ANSIvs.IEC
ElectricalStandards
ByJimCampe
Introduction
StandardDifferences
Basicdifferencesinthreeareas
Philosophy
Construction
PerformanceTesting
TypesofEquipment
MediumVoltageSwitchgear
LowVoltageSwitchgear
LowVoltageMotorControlCenter
StandardsReviewed
InAdditionIEC439has4FormsofSeparation
Thestandarddefinesseparationbetweenfunctionalunitsinto
4Forms
eachFormhasdifferentsubformsorTypesdependingonthe
levelof
separationrequired.Totalof14FormsandTypesare
defined.
EnclosureTypes
InAdditionIEC439has4FormsofSeparation
TheFormsaredefinedas:
Form1NoSeparation.
Form2Separationofbusbarsfromfunctionalunits.
Form2a,Form2Type1&Form2Type2definitions
exist.
Form3Separationofbusbarsforthefunctionalunitsand
separationofallfunctionalunits,butnottheirterminals
forexternalconductors,fromoneanother.Theterminals
forexternalconductorsneednotbeseparatedfromthe
busbars.
Form3a,Form3bType1&Form3Type2definitions
exist.
Form4Separationofbusbarsfromthefunctionalunits
andseparationofallfunctionalunitsfromoneanother,
includingtheterminalsforexternalconductorswhichare
anintegralpartofthefunctionalunit.
SEPARATION
According to the Standard, Separation can be claimed if one
of the following is met:
Defined by BS EN 60439-1
Form 2 Type 2
As Form 2, but busbar separation is achieved by rigid
metallic or non-metallic barriers or partitions.
Terminals are separated from the busbars, but not from
functional units or each other.
Defined by BS EN 60439-1
Form 3
Busbars are separated from functional units.
Functional units are separated from each other, and terminals.
This basic definition is refined by the UK National Annex to EN60439,
BSEN60 439-1 (Form 3a and Form 3b Type 1 and Form 3b Type 2 are
defined)
Form 3a
As Form 3.
The actual means of separation is not defined in the
Standard.
Terminals are not separated from busbars or each other.
Defined by BS EN 60439-1
Form 3b Type 1
As Form 3, busbar separation is achieved by insulated coverings,
(PVC sleeving, wrapping or coating).
Terminals are separated from busbars, but not from each other.
Defined by BS EN 60439-1
Form 3b Type 2
As Form 3, but busbar separation is achieved by metallic or
non-metallic rigid barriers or partitions.
Terminals are separated from the busbars, but not from each
other.
Defined by BS EN 60439-1
Form 4
Busbars are separated from functional units.
Functional units are separated from terminals and each
other.
This basic definition is refined by the UK National Annex to
EN60439, BSEN60 439-1 (Form 4 Types 1, 2, 3, 4, 5, 6, and 7
are defined)
Form 4 Type 1
As Form 4, busbar separation is achieved by insulated coverings,
(PVC sleeving, wrapping or coating).
Cables terminated in same compartment as functional unit, but
may be glanded elsewhere. e.g. in a common cabling chamber.
Defined by BS EN 60439-1
Form 4 Type 2
As Form 4, but busbar separation is achieved by metallic or non-
metallic rigid barriers or partitions.
Cables terminated in same compartment as functional unit, but
may be glanded elsewhere. e.g. in a common cabling chamber.
Defined by BS EN 60439-1
Form 4 Type 3
As Form 4, but busbar separation is achieved by metallic or
non-metallic rigid barriers or partitions.
Cables terminated in same compartment as functional unit,and
has its own integral glanding facility.
Defined by BS EN 60439-1
Form 4 Type 4
As Form 4, but busbar separation is achieved by insulated
coverings, (PVC sleeving, wrapping or coating).
Cables terminated outside functional unit, and separated by
insulated coverings. May be glanded elsewhere.
Defined by BS EN 60439-1
Form 4 Type 5
As Form 4, but busbar separation is achieved by metallic or
non-metallic rigid barriers or partitions.
Cables terminated outside functional unit, and separated by
insulated coverings. May be glanded elsewhere.
Defined by BS EN 60439-1
Form 4 Type 6
As Form 4, but all separation is achieved by metallic or non
metallic rigid barriers or partitions.
Cables terminated outside functional unit, and separated by rigid
barriers or partitions. May be glanded elsewhere.
Defined by BS EN 60439-1
Form 4 Type 7
As Form 4, but all separation is achieved by metallic non-metallic
rigid barriers or partitions.
Cables terminated outside functional unit, and separated by rigid
barriers or partitions with integral glanding facility.
