Critical Power

SG Series 10-40 kW

ales Presentation

ecember 2013

1
2012 General Electric Company

Product Range

UPS SG Series 10 kVA PurePulse

10kW

UPS SG Series 15 kVA PurePulse

15kW

UPS SG Series 20kVA PurePulse

20kW

UPS SG Series 30kVA PurePulse

30kW

UPS SG Series 40kVA PurePulse

40kW

CE Marked, 3x380/400/415V In & Out,


50/60Hz
Page 2
GE Critical Power
SG 10-40 kVA Presentation 2013

1
UPS Configuration

Double conversion technology


Designed for Mission Critical Applications
True On-Line Double Conversion
VFI technology
Voltage and Frequency
Independent
Inverter output transformer for
load galvanic separation

Bypass
supply

Rectifier
Rectifie
r
supply

SG CE classification: VFI SSS 111


VFI Voltage & Frequency Independent
Frequency Converter operation
available
SS

Static bypass

Inverter

AC

DC

Load
AC

DC

Battery bank

Class 1

Output voltage THD < 8% for all loads


THDv < 2% linear loads
THDv < 3% non-linear loads

111 Class 1 performance


Exceeding Class 1
Best in Class dynamic response:
+/- 3% at load step: 0-100%-0
+/- 2% at load step: 0-50%-0

SG Series

Page 4
GE Critical Power
SG 10-40 kVA Presentation 2013

UPS configuration
Double conversion with inverter output isolation transformer
Q2
MANUAL BYPASS

SSM
K6
CB4

RECTIFIER

INVERTER

Q1
K7

LOADS

INPUT MAINS

AUTOMATIC BYPASS

INVERTER
TRANSFORMER

CB3

BATTERY

Double conversion (VFI) technology with output isolation transformer


Automatic bypass for overloads, short circuit and UPS disturbances
conditions
Manual bypass for UPS maintenance operations without load
interruption
Protection safety devices integrated
Page 5
GE Critical Power
- back feed protection K6 standard
SG 10-40 kVA Presentation 2013

Backfeed protection
IEC 62040-1 : For fixed installation UPS, backfeed protection may be
provided internally or externally to the UPS in the a.c. input line
Standard feature inside UPS
cabinet
No additional cost required
No addition installation required

Backfeed contactor

static bypass

Fully compliant with IEC 62040-1


Compliance to UPS installation
safety requirements
Safer operating condition
Safer operation for end users
and
service engineers

Input
mains

Rectifier

Inverter
DC

AC
DC

Load
AC

Battery bank

preventing feedback to the mains


from the inverter in case of mains
failure and a fault in the bypass
circuit
Page 6
GE Critical Power
SG 10-40 kVA Presentation 2013

UPS configuration

dvantages - Output Isolation Transformer


No DC component in output (galvanic isolation by
transformer)
Transformer less UPS DC components are controlled
electronically
Lower DC voltage less number of batteries per string
(30-32 blocks)
Less cost for same type of batteries and back up time
Better
short circuit capability in battery mode (bypass not available)
Transformer less UPS More battery blocks, connections
Transformer based UPS 2.7 X Nominal current Ph-Ph
etc
- 4 X Nominal current Ph-N / G
Transformer less UPS 2.2 X Nominal current
No neutral current back to the mains in case of unbalanced load in
Double conversion mode
Better management of unbalanced load.
A Zig-Zag transformer will share an unbalanced load on the three inverter
bridges
Transformer less UPS inverter legs may see unbalanced load ( different
leg operates at different load % - Components stress level are different)
improves battery lifetime through less ripple
Page 7
GE Critical Power
Better management of non linear load (low level harmonics
are
SG 10-40
kVAshortPresentation 2013
circuited)

2
Input performance

IGBT technology for clean input


Pure Pulse configuration for highest input performances

Constant behavior at all loads


Negligible harmonics contents at full
and
partial loads
Benefit on input mains
Saving in the sizing of upfront
equipment's
e.g. GenSet, cablings, circuit breakers,

No disturbances to nearby equipment


Saving cost due to additional filters

Total Input Harmonic Distortion


5%
4%

THDi

UPS input performances


Total Current Harmonic Distortion
THDi=2% @ 100% load and 5% @ 50%
load
UPS input power factor: 0.99

