Ovation Safety

Instrumented System
(SIS) Overview

EMERSON Process Management


Power and Water Solutions

Copyrighted Material / Duplication Prohibited

Objective
Upon completion of this module, you will be able to define
Basic Process Control System

Safety Instrumented System

Safety Instrumented Function

Ovation SIS hardware architecture

Ovation SIS software architecture

Ovation SIS capacities

Ovation SIS building blocks

Project procedures

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-2

Part-1
Safety Instrumented
System (SIS) Basics

EMERSON Process Management


Power and Water Solutions

Copyrighted Material / Duplication Prohibited

Behavior of a process
Emergency response

x x

Passive protection
(example: bund)

Mitigate
Mitigate

Active protection
Incident

Prevent
Prevent

(example: Relief valve, rupture disk)


SIS
(SIFs)

Trip level alarm


operator
process alarm
Process
Value

EMERSON Process Management


Power and Water Solutions

intervention

normal behaviour

Course OV 236 Rev 2 01/02/2010

BPCS
(HMI & Alarm Handling)
BPCS
(Process Control)

Copyrighted Material / Duplication Prohibited

1-4

Why BPCS?
A Basic Process Control System (BPCS) compares the
process values continuously against Operator set
points and regulates final control element to maintain
those set points.
Ovation Automation System is a BPCS.

It regulates the process to maintain desired:


Quality
Rate of production
Cost of production

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-5

Why SIS?
To Reduce RISK so as to:
take the process to the Safe State at the shortest
possible time (ESD)
allow process to go ahead when per missives and
interlocks are through (BMS)
mitigate the risk if the incidence happens in the plant
(FGS)

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-6

Various Functions
Safety Instrumented Function
A Safety
Instrumented
Function (SIF) is a combination
Control
Function
of sensors, Logic Solver and final elements with a
specified safety integrity level that detects an out of
limit condition and brings the process to a
Safety Function
functionally safe state.
SIF1, monitors a high pressure condition and closes
the solenoid valve to stop catalyst flow to avoid a
hazardous event.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-7

Terminology
BPCS: Basic Process Control System A DCS.
Intention is to control the QUALITY of the product by
process control.
SIF: Safety Instrumented Function A smallest
building block of a SIS. Many SIFs make a SIS.
SIS: Safety Instrumented System Intention is to
reduce RISK to acceptable level by prevention and/or
mitigation.
IL: Integrity Level The level of risk reduction
When more than
(Targeted / achieved)
one ILs are
SIL: Safety Integrity Level
applicable,
EIL: Environmental Integrity Levelhighest one is
CIL: Commercial Integrity Level qualifying IL.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-8

Safety Instrumented Function (SIF)

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-9

Safety Instrumented Systems (SIS)


A Safety Instrumented System (SIS) consists of sensors, Logic Solvers
executing SIFs and final control elements. A SIS will typically execute
multiple SIFs. The example below consists of a SIS executing SIF1 for
high pressure and SIF2 for high temperature.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 10

Failure The main concern

Why things fail?


When Stress is more than strength, things fail!

Why stress can be more than the strength?


Natural calamities :: Random Failures
Man made mistakes :: Systematic Failures

Modes of failure
Safe / Dangerous
Detected / undetected

Behavior of failures
On demand
Average

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 11

Failure rates a basic measure

Failure record of the device (element of SIF): No of devices :: No.


of hours of operation :: No of devices failed. This will help to
determine Failure rate of the device.
Failures / Year ()

is not a constant, but it changes with time. of a new system is


minimal and as it ages, it rises exponentially. In other words,
probability of failure increases with time.

We can find an average of probability of failure over a period of


time Pavg.

Failures are of two types Safe and Dangerous.

What matters is dangerous failures, which put the process in


dangerous states.

Also probability of dangerous failure matters the most when the


system is required to do its intended job than it is idle or not in
demand.