Defined by BS EN 60439-1
EnclosureTypesANSI
ApplicationSpecific
NEMA Type Nearest IEC Equivalent
NEMA 1-General Purpose. Protection of people IP2X*-Protected against solid objects greater than
from live parts. Protection against falling dirt. 12mm.
Test: 1/8" to 1/2" (3.175-12.7mm) rod entry test Test: Metallic test finger and 12mm sphere tests.
and rust resistance test.
No IEC rust resistance test.
NEMA 3-Dusttight, Raintight, and Sleet Resistant. IP54-Dust protected. Protected against splashing
water.
Test: Rain, dust, external, icing & rust resistance Test: Dust and oscillating sprinkler test.
tests.
No IEC rust resistance or icing test.
NEMA 3R-Rainproof and Steet Resistant. IP34- Protected against solid objects greater than
2.5mm. Protected against splashing water.
Test: Rod entry 1/8-1/4 (3.175-6.35mm), rain, Test: 2.5mm rod and oscillating sprinkler tests.
external icing, and rust resistance tests.
No IEC rust resistance or icing test.
NEMA 4-Watertight and Dusttight. IP65-Dusttight. Protected against water jets.
Test: Hosedown, rust resistance and external Test: Dust and spray nozzle test.
icing tests.
No rust resistance or external icing test.
EnclosureTypesANSI
ApplicationSpecific(continue)
NEMA 12- Dusttight and Driptight. IP61- Dusttight and Protected against dripping water.
Test: Drip, dust, and rust resistance tests. Test: Dust and rain simulator tests.
No IEC rust resistance test.
NEMA 13- Oiltight and Dusttight. IP6X- Dusttight.
Test: Oiltightness and rust resistance tests. Test: Dust test.
No IEC oiltightness or rust resistance tests.
EnclosureTypesIEC
IndicatedbyIPXX
(firstcharacter,contactwithliveparts)
"X" - indicates that the NEMA type enclosure is judged to comply with the requirements for the corresponding characteristic
numerals of IEC 529.
"O" - indicates that the NEMA type enclosure is judged not to satisfy the requirements corresponding to the characteristic
numerals of IEC 529. For example, Type 3 is judged to satisfy the requirements of IP11 to IP65 and Type 3R of IP11 to IP24.
MotorControl
NEMAMotorStartersaredesignedfor
easeofselectionoverawiderangeof
applications.
IECMotorControlisdesignedaround
performancestandardsandisapplication
anddutyspecific.
MotorControl
NEMAdeviceshaveahighlevelof
performanceforawiderangeof
applications.Typicallyproductshavea
largerreservecapacitythatisnot
requiredinmostsituations.
IECcontrollersareselectedbasedonthe
ratingsandperformanceexpectationsfor
differentapplicationsandduties.
MotorControl
ANSIvs.IEC
Differencesworthconsideration
NEMA IEC
Starter - combination of contactor and Contactor and overload protection are
overload on a sub-assembly. separate, overload typically direct
connects to contactor.
Large metal back plates with Smaller - DIN rail mounting, overload is a
interchangeable contacts, coils and fixed heater type. Class 10 overload
overload heater packs. protection.
ANSIstandardsaredesignand
constructionspecific
Metalcladormetalencloseddesigns
11gaugesteelforcircuitbreaker
compartments
Individualcircuitbreakercompartments
Specificwirelugandterminalrequirements
metalbarriersforallbussectionalizers
barriersmustbe14gaugesteelminimum
Controltransformersmustbefused
LowVoltageSwitchgear
ULstandardsaremorespecific
Mainbussizingtablesmustbefollowed
Bussplicinghardwareisspecified
Allinteriorcomp.mustbeULapproved
AllwiringmustbeSIStype
Serviceentrancebarriersaredetailed
Bussupportsanddistancesaredetailed
Ventilationopeningsaredefined
Cableterminationrequirementsareprovided
LowVoltageSwitchgear
IECstandardsaremore
performanceandtestingoriented
Listsdetailedandspecificperformanceteststhatall
electricalequipmentmustbesubjectedtoasTypeTests
andasRoutineTests.8TypeTestrequirementsforeach
typeandrating.
DefinesTotallyTypeTestedandPartiallyTypeTested
Assemblies.
Allowsforselftestingbutencouragesthirdpartytype
testingratherthatendorsinganapprovalagency.
Constructionorarrangementrequirementssubjectto
agreementbetweenmanufacturerandspecifierbut
definesFormsofSeparationrequirements.
LowVoltageSwitchgear
IECstandardsaremore
performanceandtestingoriented
BecausethestandardisthesameforMotorControl
CentresandforDistributionSwitchgearand
Switchboards,theytendtolookalike.IEC439doesnot
differentiatebetweenSwitchgearandSwitchboardor
MCC.