PurePulse technology for IGBT


rectifier

3%
2%
1%
0%
0%

20%

40%

60%

Load

80%

100%

Page 9
GE Critical Power
SG 10-40 kVA Presentation 2013

Input rectifier performances


Wide input window to preserve battery autonomy and lifetime
Input window

Soft start
Rectifier can be activated gradually,
controlling the input current
Preventing instable situation for
GenSet
Avoids false trip of upfront
protection devices
Sequential softstart for parallel UPS

+10%

Input
frequency

Wide input voltage and frequency


windows
Limited use of battery
Preserve battery autonomy for real
input mains failures
Increase battery lifetime

50 Hz
10%
-15%

400V

Input
voltage

+15%

Soft start
UPS input current
UPS 1
2

100%

UPS

0%
time

Page 10
GE Critical Power
SG 10-40 kVA Presentation 2013

Perfect integration with GenSet


No GenSet oversizing required
GenSet integration

Compatible with GenSet design


Saving GenSet size
(suggested GenSet vs. UPS ratio ~ 1.1)
Reducing GenSet installation space
Saving GenSet investment

GenSet system integration


GenSet integration via Customer
Interface (dedicated auxiliary contact)
Programmable functions based on
GenSet working condition (Gen on/off)

Page 11
GE Critical Power
SG 10-40 kVA Presentation 2013

3
Output performance

Highest UPS output power capability


Capability to supply Inductive, Resistive and Capacitive loads

Full range power capability


Designed to supply real power for
any type of application
- inductive loads
- resistive loads
- capacitive loads

I.e. SG-CE 20kVA load capabilities:


Inductive load PF=0.9 18 kW / 20 kVA
Resistive load PF=1

20 kW / 20 kVA

Capacitive load PF=0.9 18 kW / 20 kVA

No over-sizing required to supply


resistive and capacitive loads
Suitable for modern power supply
application with unit or capacitive
power factor (e.g. new servers
generation), crest factor up to 3:1

Page 13
GE Critical Power
SG 10-40 kVA Presentation 2013

No output voltage distortion


Best in class inoutput dynamic stiffness
No output voltage distortion with
linear and non-linear loads
Voltage distortion
- linear loads:
THDv <2%
- non-linear loads: THDv < 3%

Enhanced customer productivity


Improved quality of application,
reducing
stress for loads
supplied
Increased uptime and MTBF of
customer
Reduced service intervention

Output voltage with linear + nonlinear load


output voltage

curren
t

Output voltage with non-linear


load
output voltage

curren
t

Page 14
GE Critical Power
SG 10-40 kVA Presentation 2013

Output Dynamic Stiffness


Best in class inoutput dynamic stiffness

Best in class in output voltage


variation with load steps:
Static
:<+
1%
Dynamic at load steps 0-50-0% : < +
2%
Dynamic at load steps 0-100-0% : < +
3%

Enhanced customer unit productivity


Improved quality of application
(i.e. medical images)
Capability to supply critical loads with
high and fast loads steps (pulsating
loads)
Increased uptime and MTBF of customer
Reduced service intervention

Medical scanner - dynamic current


absorbtion
1
ms

Voltage variation at 0100% load


step

load step 0-100%


output voltage
Page 15
GE Critical Power
SG 10-40 kVA Presentation 2013

High Efficiency at all loads


Reduced customer operation costs and cost saving in air conditioning
design
High efficiency performances
High efficiency > 92% at full and
partial loads for real benefit in
operating conditions
Energy cost saving
Reduced cost of customer equipment
operation at all loads
Air conditioning cost saving
Reducing size and cost of air condition
system
Reducing consumption and related
operating cost
Higher backup time
Page 16
GE Critical Power
SG 10-40 kVA Presentation 2013

Superior Battery Management


Safe and protected battery management to preserve investment and UPS
reliability
Charging voltage = f (battery temperature)
2.36
2.33
Volt per cell

Flexible applications
Different battery technologies
applicable: PB sealed (VRLA) - PB
vented NiCd
Wide autonomy range: few minutes
... hours

2.30
2.27
2.24
2.21
2.18
0

User friendly information


Prediction of true back-up time,
based on load status
Alarm for stop operation to
prevent
any unknown shut-down
Monitoring and control
Battery test (programmable or
manual) ; preserve UPS system
reliability
Battery earth fault detection; safer
operation
for service engineer &
end user

10

15

20

25

30

35

40

Battery tem perature [C]

