- K. Arputharaju,
Assistant Executive Engineer /
Operation,
Basin Bridge Gas Turbine Power Station,
TANGEDCO, TNEB Ltd., Chennai 600
012.
1
REQUIREMENTS OF POWER
SYSTEM
It must supply energy practically everywhere the customer demands.
The load demands vary with time. The system must able to supply this
ever changing demand.
The delivered energy must meet certain minimum requirements in
regard to quality. The following factors determine the quality:
a) The system frequency must be kept around 50Hz with
a variation of 0.05Hz.
b) The magnitude of the bus voltages are maintained within
prescribed limit around the normal value. Generally the
voltage variation should be limited to 5%.
The energy must be available with high reliability.
The energy must be delivered without overloading any element in the
power system.
The energy must be delivered at minimum cost.
TYPE OF LOADS:
TYPE OF LOAD
PHASOR
PHASE
ANGLE
I
V
R
I
= 0
P>0
Q=0
= +90
P=0
Q>0
= - 90
P=0
Q<0
0<<+90
P>0
Q>0
V
L
L
4
TYPE OF LOADS:
TYPE OF LOAD
PHASOR
PHASE
ANGLE
I
R
C
-90<<0
P>0
Q<0
P=0
Q=0
Tuned to
Resonance
IL = Ic
I
V
C
Ic
IL
PL = Pc
Energy travels
-90<=<=+90
TYPE OF LOADS
CONTROLS
FREQUENCY
CONTROLS
REAL POWER
V1
V2
jX
P jQ
1.
2.
3.
Take V1 as reference.
V2=V1-jXI -----------------------------------(1)
V1 * I = P jQ
I = (P-jQ) / V1 ------------------------------(2)
Substitute (2) in (1)
V2 = V1 jX [(P/V1) j(Q/V1)]
V2 = [V1 (X/V1)Q] j(X/V1)P]
VECTOR DIAGRAMS:
V2 = V1- X Q - j X P
V1
V1
BOTH DROPS EQUAL
DOUBLE P
V1
V1
X Q
V1
V2
DOUBLE Q
X
V1
X P
V1
V1
Q
V2
V2
XP
V1
2X Q
V1
2X P
V1
LAGGING MVAR
GEN. VOLTAGE
EXCITATION LESS
LAGGING MVAR
GEN. VOLTAGE 10
CONNECT
CAPACITORS
LIGHT LOAD
CONDITION
CONNECT
REACTORS
TO CONTROL
VOLTAGE
S.C.C.
O.C.C.
a
1.0
C
E
c
o
SCR = o Fo
o Fs
c Fo
b Fs
Fo
c Fo
a Fo
Fs
1
a Fo / c Fo
AD
AE
DE
AB
AC
BC
FIELD CURRENT
1
Per unit voltage on open circuit
Corresponding per unit current on short circuit
1
Xd
12
SCR
AIR GAP
WEIGHT
SIZE
TRANSPORTATION
PROBLEM
Present trend is to build low value of SCR since fast acting excitation
system available.
13
B
E
IX
d
Cos
CASE-I:
MW
Multiply
both sides
by
V
D V
C
Xd I
MVAR
EV Sin = VI Cos = REAL
Xd
POWER
At =90, We get the maximum power i.e. the theoritical stability line.
CASE-I I:
In ABC, CD=AC AD;
In BCD, CD=IXd Sin
In ABC, AC=E Cos & AD = V
IXd Sin = E Cos - V ; Multiply both sides by V , We get
Xd
EV Cos V2 = VI Sin = REACTIVE POWER
Xd
Xd
14
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
15
16
17
III) COMPARISON
MW = 50
p.f.=cos(6.5)=0.994 lag
MVAR = 6
V=(MVA X 106)/(3 X
= -- (No measurement)
V = 11.2 KV
Iarm.)
Iarm.)
18
A.
B.
C.
D.
E.
CAPABILITY CURVE