Ventilation
Supply and
Exhaust
Reporter : Mark Anthony
Benter
MINIMUM
VENTILATION
RATE IN
BREATHING
ZONE
Table 4-1
1)
4-
Where:
Az=zone floor area. The net occupiable
floor area of the zone .
Pz=zone population. The largest no. of
people expected to occupy the zone during
typical usage.
Rp=outdoor airflow rate required per
person as determined from Table 4-1.
Outdoor air floor rate per unit area
Ra= outdoor airflow rate required per unit
area as determined from Table4-1
Vbz=RpPz+RaAz---(Equation 4-1)
Multi-zone System
403.4.2 System
Ventilation Efficiency.
The system ventilation efficiency (Ev)
shall be determined using Table 4-3.
Table 4-3 . System Ventilation Effiency
403.6Dynamic Reset
The system shall be permitted to be
designed to vary the design
outdoor air intake flow (Vot), or the
space or zone air flow as operating
conditions changes.
403.7 Exhaust
Ventilation.
Exhaust airflow shall be provided in
accordance with the requirements
in Table4-4. Exhaust make up air
shall be permitted to be any
combination of outdoor air, recirculated air, and transfer air.
Table4.4
Minimum
Exhaust
Rates
405.1 Location.
Evaporative cooling systems
shall be installed so as to
minimize the probability of
damage from an external
source.
405.3 Installation.
An evaporative cooler supported by the
building structure shall be installed on a
substantial level base and shall be secured directly
or indirectly to the building structures by suitable
means to prevent displacement of the cooler.
Modifications made to the supporting
framework of the buildings as a result of the
installation shall be in accordance with the
requirements of the National Building Code.
Openings in Exterior walls shall be flashed in an
approved manner in accordance with the
requirements of the building code.