Voltage temperature compensation

Page 17
GE Critical Power
SG 10-40 kVA Presentation 2013

4
Improved serviceability
High Reliability

Improved diagnostic, High Reliability


SG Series Improved diagnostic, High
reliability
Front access (including battery)
Wave form capture capability
Fan failure detection
AC Capacitor health monitoring
Component life time counters
Dedicated supply path for bypass logic
Regulated power supply

Page 19
GE Critical Power
SG 10-40 kVA Presentation 2013

Improved diagnostic, High Reliability


SG Series Improved diagnostic, High
reliability
Robust RPA communication (Manchester
coded)
Simplified design through reduction of
PCBA & connections
Output filter capacitors PCBA mounted,
easy to replace
Input & battery circuit breaker instead of
contactor
Robust rectifier control with input mains
diagnostic

Page 20
GE Critical Power
SG 10-40 kVA Presentation 2013

New FLEX DSP board


Improved diagnostic capabilities

Extended modularity

Enhanced connectivity

Black box -> Waveform Capture


capability improved diagnostic
Higher computing capability ->
more ability to manage data

New digital communication


3X bandwidth
Faster connectivity -> up to
10x with connectivity devices
hardware upgrade

Waveform capture

Improved reliability

Dedicated supply for bypass logic


Dedicated supply for connectivity
channels
Redundant logic for emergency bypass
activation
Main-board integrated RPA control: RPA
board contains only interface hardware
More robust RPA communication
(Manchester coded)

Common platform
Page 21
GE Critical Power
SG 10-40 kVA Presentation 2013

New FLEX DSP board: the black-box Option

Waveform capture, diagnostic and trend analysis


Simultaneous acquisition of 32 channels
Sampling frequency up to 10kHz
Smart trigger capability with up to 16 indipendent trigger
sources to record only specific events with pre/post trigger
data acquisition
Buffer depth of 1000 samples per channel: each event is
recorded for 100ms @ s.f. 10kHz
8 buffers to record up to 8 events without losing older
events can be extended with external USB mass storage
devices

WAVEFORMS

Inverter voltages

Bypass voltages

Input mains voltages

Output voltages:

Output current Phases:

Input capacitors Cin voltages:

Inverter primary current:

Input current:

IDC current:

Battery current:

Bypass current:

UDC

Communication status RPA

Auxiliary status

SSM status

Fuses status

Phase error slave master.

Page 22
GE Critical Power
SG 10-40 kVA Presentation 2013

EMC - Immunity

Immunity
SG-CE products design exceed IEC 62040-2 C3 level
for immunity, i.e. can withstand possible disturbances
and noise without affecting standard working
conditions
IEC 62040-2 C2 SG Series 10kVA

Immunity

SG-CE
immunity level

IEC requirements

ESD

8kV (air)
4kV (contact)

8kV (air)
4kV (contact)

Surge

2kV line to line


4kV line to earth

1kV line to line


2kV line to earth

Burst

4kV @5kHz

2kV @5kHz

RF common mode (1kHz)

10V

10V

Page 23
GE Critical Power
SG 10-40 kVA Presentation 2013

Redundant Parallel Architecture


True redundancy with no single point of failure

Modular design
Future system expansion
Saving investment

Input mains
rectifier

bypass

rectifier

bypass

True redundancy
No single point of failure
Decentralized bypass
Distributed parallel management
system
Redundancy loss alarm
Increased system reliability
Safe and reliable power supply for
mission critical applications
Increase productivity
True redundancy with no single
point of failure

AC

AC
DC

battery

DC

battery

DC

DC
AC

AC

critical load

Page 24
GE Critical Power
SG 10-40 kVA Presentation 2013

Control panel
Easy and intuitive interface

Back lit Graphic Display (LCD)


Multilanguage communication
interface:
English, German, Italian, Spanish,
French, Finnish, Polish, Portuguese,
Czech, Slovakian, Chinese, Swedish,
Russian and Dutch
Synoptic diagram indicating UPS status
Command keys and parameters setting
UPS status control LED
LED - red
Stop
Operation
LED - yellow
Alarm

LED - green
Operation

Page 25
GE Critical Power
SG 10-40 kVA Presentation 2013

Customer interface
Easy integration with Building Management System (BMS)
UPS supervision capability
1x RS232 Serial Communication Port
6 programmable potential free alarm
contacts:
- D plug
- Terminals blocks
1x Emergency Power OFF contact
1x Gen-ON Input contact
1x Control Input contact

