC).
+/- 1% in a range from
+/- 5% in a range from

130 - 1150V ( main pole voltages )


15 - 130V

0 V if < 15V
Voltage evaluation values as rms values

Moeller GmbH
BU Circuit Breaker

Part 5: Further inf. about the measurement modules

Protective note to rule DIN ISO 16016 is to be considered

Power and Harmonic measurement functions

ILS-P / W. Wagner Aug 03, 05 IZM comm. with PROFIBUS DP , page 68

The new line of circuit breaker IZM

Anda mungkin juga menyukai