Hence, the term Probability of failure in demand (average)


of a SIF is of key importance
in Safety engineering.
Course OV 236 Rev 2 01/02/2010
EMERSON Process Management
Copyrighted Material / Duplication Prohibited
Power and Water Solutions

1 - 12

Safety Integrity Level (SIL)


Each SIF is designed to meet a Safety Integrity Level (SIL). A SIL is
determined by a target risk reduction shown in the right column of the
table below.
Various qualitative or quantitative methods can be used to calculate
the target risk reduction which is a combination of likelihood and
consequence of an event.
Safety Integrity Level (SIL)

Target average Probability of


Failure on Demand
(Demand Mode of Operation)

Target Risk Reduction

> 10-5 to <10-4

>10,000 to <100,000

> 10-4 to <10-3

>1,000 to <10,000

> 10-3 to <10-2

>100 to <1,000

> 10-2 to <10-1

>10 to <100

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 13

Safety Integrity Level (SIL)


To ensure a SIF will perform on demand, the combination of the
sensors, Logic Solver and final elements together must meet a
Probability of Failure on Demand (PFD).
Assuming that a target risk reduction of SIL3 is required, then the
failure rates of the instruments and Logic Solver combined must fall
within the PFD of > 10-4 to <10-3.
Safety Integrity Level (SIL)

Target average Probability of


Failure on Demand
(Demand Mode of Operation)

Target Risk Reduction

> 10-5 to <10-4

>10,000 to <100,000

> 10-4 to <10-3

>1,000 to <10,000

> 10-3 to <10-2

>100 to <1,000

> 10-2 to <10-1

>10 to <100

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 14

SIF SIS - SIL


Be particular about the usage of these
acronyms!

Many SIFs can make a SIS


A SIF has a SIL but SIS does
not have a SIL
Customers ask for a SIL rated
system a misnomer
SIL is not a constant!
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 15

BPCS SIS Integration


Data is often passed between a BPCS and the SIS for coordination and
interlocking. The BPCS and SIS are typically from different vendors
which can make the integration effort extensive.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 16

Orientation
Knowing the basic requirements of the Safety Engineering, the
system training is required by the following:

The Design Group (End Customer, EPC, Safety


consultant)
The Safety Engineering Group (Vendor
Marketing, Proposals & Sales, Engineering)
The Operations and Maintenance Group (O&M of
End Customer)
Every phase of the Life Cycle can call upon in-depth study of the
every subject, however further training is intended for the
understanding of the Safety Instrumented System Hardware
requirements and implementation requirements and techniques
as required by the Operations and Maintenance Group of
Marafiq at Yanbu-II.
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 17

A Safety System components


Safety Critical components:
SIL rated Field Instruments and Equipment and interface devices.
SIL rated Logic Solver(s)

SIL rated interface devices and accessories

Qualified hardware design

Qualified programming tools and components

Dedicated and certified communication channel

Non-safety critical components:


Interface to DCS

HMI and HMI builder tools

Interface to third party systems

Other supporting functions

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 18

Part-2
Ovation SIS System

EMERSON Process Management


Power and Water Solutions

Copyrighted Material / Duplication Prohibited

Emersons Control and Safety


systems
RS-3 DCS
DeltaV
DCS
DeltaV SIS
Standalone DCS

WDPF DCS
Ovation
DCS
Ovation SIS

Standalone SIS

ICSS

Third Party
Safety System
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 20

Ovation SIS Architecture

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 21

Ovation SIS - Hardware


Hardware components:
Safety Logic Solvers
Safety Data Server with Power Supply
SIS Net repeater / SIS Net extender
Power Supplies and diodes
Interface devices Safety Relay; Safety Barrier
SIS LAN Switches
SIS Routers
Dedicated Ovation controller

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 22

Ovation SIS Safety Logic


Solver(SLS)
Read Inputs
Resolve and
execute Safety
Logic
Deliver Outputs
Universal IOs 16
per SLS
Redundant
configuration
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 23

