REDUCING HIGH VIBRATION OF UNIT-1

COOLING TOWER C BY VIBRATION ANALYSIS


METHODE AND DYNAMIC ANALYSIS

Andisyah Purdanto
Condition Monitoring Analyst (Mechanical Rotating)
Star Energy Geothermal (Wayang Windu) Ltd

STAR ENERGY GEOTHERMAL (WW) LTD

Located 40 km south of Bandung


Unit-1 : 110 MW
Unit-2 : 117 MW

Cooling Tower Unit-1 :


- Counter Flow
- 8 cell

Strictly Confidential

U1 COOLING TOWER

Electric Motor

Drive shaft

Fan Hub

Fan (8)

Fan stack
Gearbox
Torque Tube

Wooden Structure

Strictly Confidential

Background
To Improve CT realiability & thermal performance, some equipment replaced :
Fan Hub (replaced)

Electric Motor
Drive shaft (replaced)
(replaced)

Fan (replace and add 2 fan)

Fan stack
Gearbox
(replaced)
Torque Tube

Wooden Structure

Strictly Confidential

Background

Gearbox
Dominant frequency : 9 Hz & 15.5 Hz

Motor Dominant frequency : 9 Hz

Equipment

Before
replacement

After
replacement

Gearbox

2.3 (mm/s pk)

8.19 (mm/s pk)

Motor

9 Hz & 16 Hz : suspected structure & torque tube resonance

M1V 3.06

8.21

M1H 3.01

2.56

M1A 3.25

5.35

M2V 3.03

5.46

M2H 2.88

1.23

M2A 5.27

7.09
Strictly Confidential

FRF (Frequency Response Function) Test

Strictly Confidential

FRF (Frequency Response Function) Test


Gearbox Horizontal

Motor Torque Tube Vertical

Gearbox Structure Horizontal

Motor Torque Tube Axial

Strictly Confidential

ODS

Strictly Confidential

ODS

9.5 HZ

15.5 HZ

Strictly Confidential

Dynamic Analysis of Torque Tube / Structure

Strictly Confidential

Dynamic Analysis of Torque Tube

Strictly Confidential

Dynamic analysis Torque Tube


1st Mode Shape = 12.14 Hz

2nd Mode Shape = 15.5 Hz

Torque Tube Model Validation

Strictly Confidential

Dynamic AnalysisTorque tube Constrain of Exitation Load


Torque Tube Model Validation

Strictly Confidential

Modification

#5

#1

#2

#4

#5

#3

Strictly Confidential

Comparison
Comparison of vibration after modification (micron pk-pk)

Comparison of percentage of reduction after modification (micron pk-pk)

Strictly Confidential

Comparison
#4

#5

9.5 Hz

9.5 Hz

#4

#5

16 Hz

16 Hz

Strictly Confidential

Dynamic Analysis of Structure

Strictly Confidential

Mode Shape

1st Mode shape 9.93 Hz

9th Mode shape 15.84 Hz

No

Mode

FRF (Fn) Hz

Model (Fn) Hz Error (%)

1st

9.5

9.98

<1

9th

16

15.75

1
Strictly Confidential

Dynamic analysis Structure constrain of exitation load


No

Load

Freq
(Hz)

Measured
micron pk-pk

Model
micron pk-pk

Error
(%)

Axial

9.5

69

69

Horizontal 16

88

88

Strictly Confidential

Purpose Modification
Modified Torque Tube

Strictly Confidential

Frequency Response to Single Load


Viibration after modification, micron pk-pk
No

Position

Before

After

Axial (9.5Hz)

69.11

8.51

87.69

Horizontal (16Hz)

88

12.59

85.69

Strictly Confidential

Frequency Response to Multiple Load

No

Position

Before

After

Axial (9.5Hz)

69.11

8.77

87.31

Horizontal (16Hz)

88

13.96

84.14

Strictly Confidential

Vibration After Running (Motor)


Pos. Of
Meas

Before

After (1)
14:00

After (2)
10:00

M1V

8.19

1.85

2.28

M1H

2.41

1.31

1.65

M1A

8.91

2.26

6.36

M2V

6.68

1.63

3.29

M2H

1.58

1.12

1.36

M2A

8.96

2.70

5.47

Strictly Confidential

Vibration After Running (Gearbox)


Pos. Of Meas Before

After (1) 14:00

After (2) 10:00

G1H

3.5

3.8

8.19

Strictly Confidential

Thank You...