Primary/Secondary System
Variable Speed
Secondary Pumps
Typical
load
with
two
way
valves
Constant Speed
Primary Pumps
Common Pipe
54.0 F
44.0 F
Secondary Pumps
1080 GPM @ 44.0 F
54.0 F
44.0 F
44.0 F
54.0 F
Typical
Coil
44.0 F
Primary Pumps
360 GPM Each
No flow
54.0 F
1080 GPM @ 54.0 F
Proprietary & Confidential
51.5 F
44.0 F
51.5 F
44.0 F
44.0 F
51.5 F
Typical
Coil
44.0 F
Primary Pumps
360 GPM Each
Primary/Secondary System
OFF
Secondary Pumps
720 GPM @ 44.0 F
54.0 F
44.0 F
44.0 F
54.0 F
Typical
Coil
44.0 F
Primary Pumps
360 GPM Each
No Flow
54.0 F
Primary/Secondary System
OFF
Secondary Pumps
792 GPM @ 44.0 F
54.0 F
44.0 F
44.0 F
54.0 F
Typical
Coil
44.0 F
Primary Pumps
360 GPM Each
72 GPM @ 53.0 F
53.0 F
Primary/Secondary System
OFF
Secondary Pumps
792 GPM @ 44.8 F
53.0 F
44.0 F
44.8 F
53.0 F
Typical
Coil
44.0 F
Primary Pumps
360 GPM Each
72 GPM @ 53.0 F
53.0 F
Primary/Secondary System
OFF
Secondary Pumps
900 GPM @ 44.8 F
51.9 F
44.0 F
44.8 F
51.9 F
Typical
Coil
44.0 F
Primary Pumps
360 GPM Each
Primary/Secondary System
Secondary Pumps
Primary Pumps
Automatic
Isolation Valve
54.0 F
44.0 F
54.0 F
44.0 F
Primary Pumps
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
54.0 F
44.0 F
Primary Pumps
270 GPM Each
Typical
load
with
two
way
valve
54.0 F
44.0 F
Bypass
Closed
Chiller off
Automatic
Isolation Valve
54.0 F
44.0 F
Primary Pumps
180 GPM Each
Typical
load
with
two
way
valve
54.0 F
44.0 F
Bypass
Closed
Chiller off
Automatic
Isolation Valve
Closed
Chiller off
Pumps
off
Closed
90 GPM @ 44.0 F
Primary Pumps
120 GPM (one
operating)
51.5 F
44.0 F
Bypass
Open
30 GPM @ 44.0
Flow meter
90 GPM @ 54.0 F
Proprietary & Confidential
Typical
load
with
two
way
valve
Chiller off
Automatic
Isolation Valve
Closed
Pumps
off
Closed
90 GPM @ 44.0 F
Primary Pumps
120 GPM (one
operating)
51.5 F
44.0 F
Bypass
Open
30 GPM @ 44.0
Flow meter
90 GPM @ 54.0 F
Proprietary & Confidential
Typical
load
with
two
way
valve
Automatic
Isolation Valve
Primary Pumps
Typical
load
with
two
way
valve
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
Primary Pumps
Typical
load
with
two
way
valve
54.0 F
45.0 F
Bypass
Closed
Automatic
Isolation Valve
55.0 F
Primary Pumps
198 GPM
55.0 F
55.0 F
35.0 F
Bypass
Closed
55.0 F
Primary Pumps
198 GPM
55.0 F
55.0 F
35.0 F
Bypass
Closed
Automatic
Isolation Valve
Open slowly
Chiller 2 comes on when flow
exceeds minimum
55.0 F
Primary Pumps
132 GPM
55.0 F
55.0 F
40.0 F
Bypass
Closed
Automatic
Isolation Valve
Primary Pumps
198 GPM
44.0 F
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
55.0 F
Primary Pumps
120 GPM
55.0 F
55.0 F
42.0 F
Bypass
Closed
Automatic
Isolation Valve
Primary Pumps
198 GPM
44.0 F
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
54.0 F
44.0 F
54.0 F
44.0 F
Primary Pumps
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
54.0 F
44.0 F
54.0 F
44.0 F
Primary Pumps
0 GPM @ 44.0 F
Typical
load
with
two
way
valves
54.0 F
44.0 F
Bypass
Open
Automatic
Isolation Valve
54.0 F
44.0 F
54.0 F
44.0 F
Primary Pumps
324 GPM Each
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
54.0 F
44.0 F
54.0 F
44.0 F
Primary Pumps
288 GPM Each
54.0 F
44.0 F
Bypass
Closed
Automatic
Isolation Valve
54.0 F
44.0 F
54.0 F
44.0 F
Primary Pumps
252 GPM Each
54.0 F
44.0 F
Bypass
Closed
Chiller is more efficient at 80% than at 40% for the given ambient temperature.
288 GPM
9 Ft. Head
288 GPM
144 GPM
each 2.5 Ft.
Head
Proprietary & Confidential
Chiller is more efficient at 40% than at 80% for the given ambient temperature.
The Setup
20 ton VPF cooling system
One chiller, one AHU
44F chilled water with 54F return
Chiller has two scroll compressors (0%, 50%, or 100% capacity)
The Problem
Load remains constant at around 55% or 60% for several hours
Chiller cant meet demand with one compressor on
Chiller severely over-cools with both compressors on
System is unstable
The Hint
Start by thinking about how increasing system water volume can add stability
Summary