Ovation SIS Safety Data Server


(SDS)
Load the Logic
Solvers
Communicate with
the DCS system
Provide Diagnostic
information
Execute noncritical safety
functions like
Alarm and
Graphics tasks
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 24

Ovation SIS SISNet repeater

EMERSON Process Management


Power and Water Solutions

Provide as a
dedicated
communication
device between
Logic solvers
Provide to extend
the Safety
network
Handle Safety
critical
communication
protocol

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 25

Ovation SIS Capacity Chart

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 26

SIS I/O Hardwired IOs


Each Logic Solver has 16 I/O channels. The channels are universal
Analog Inputs

HART Analog Inputs

HART Two-state Outputs

Discrete Inputs

Discrete Outputs

SLS 1508

SLS 1508

SLS 1508

SIF1

SIFX

SIFX

+
-

+
-

Ch1....Ch16

Ch1....Ch16

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 27

SIS I/O Soft IOs - Secure


Parameters
Ovation Logic Solvers communicate with each other using peer to peer
communications through secure parameters and secure parameter
references. All Logic Solvers under the same controller can read any
secure parameters on the Local Peer to Peer. Each Logic Solver has 16
High-density secure parameters that can be broadcast on the Local
Peer to Peer.
SLS 1508
SIF1

Secure Parameter
EMERSON Process Management
Power and Water Solutions

SLS 1508

Local Peer to Peer

SIFX

Secure Parameter Reference


Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 28

SISNet Repeaters and SISNetwork


SISNet Repeaters provide communication between Logic Solvers that
are attached to different controllers for Remote Peer to Peer
communications. Only Boolean data can be transferred between SIS
modules on different controllers and a total of sixteen Booleans can be
broadcast by a Logic Solver.
SLS 1508

SLS 1508

SLS 1508

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

SLS 1508

Copyrighted Material / Duplication Prohibited

1 - 29

SIS LAN
SIS LAN is configured of SIS Data Servers (SDSs). The Switch is uplinked
to the router. Refer to typical SIS architecture shown on next page.
Components of SIS Network include
Ovation Controller OCR1100
For dedicated traffic and secondary functions

SIS Data Server SDS


Main communication gateway to Ovation LAN

SIS Logic Solver SLS1508

CISCO Switch IE3000


Forms a SIS LAN

CISCO Routers R2801


Interface between Ovation and SISLAN

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 30

Ovation SIS Network Architecture

Note: All components are present in Redundant Configuration.


EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 31

Ovation Applications

EMERSON Process Management


Power and Water Solutions

Copyrighted Material / Duplication Prohibited

Integrated Yet Separate!


The BPCS and SIS systems share :
Common Database
Common Applications
Common Network and devices for Nonsafety Critical traffic
Dedicated Network and devices for Safety
Critical traffic
Next slides show the common environment
already existing for the Ovation BPCS.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 33

Ovation SIS - Applications


Main Applications:

Developer Studio
Control Builder
Other Ovation Applications

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 34

SIS - Applications

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 35

SIS - Applications

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 36

SIS - Applications

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 37

SIS - Applications

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 38

Ovation SIS Alarm


All SIS signals can be identified using a special characterization called
as S in the alarm window. Please refer to the AY column in the alarm
window as shown on next page. Pre-trip and trip alarms are notified by
the same colors as in Ovation DCS. Ovation SIS has alarms for

Sensor pre-trip thresholds

Sensor trip thresholds

Voter Alarm

SOE Alarm

Trip Alarm

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 39

Ovation Alarm Window

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 40

Ovation SIS User Rights


Specific user rights are allocated for SIS functions. Details below shows
how the Ovation SIS roles are categorized for different users.
Operator
SIS-Allow test Mode on-off

SIS Engineer

SIS - Allow test Mode on-off


SIS Enable control functions
SIS Enable Tuning functions
SIS Enable Enter Value

EMERSON Process Management


Power and Water Solutions

Note: Any change in the SIS control function in


the future is not allowed and in case if there is
any mandatory reason to make change, then it
is expected from the person to follow the
proper procedure/channel and inform the right
person before making any change.
If the change is considered to be relevant then
the right person will be allocated this task and
the changes will be made. Changes in the
logic, ranges, loading SLS, loading OCR is not
permitted.

