Lecture No.3 Lecture Contents Fault and Symmetrical Components System Earthing Types of Earthing according to application Special Topic (Portable Earthing) Symmetrical Components The method of symmetrical components is used to simplify fault analysis by converting a three-phase unbalanced system into two sets of balanced phasors and a set of single-phase phasors, or symmetrical components These sets of phasors are called the positive-, negative-, and zero-sequence components These components allow for the simple analysis of power systems under faulted or other unbalanced conditions Once the system is solved in the symmetrical component domain, the results can be transformed back to the phase domain. Converting Between the Phase and Symmetrical Component Domains where I0, I1, and I2 are the zero-, positive-, and negative sequence components, respectively This equation shows the symmetrical component transformation in terms of currents, but the same equations are valid for voltages as well Transformers are simply represented as their positive- and negative- sequence impedances in the positive- and negative sequence networks, respectively However, the transformer representation in the zero-sequence network can be more complex and is dependent on the type of transformer connection Once the sequence networks for the system are defined, the way they are connected is dependent on the type of fault Sequence network connections for common shunt fault types For a three-phase fault, the positive- sequence network is used with the fault point connected back to the neutral bus, as shown in Fig. For a single-phase-to-ground fault, the three networks are connected in series Any fault impedance is multiplied by 3 and included in this connection For a phase-to-phase fault, the positive- and negative sequence networks are connected in parallel, as shown Circuit for Unbalanced Sources Network Reduction fault at Bus G Circuit reduction and current distribution Grounding for system protection It is well known fact that the phase-to-ground faults in a system can limit the ground fault current depending on adding external impedance between neutral and the earth This Lecture briefly covers the various methods of grounding that are adopted in the electrical systems In the following clauses, the star-connected transformer is shown which are widely used in power distribution The grounding methods are also applicable in case of generators, whose windings are also invariably star connected The following table highlights the possible problems that can occur in a system due to the common faults and the solutions that can be achieved by adopting system grounding; Assignment No.1 In this example, the objective is to determine maximum current through the breaker B due to a fault at the location shown in Figure All three types of unbalanced fault, as well as the balanced fault are to be considered This is the sort of calculation that has to be done whenever a line is installed or modified, so that Assignment No.1 Problems in System Problems (1) Phase faults: High fault currents Only limited by inherent impedance of power supply. (2) Earth faults: Solid Earthing means high earth fault currents Only limited by inherent zero sequence impedance of power system. Consequences: 1. Heavy currents damage equipment extensively danger of fire hazard. 2. This leads to long outage times lost production, lost revenue. 3. Heavy currents in earth bonding gives rise to high touch potentials dangerous to human life. 4. Large fault currents are more hazardous in igniting gases explosion hazard. Solutions Solutions Phase segregation: Eliminates phase-to-phase faults Resistance Earthing: Means low earth fault currents can be engineered to limit to any chosen value. Benefits 1. Fault damage now minimal reduces fire hazard. 2. Lower outage times less lost production, less lost revenue. 3. Touch potentials kept within safe limits protects human life. 4. Low fault currents reduce possibility of igniting gases minimizes explosion hazard. 5. No magnetic or thermal stresses imposed on plant during fault. 6. Transient overvoltages limited prevents stressing of Earthing Devices Solid Earthing: In this case, the neutral of a power transformer is earthed solidly with a copper conductor as shown in Figure; Solid Earthing Advantages Neutral held effectively at earth potential. Phase-to-ground faults of same magnitude as phase-to-phase faults; so no need for special sensitive relays Cost of current limiting device is eliminated. Grading insulation towards neutral point N reduces size and cost of transformers Disadvantages As most system faults are phase-to- ground, severe shocks are more considerable than with resistance earthing Third harmonics tend to circulate between neutrals Resistance Earthing A resistor is connected between the transformer neutral and earth, see Figure in subsequent slide; Mainly used below 33 kV. Value is such as to limit an earth fault current to between 1 and 2 times full load rating of the transformer Alternatively, to twice the normal rating of the largest feeder, whichever is greater Resistive Earthing Advantages Limits electrical and mechanical stress on system when an earth fault occurs, but at the same time, current is sufficient to operate normal protection equipment Disadvantages Full line-to-line insulation required between phase and earth Reactance Earthing A reactor is connected between the transformer neutral and earth (see Figure ) Values of reactance are approximately the same as used for resistance earthing. To achieve the same value as the resistor, the design of the reactor is smaller and thus cheaper Arc Suppression (Petersen coil) A tunable reactor is connected in the transformer neutral to earth (see Figure ) Value of reactance is chosen such that reactance current neutralizes capacitance current The current at the fault point is therefore theoretically nil and unable to maintain the arc, hence its name. Virtually fully insulated system, hence current available to operate protective equipment is so small as to be negligible To offset this, the faulty section can be left in service indefinitely without damage to the system as most faults are earth faults of a transient nature, the initial arc at the fault point is extinguished and does not restrike Sensitive watt-metrical relays are used to detect permanent earth faults An earthing reactor connected between the neutral