Method
Design of Two way floor system for
Flat slab
Given data
Figure-1 shows a flat slab floor with a total area of 12,500 sq ft. It
is divided into 25 panels with a panel size of 25 ft x 20 ft.
Concrete strength is fc 3000 psi and steel yield strength is
fy=40,000 psi. Service live load is to be taken as 120 psf. Story
height is 10 ft. Exterior columns are 16 in. square and interior
columns are 18 in. round. Edge beams are14 24 in. Overall;
Thickness of slab is 7.5 in. outside of drop panel and 10.5 in.
through the drop panel. Sizes of column capital and drop panels
are shown in Fig.-1.
2
Fig.-1
3
4
[Problem-1]
Compute the total factored static moment in the long and short
directions of an interior panel in the flat slab design as shown in
Fig.1.
5
Neglecting the weight of the drop panel, the service dead load is
(150/12)(7.5)=94 psf; thus
wu=1.2wD +1.6wL
=1.2(94) +1.6(120)
=132 + 204
=336 psf
2 5
2 2
1 2 2c 1 2
Mo w uL 2L1 1 0.336 20 25 1 395 ft kips
8 3L1 8 3 25
(in long direction)
0.336 25 20 2 1 2 5
2 2
1 2c 1
Mo w uL 2L21 1 292 ft kips
8 3L1 8 3 20
(in short direction)
6
The equivalent square area for the column capital has its side
equal to 4.43 ft; then, using Eq.1, with Ln measured to the face
of capital (i.e., equivalent square),
1 1
w uL 2L2n 0.336 20 25 4.43 356 ft kips
2
Mo
8 8
(in long direction)
1 1
Mo w uL 2L n 0.336 25 20 4.43 255 ft kips
2 2
8 8
(in short direction)
So far as flat slabs with column capitals are concerned, it
appears that the larger values of 395 ft-kips and 292 ft-kips
should be used because Eq.8 is specially suitable; in particular,
ACI states that the total factored static moment shall not be less
than that given by Eq.1. 7
Given data [Problem-2]
Review the slab thickness and other nominal requirements for the
dimensions in this flat slab design described in problem-1.
8
(a) Stiffness of edge beams.
Before using Table-1, the values for the edge beams are
needed. The moment of inertia of the edge beam section
shown in Fig.2 is 22,9000 in4. Thus the value for the long
edge beam is
Fig.-2
9
Stiffness of edge beams.
10
bw h 3
Ib k
In which 12
t t
2 3
bE t t bE
1 1 4 6 4 1
bw h h h bw h
k
bE t
1 1
bw h
where
h = overall beam depth
t =overall slab thickness
bE =effective width of flange
bw = width of web
Ib 22,900 22,900
5.42
Is 120 7.5 3
4220
12
and for the short edge beam, it is
Ib 22,900 22,900
4.34
Is 150 7.5 3
5270
12
Ln Ln Ln Ln Ln Ln
75
28 31 31 31 34 34
L n 20.57(12)
min t 6.17 in.
40 40
The minimum thickness required is, from part (b), 6.17 in. The 7.5
in. slab thickness used is more than ample; 6.5 in. should
probably have been used.
15
(d) Thickness of drop panel.
In order that the full 3-in. projection of the drop below the 7.5 in.
slab is usable in computing reinforcement, the 6 ft 8 in. side of
the drop is revised to 7 ft so that one-fourth of the distance
between the edges of the 5-ft column capital and the 7-ft drop is
just equal to (10.5 - 7.5) = 3 in.
16
Given data [Problem-3]
17
18
Fig.-4
19
Fig.-5
Longitudinal moments in the Frame.
The longitudinal moments in frames A, B, C, D are computed
using Case 4 of Fig.23(DDM) for the exterior span and
Fig.19(DDM) for the interior span. The computations are shown
in Table-1 and the results are summarized in Fig.4&5. 20
(a) Check the five limitations (the sixth limitation does not apply
here) for the direct design method. These five limitations are
all satisfied.
FRAME A B C D
M0 395 198 292 146
Mneg at exterior support, 0.30M0 118 59 88 44
Mpos in exterior span, 0.50M0 198 99 146 73
Mneg at first interior support, 0.70M0 276 139 204 102
Mneg at typical interior support, 0.65M0 257 129 190 95
22
Given data [Problem-4]
For the flat slab design problem-1, compute the torsional constant
C for the edge beam and the interior beam in the short and
long directions.
23
For the short or long edge beam Fig.6(a), the torsional constant C is
computed on the basis of the cross-section shown in Fig.6(a).
Fig.-6
24
The torsional constant C equals,
x x3 y
C 1 0.63 (17 )
where y 3
x x3 y
C 1 0.63
y 3
0.63(7.5) (7.5)3 (51.5) 0.63(14) (14)3 (16.5)
C 1 1
51.5 3 16.5 3
6575 7025 13,600 in4
or
0.63(14) (14)3 (24) 0.63(7.5) (7.5)3 (37.5)
C 1 1
24 3 37.5 3
26
13,890 4610 18,500 in4 Use
Fig.-8
For the short or long interior beam [Fig.6(b)], a weighted slab
thickness of 8.5 in. is used, on the assumption that one-third
of the span has a 10.5 in. thickness and the remainder has a
7.5 in. thickness.