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 41

Engineering / Operator Roles

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 42

Trends & Historical reviews


All SIS signals are available on the Historical alarms, trends, reviews
and its past values can be viewed for easy analysis. Operator can view
data in graphical form or in data form.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 43

Sequence of Events (SOE)


SOE is a feature available on an Historian which shows timestamp for
events that occur in the process.
Operator can make use of SOE to analyze the different causes which
caused a trip along with the timestamps.
Further information given from the SOE can be used by Operational
personnel to further investigate on a trip and to avoid such occurrence
in the future.
SOE shows
Date

Time

Point Name

Description

State (Normal/Trip)

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 44

SOE Window

Fig. Shows a sample on how SOE are recorded onto the historian and is
available on all Operator workstation which can be utilized for
analysing past values and for other important reason. SOE together
with SIS Master Trip First Out will help maintenance people to easily
judge the root cause of failure and to avoid such failure in the future.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 45

Graphics Overview
Graphics offers,

First Out

Thresholds, Voting logics

Bypasses status

Acknowledge alarms

Trip Status for all protection signals

Delays

Conditions to Activate Protections

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 46

Graphics Window

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 47

SIS Diagnostics
Although there is no Diagnostic application available for SIS, we usually
show Diagnostics on Graphics which shows all SIS related components,
their status and hardware errors.
Diagnostics page offers the following Information
Logic Solver (SLS) CRC

SIS Network Architecture

Switch Diagnostics, Port Status, Power ON-OFF

Ovation Controller (OCR) Status and Mode

Logic Solver (SLS) Status (Active/Standby)

Channel Configuration (Click on the resp. Logic Solver and a popup window appears showing the Channel Configuration for that
SLS)

SIS Data Server (SDS) Status Active/Standby Mode

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 48

Diagnostic Window

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 49

Ovation SIS
Components

EMERSON Process Management


Power and Water Solutions

Copyrighted Material / Duplication Prohibited

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

OW331_47.pdf
Copyrighted Material / Duplication Prohibited
1 - 51

SIS Function Blocks


IO
IO

Logic
Logic
Logic

Functions
Functions
Functions

Timing
Timing
Timing

Special
Special
Special

Connectors
Connectors

SIS connector algorithm


LSAI LSAND LSBFI LSOFFD
LSAVTR
LSAVT
SISconnector
connector algorithm
LSOFF LSAVTR SIS
table algorithm
LSAI
LSAI LSAND
LSAND LSBFI LSOFFD
R
table
D
table
LSNAN LSBF
LSDVT
LSDI LSNAN
LSOND LSDVT
GSECPARAMREF
LSNAN
D
O LSOND LSDVT
R
LSDI
GSECPARAMREF
LSDI
LSBFOLSOND
LSBFO
GSECPARAMREF
R
D
LSCM
LSDO
LSNDE
LSTP
LSCEM
NONSECPARAM
LSDO
LSDO LSNDE
LSNDE LSCMP
LSTP
LSTP LSCEM
LSCEM
NONSECPARAM
NONSECPARAM
P
LSDV LSNOR
LSDVC
LSNOR
LSLIM
LSRET
LSSEQ
SECPARAM
LSDVC
LSNOR
LSLIM
LSRET
SECPARAM
SECPARAM
LSNOR LSLIM
LSLIM LSRET
LSRET LSSEQ
LSSEQ
SECPARAM
C
LSNOT
LSBDE