of a system and earth and having a specially selected, relatively high value of reactance in such that the reactive current to earth under fault conditions balances the capacitance current to earth flowing from lines so that the earth current at the fault is limited to practically zero If the ground fault is in air, such as an insulator flash- over, it may be self extinguishing This method of grounding is used primarily on 110 kV systems, consisting largely of overhead transmission or distribution lines Since systems of such construction are rarely used in industrial or commercial power systems. Earthing via Reactance The neutral is connected to earth through reactor The ground fault that may flow is a function of the neutral reactance, the level of the fault current is often used as a criteria for describing the degree of grounding In this method the ground fault current should be at least 60% of the three phase fault current to prevent serious transient over voltages This is considerably higher than the level of fault current desirable in the system using resistor, and therefore reactance grounding is usually not considered as an alternative to the system using resistor This system is used when the system neutral transformer is not available ( DELTA connected system ) in such case the reactor is used as transformer grounding to obtain the neutral Comparison between solid and resistive earthing Subject Effective/solid Resistive Earthing Earthing (a) Rated voltage of system Need not exceed 0.8Um Must be at least 1.0Um for components, particularly 100 s power cables and metal oxide surge arresters (b) Earth fault current Approximately equal to Reduced earth fault current magnitude three-phase fault current magnitude (typically (typically 210 kA) 300900 A) (c) Degree of damage, High degree of damage at Lesser degree of damage at because of an earth fault fault point and possible fault point and usually no damage to feeder damage to feeder equipment equipment (d) Step and touch High step and touch Reduced step and touch potentials during earth fault potentials potentials (e) Inductive interference on High probability Lower probability and possible damage, to control and other lower- voltage circuits (f) Relaying of fault Satisfactory Satisfactory conditions Lower initial cost but higher High initial cost but low (g) Cost long-term equipment repair long-term equipment repair cost cost Given figure gives the touch potential with solid earthing Next Figure shows the touch potentials with resistance R introduced in the neutral Here the ground fault current is limited by the resistance R, so only reduced current flows to the earth However, it is a normal practice to adopt solid earthing method at low voltages (up to say 600 V) and resistance grounding is adopted for higher voltages (upto 33 kV) The other methods of earthing (reactor, transformer, etc) are generally adopted in the cases of voltages beyond 33 kv Cost invariably determines the earthing method The main reason for adopting solid earthing is because, the resistance earthing cannot be used for single-phase loads, whereas most of the LV distribution mainly households, etc. comprise of single-phase loads Nevertheless, resistance grounding is considered at low voltages in industrial environments, where three-phase loads are connected and the process conditions do not accept frequent shutdowns due to ground faults Though it is true that the power interruptions can be kept low with the use of resistive earthing method, human protection demands that the power to be isolated in case of ground faults That is one more reason for using solid earthing in utility distribution transformers Effect of Electric Shock There are four major factors, which determine the seriousness of an electric shock: 1. Path taken by the electric current through the body 2. Amount of current 3. Time the current is flowing 4. The bodys electrical resistance The most dangerous and most common path is through the heart (see Figure ) Persons are not normally electrocuted between phases or phase-to-neutral, almost all accidents are phase-to-earth Sensitive Earth protection Earthing does not ensure that humans will be protected when coming in contact with a live conductor Though there may be relays, which are set to sense the earth leakages, invariably their settings are high Hence earth leakage circuit breakers (ELCB) or residual current circuit breakers (RCCB) are adopted where possibility of human interaction to a live conductor is high These breakers work on the core balance current principle Figure in next slide illustrates the operation of the core balance leakage device When the system conditions are normal, the phase current and neutral current will be equal and in phase Hence the CT will not detect any current under normal conditions since IL + IN = 0 (vector sum). The ELCB comprising of core balance CT is mounted at the source end When a human comes in contact on any part of the line, a part of the current will start flowing through the body It will result in unbalance of the currents entering and returning to the CBCT of the ELCB If the fault current IF, flows through the human body, IN is reduced by this amount. Relay is operated by this unbalance quantity, and immediately trips the ELCB It is normal that the ELCBs are moulded breakers similar to the miniature circuit breakers including, CBCT mounted inside It is also common that the CBCT can be mounted outside and the unbalanced current can be taken to trip a separate relay namely earth leakage relay. The above example considered a single-phase system However, the principle is the same for three-phase systems with neutral, where also the vector sum of the three-phase currents (IR + IY + IB) and the returning neutral current IN will be zero All the phase and neutral conductors are taken in through the CBCT so that the CBCT does not sense any current under normal conditions In the event of any leakage in any phase, the CBCT immediately detects unbalance and causes the breaker to trip The ELCBs are available with sensitivity of 30 mA, 100 mA and 300 mA For human protection, 30 mA ELCBs is recommended, since currents flowing above 30 mA in a human can cause serious damage including death
The Exciting Impedance Ze of The Auxiliary Transformer T and The Capacitance of The Potential Divider Together Form A Resonant Circuit That Will Usually Oscillate at A Certain Frequency