28
The percentages of the longitudinal moments going into the
column strip width are shown in lines 10 to 12 of Table-2. The
column strip width shown in line 2 is one-half of the shorter
panel dimension for both frames A and C, and one-fourth of this
value for frames B and D. The sum of the values on lines 2 and
3 should be equal to that on line 1, for each respective frame.
The moment of inertia of the slab equal in width to the
transverse span of the edge beam is:
240(7.5)3
IS in t for A and B 8440 in4
12
and
300(7.5)3
IS in t for C and D 10,600 in4 29
12
These values are shown in line 5 of Table-2.
30
Table-2 Transverse distribution of longitudinal moment for flat slab
LINE
NUMBER EQUIVALENT RIGID FRAME A B C D
1 Total transverse width (in.) 240 120 300 150
2 Column strip width (in.) 120 60 120 60
3 Half middle strip width (in.) 2@60 60 2@90 90
4 C(in4) from previous calculations 18,500 18,50 18,50 18,50
0 0 0
5 Is(in.4) in t 8,440 8,440 10,60 10,60
0 0
6 t= EcbC/(2EcsIs) 1.10 1.10 0.87 0.87
7 1 from previous calculations 0 5.42 0 4.34
8 L2/L1 0.80 0.80 1.25 1.25
9 1 L2/L1 0 4.33 0 5.43
10 Exterior negative moment, percent to 89.0% 91.6% 91.3% 88.7%
column strip
11 Positive moment, percent to column 60.0% 81.0% 60.0% 67.5%
strip
12 Interior negative moment, percent to 75.0% 81.0% 75.0% 67.5%
31
column strip
Table-2A:Percentage of longitudinal moment in column strip
33
(a) Moments in column and middle strips
The typical column strip is the column strip of equivalent rigid frame
C of Fig.5; but the typical middle strip is the sum of two half middle
strips, taken from each of the two adjacent equivalent rigid frames C.
The factored moments in the typical column and middle strips are
shown in Table-3.
34
Table-3: Factored moments in a typical column strip and
middle strip
35
(b) Slab thickness for flexure
For fc' 3000 psi and fy 40,000 psi, the maximum percentage
for tension reinforcem ent only is 0.75b 0.0278.
The actual percentage used (lines 6 of Table - 4 and 5)
are nowhere near this maximum. Thus there is ample compressiv e
strength in the slab. This phenomenon is usual because of the
deflection control exerted by the minimum slab thickness requiremen ts.
1
Rn f y (1 m)
2
fy
m
0.85 f c
36
Table-4: Design of reinforcement in column strip
EXTERIOR SPAN
INTERIOR SPAN
1 Moment, Table-2, line 3 (ft- -80 +88 -153 -142 +58 -142
kips)
2 Width b of drop or strip (in.) 100 120 100 100 120 100
3 Effective depth d (in.) 8.81 6.44 8.81 8.81 6.44 8.81
4 Mu/ (ft-kips) -89 +98 -170 -158 +64 -158
5 Rn(psi)= Mu/(bd2) 138 236 263 244 154 244
6 , Eq. or Table A.5a 0.35% 0.62% 0.70% 0.64% 0.39% 0.64%
7 As = bd 3.08 4.79 6.17 5.63 3.01 5.63
8 As =0.002bt* 2.40 1.80 2.40 2.40 1.80 2.40
9 N=larger of (7) or(8)/0.31 9.9 15.5 19.9 18.2 9.7 18.2
10 N=width of strip/(2t) 5 8 5 5 8 5
11 N required, larger of (9) or 10 16 20 19 10 19
(10)
37
*bt=100(10.5)+20(7.5)=1200 in for negative moment region.
2
Table-5: Design of reinforcement in Middle Strip
40
Given data [Problem-7]
41
Wide beam action. Investigation for wide beam action is made
for sections 1-1 and 2-2 in the long direction, as shown in
fig.10. The shot short direction has a wider critical section and
short span; thus it does not control. For section 1-1, if the entire
width of 20 ft is conservatively assumed to have an effective
depth of 6.12 in. Fig.-10
42
Vu 0.336 20 9.52 64 kips (sec tion 1 1)
1
Vn Vc 2 fc 240 6.12 161 kips
1000
Vn 0.85161 137 kips Vu OK
It will be rare that wide beam (one way) action will govern.
(b)Two way action. The critical sections for two way action are the
circular section 1-1 at d/2 = 4.56 in. from the edge of the
column capital and rectangular section 2-2 at d/2 =3.06 in. from
the edge of drop, as shown in fig.11. Since there are not
shearing forces at the centerlines of the four adjacent panels,
the shear forces around the critical sections 1-1 and 2-2 in
fig.11 are 44
Fig.-11
5.76 2 5.76 2
Vu 0.336 500 1.2 0.038 7 8.33
4 4
159.2 1.7 161 kips (sec tion 1 1)
45
In the second term, the 0.038 is the weight of the 3in. drop in ksf.
Vu 0.336 500 8.84 7.51 146 Kips (sec tion2 2)
than Vu, the section around the drop panel is loaded to slightly
higher percentage of its strength (50% for section 2-2 vs 47%
for section 1-1). Shear reinforcement is not required at this
interior location.
47