LSSTD
SECPARAMREF
LSBD

LSNOT
LSNOT LSBDE

LSSTD
SECPARAMREF
SECPARAMREF

LSNOT LSBDE

LSSTD
SECPARAMREF
LSCAL
E

LSOR
LSOR LSALM

LSCALC

LSOR LSALM

LSCALC

C
LSAL
LSPDE
LSPDE

LSOR LSMID
LSCALC

LSPDE
LSMID

LSRS
LSRS

LSRS LSMI

LSPDE

LSSR
LSSR

D
LSXNO
LSXNO

LSRS

LSSR

LSXOR
LSXOR

LSXNO

LSXOR

1 - 52

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

SIS Algorithm Palette - IO

Analog Input Accepts a single analog signal from an I/O


channel and makes it available to other algorithms.
Digital Valve Controller Similar to a digital output
algorithm,
however it drives a two-state analog output channel
connected
to a Fisher Controls DVC6000. Contains parameters for
partial
stroke testing.
Digital Input Accepts a single digital input from a twostate
field device and makes the processed physical input
available to
other algorithms.
Digital Output Drives an output channel to a solenoid or
other
final element using a 24VDC channel.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 53

SIS Algorithm Palette - Logic

Calculation Logic Evaluates an expression you


define in structured text including mathematical
functions, logical operators, constants, and
parameter references.

Comparator Compares a digital value with a


compare value 1 and sets a LT, GT, EQ, or NEQ
output. Additionally, a compare value 2 can be
used to determine if the value is in range INRGE.

Limit Limits an input value between a high and


low limit. A limit indicator signals whether the value
was limited high or low.

Middle Signal Select Selects a middle value


input from multiple analog inputs. When there is an
even number of inputs, the average of the middle
two are used as the output. As many as 16 inputs
may be used.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 54

SIS Algorithm Palette - Logic

Alarm Performs alarm detection on an analog


input you specify.

Bi-directional Edge Trigger Generates a


True(1) digital output when the digital input makes
a False-to-True transition or a True-to-False
transition.

Boolean Fan In Generates a digital output based


on a binary weighted input (up to 16 inputs), and
first out trapping.

Boolean Fan Out Decodes a binary weighted


input into as many as 16 bits.

Logical And Performs an AND function on as


many as 16 inputs.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 55

SIS Algorithm Palette - Logic

Logical XOR Performs an exclusive OR function


on 2 digital inputs.

Neg-directional Edge Trigger Generates a True


(1) digital output when the digital input makes a
negative (True-to-False) transition.

Pos-directional Edge Trigger Generates a True


(1) digital output when the digital input makes a
positive False-to-True transition.

Reset Set Flip Flop Generates a digital output


value based on NOR logic of the reset and set
inputs.

Set Reset Flip Flop Generates a digital output


value based on NAND logic of the set and reset
inputs.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 56

SIS Algorithm Palette - Timers

Off Delay Delays the transfer of a False(0) digital


input value to the output by a specified time.

On Delay Delays the transfer of a True(1) digital


input value to the output by a specified time.

Retentive Timer Generates a True(1) digital


output after the input has been True for a specified
time period.

Timed Pulse Generates a True(1) digital output


for a specified time duration when the input makes
a positive (False-to-True) transition.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 57

SIS Algorithm Palette Special


Functions

Analog Voter Monitors as many as 16 Analog


Inputs and
initiates a safety procedure if a predetermined
number of inputs vote to trip.

Digital Voter Monitors as many as 16 digital Inputs


and initiates a safety procedure if a predetermined
number of inputs vote to trip.

Cause Effect Matrix Associated 16 inputs (Causes)


with 16 outputs (Effects) to control one or more final
elements.

State Transition Diagram Employs a state


machine to determine the algorithms state based on
the state of inputs and active transitions.

Step Sequencer Defines as many as 16 states,


and as many as
16 output values may be defined in each state. May
automatically increment and decrement through the
states.
Course OV 236 Rev 2 01/02/2010
EMERSON Process
Management
Copyrighted Material / Duplication Prohibited
Power and Water Solutions

1 - 58

SIS Algorithm Palette - Connectors

External Input Point Reads data from outside the current sheet,
but within the same SIS Module.