Additional interface:
SNMP Interface Card
(10/100Mbps auto-select)
MODBUS RTU Interface (RS232 or
RS485)
Page 26
GE Critical Power
SG 10-40 kVA Presentation 2013

Installation flexibility - Product options

Product Options
Empty Battery cabinets:
Rectifier, Bypass transformer
RPA card, SNMP card, Modbus RTU
iUPSGuard (Remote monitoring)
Black box capability
24V DC Power supply
EMC filter class A (40 kVA) the 40kVA is class C2 standard as
well (adding 4x ferrites)
Customer connection kit

Page 27
GE Critical Power
SG 10-40 kVA Presentation 2013

5
Product Comparison

Product Comparison

Site pro 10-40 kVA

SG Series 10-40 kVA

Rectifier topology Thyristor based

Rectifier topology IGBT

Input power factor 0.8

Input power factor 0.99

Input THDi 30%

Input THDi 2%

Efficiency Low at part load


Filter Capacitor overhang
mounting

Robust control
Efficiency Improved by 1-1.5%
Filter Capacitor PCBA mounting

Service access Side for battery

Service access Front/Top only

Customer interface Separate card

Customer interface embedded


card

Page 29
GE Critical Power
SG 10-40 kVA Presentation 2013

Product Comparison

Site pro 10-40 kVA


Power supply not regulated AC
power

SG Series 10-40 kVA


Power supply regulated AC/DC
power

Battery disconnect Optional

Battery disconnect Standard CB3

Cooling system One blower

Cooling system Fans

No Fan failure detection

Fan failure detection

No Cooling redundancy

Partial Cooling redundancy

Enhance diagnostic capability No

Enhance diagnostic capability

Galvanic isolation

Galvanic isolation

No Capacitor monitoring

Capacitor monitoring

Page 30
GE Critical Power
SG 10-40 kVA Presentation 2013

Product Comparison
Site pro 10-40 kVA

Cable connection

SG Series 10-40 kVA

Cable kit extension available to replace


Sitepro without changing cable connections.

Page 31
GE Critical Power
SG 10-40 kVA Presentation 2013

New SG Series.... high


performances UPS

- Increased reliability
- Better short circuit
cap

Output isolation
transformer

Saving in the sizing


-Input Breaker
-Input cables

High Efficiency > 92%

Output pf 1.0
(lead to lag)

- More Output power


Clean Input < 5%
THDi
Input pf 0.99
Wide input voltage
-Inbuilt back feed
protection
Saving in the sizing
- Genset

Output V THDv
<2%
- Reduce stress on load
- Stiff bus for pulsed loads
-Enhance battery life

Low Total Cost of


Ownership

Page 32
32
GE Critical Power
SG 10-40 kVA Presentation June 2013

SG 10-40 kVA - Applications

Process industries

Large railway
organizations

Control systems

Healthcare

33
2012 General Electric Company

Page 34
GE Critical Power
SG 10-40 kVA Presentation 2013

Competitive Comparison

Technology
Power range
Input PF
Input THDi
Output PF
Efficiency
IP degree of
protection
Input/output
Back-feed
Foot Print

Serviciability

GE
SG 10-40 kVA

Socomec
Masterysy

Riello
Master MPS

Riello
Multisentry

Liebert
NXC

Tx based
10-40
0.99
< 3%
1
92%

Tx based
10-40 (up to 80)
0.99
< 3%
0.9/0.8
?

Tx based
10-800
0.92
< 5-7%
0.9
92 ?

Tx less with internal


option
10-40 (upto 120)
0.99
<3%
0.9
up to 94% ?

Tx less with internal


option
10-40
0.99
< 4%
0.9
92.5% (with Tx)

20
3/3
Standard
680 x 800 x 1450 mm

31
3/3 & 3/1
Optional
600 x 800 x 1400 mm
1000 x 835 x 1400 mm
(40kVA)

20
3/3 & 3/1
Optional
555 x 740 x 1400
Internal Batt upto
20kVA

20 (31 option)
3/3 & 3/1 (20 kVA)
Optional
440 x 850 x 1320

20
3/3 & 3/1 (20 kVA)

500 x 860 x 1240


600 x 850 x 1600 (3040 kVA)

Front access

Front and back access

Front access

Internal battery upto 40


kVA
Internal Batt upto 30kVA
Front access
Front access

Page 35
GE Critical Power
SG 10-40 kVA Presentation 2013