External Output Point Writes data to a point, which can be


referred by some other control sheet, within the same module

Secparam Sends Boolean data to other SIS modules.

Secparamref Receives Boolean data from other SIS modules


from within the same SIS Node.

Gsecparamref - Receives Boolean data from other SIS modules


from an external SIS Node.

Nonsecparam - Receives non safety critical boolean data from


other SIS modules or BPCS control sheets/tasks.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 59

SIS Tree
Database

Point Database

Network

Analog Points

Unit

Digital Points

Drop

Module Points

Device
SISLAN
SDS

Node Points

SDS
SLS
Control Module
Control Sheet
Secure

Parameters

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 60

Most generic SIS Functions - ESD


Emergency Shutdown Function:
1. Acquisition and conditioning
2. Trip Voting
3. Trip resolution
4. Drive Output

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 61

Logic 1 = Normal

Most generic SIS Functions - ESD


CEM

AI
AI

DO

AVTR

DVC

AI
DI

SP
DVTR

DI

E1
C1

SPR

C3
C4

RST
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

E3

C2

NSPR

E2

X
X

X
X

Copyrighted Material / Duplication Prohibited

1 - 62

Most generic SIS Functions - BMS


Reset
Trip

Start PB

Fan On FB

Tripped

Ready

Air On

From

Prepare Purging
4

Purge
Conditions FB

Fan Off FB

all States
Open Vent 11

Vent
Open FB

5 Purging
Purge Time
Over

Valves
Close FB

Stop
Stop
Stop
PBPB
PB
6 Prepare Ignition

Close Valves 10

Ignition
Conditions FB

Stop PB
9
Burner On
EMERSON Process Management
Power and Water Solutions

8
Post Ignition
Course OV 236 Rev 2 01/02/2010

Post Ignition Time Over

Ignition
Copyrighted Material / Duplication Prohibited

Safety Time Over

1 - 63

Ovation SIS Sequence execution


An Excel template is available to support
such an approach and to document the
functional requirements.

Outputs

Trips
State
Transition
Diagram
Transitions
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 64

Secure Write Mechanism


A Secure Write Mechanism, TUV-certified software, allows you to
change the value of a writeable parameter in a Logic Solver. This
significantly reduces the risk of an unintentional change to the Logic
Solver by the following means:
Does not accept the type of change message that is sent to a
Control Module.
Only accepts a new pair of change messages, command and
confirm
Only accepts configuration changes if the SLS 1508 is unlocked

Integrity checks include, checking for error corruption and a two


minute timeout between the command and confirm in all
applications except Ovation Operate Run where the timeout is 1
minute.
SLS 1508
Bypass
Secure Write
Mechanism

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 65

Standalone SIS project implementation Outline

Separate SIS Database at Engineering Centre

Database server is created and Ovation SIS installed with


licenses

For multiple units power project, it is convenient to work


on the single unit and then multiply

Create the SIS tree and organize the devices around the
database server

Implement the One-burner-One-Unit project

Test and verify the functions along with the Graphics

Integrate with BPCS

Multiply for other burners and other units

FAT

Commissioning and startup

SAT

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 66

Steps to construct a Safety Project

Receive Customer Inputs


Compare IO and Logic and clear the queries
Freeze the IO List and Logic to 90%
Create the Database server
Estimate Logic solvers and SDS Go for HW design
Freeze BOM
IO Allocation to SIFs
Conceptual Design HW and SW Customer approval
Start HW Detail Design
Start Prototype making for Control modules, Graphics for
typical unit
Complete Implementation of modules and Graphics
Generate Internal test plans
Generate FAT Plans Get Customer approvals
Internal testing and verification
Integration with BPCS and verification

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 67

Summary

Basic Process Control System

Safety Instrumented System

Safety Instrumented Function

Ovation SIS hardware architecture

Ovation SIS software architecture

Ovation SIS capacities

Ovation SIS building blocks

Project procedures

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 68