LowVoltageSwitchgear
Definition:
Panelboards
Custom Control
Distribution
Switchgear
Wall Mounted
Motor Control Custom Control Custom Control
Centres
StandardsReviewed
IEC 439-1: Low-voltage Switchgear and
Controlgear Assemblies.
ANSI IEC
Short circuit rating of the switchboard is Individual devices have short circuit
equal to the lowest device rating in the ratings no specific requirements for
switchboard. overall rating. Manufacturer determines
rating of the assembly and tests
accordingly.
Allows for series ratings for protection of No series ratings tests specified. Devices
lesser rated devices downstream by specific must be rated for the full prospective
testing of each type device. rating.
Devices are rated for interrupting Electrical assemblies have a rated short
symmetrical faults only. time withstand current rating in
symmetrical amperes and a peak
Devices based on size are tested on a fixed withstand current rating in asymmetrical
average asymmetrical value. amperes with a full degree of asymmetry.
Typically 1 or 3 second rated withstand
I.e. power breakers X/R=6.5912
with a 2.1 times peak, e.g. 50 kA for 1
Molded case > 20 KA, X/R=4.899
second has a 105kA peak rating.
Molded case > 10 KA, X/R=3.1798
Molded case < 10 KA, X/R=1.7321
For a device to interrupt a fault with a higher No derating factors required. Device must
X/R ratio then a complex natural logarithmic be asymmetrically rated.
must be applied to derate the breaker
interrupting rating.
LowVoltageSwitchgear
IECvsANSI
TemperatureRiseRequirements
ANSI IEC
Main switchboard bus is limited to Main switchboard bus is limited to
a 65 deg. C rise over a 40 deg. C a 70 deg. C rise over a 40 deg. C
ambient. ambient. See seperate comment.
Circuit breakers are only allowed a Circuit breakers are only allowed a
60 deg. C rise over a 40 deg. C 80 deg. C rise over a 40 deg. C
ambient ambient measured at the terminals.
Terminals for 80% rated devices Terminals for external connection
are limited to 50 deg. C rise and limited to 70 deg. C rise.
wire is rated at 75 deg. C.
Terminals for 100% rated devices No tests required at 100% of
are limited to 60 deg. C rise and equipment rating.
wire is rated at 75 deg. C.
LowVoltageSwitchgear
IECvsANSI
TemperatureRiseRequirements
IEC439 does not have an overall temperature rise limit for the
assembly as a whole: Test ambient is 35 Degrees C.
Built in Components: Limited only by their own component standard
taking into account the fact that they are in an enclosure.
Terminals for External insulated conductors: 70 Deg. C
Busbars and Conductors: No limit. Only limited by the mechanical
strength of the conducting material, the possible heating effects on
adjacent equipment, permissible temperature of the support and
insulating material.
Manual operators: 15 Deg. C for metallic parts, 25 Deg. C for
insulated parts.
Accessible external covers: 30 Deg. C for metallic covers, 40 Deg. C
for insulated covers.
Temperature rise and therefore temperature limits are set for external
interfaces, cable terminals, covers and handles only. Differentiation is
also made for the type of material used.
LowVoltageSwitchgear
IECvsANSI
ShortCircuitTests
ANSI IEC
Tests are performed at maximum Tests are performed at 110% of
rated voltage - 105.8% of nominal. operating voltage of the specific
assembly.
Test duty is fixed at 0.5 sec on, 15 Test duty for short time test is 1 sec
sec off, 0.5 sec on. The system X/R mi. Test duty for peak test is 0.1
must be 6.6 or greater. sec.
Test frequency must be within 20% Test frequency must be within 25%
of rated frequency. of rated frequency.
Test peak current must be 2.3 The test peak value is the
times the symmetrical rating and asymmetrical rating for the
verified by oscillogram. equipment and verified by
oscillogram.
Permanent deformation of busbars Only slight deformation of bus
is allowed as long as dielectric and systems is allowed.
performance tests are not
compromised.
LowVoltageSwitchgear
IECvsANSI
ItemsSubjecttoAgreementbetweenManufacturer
As IEC 439 is a very general andUser
specification covering all manner of
assemblies, it does not, of itself, specify precisely the construction or
rating of the equipment. Therefore the User/Specifier MUST add
desired criteria to a project specification. These include but not limited
to:
Construction material and thickness (e.g. steel, plastic, stainless etc.)
Supply voltage, number of phases and frequency,
Current capacity of busbars including the Neutral (if busbars are fitted)
System fault rating and duration. (e.g. 50kA for 3 seconds)
Rated diversity factor (e.g. 1, 0.7, 0.8 etc)
Special service conditions (e.g. altitude if above 1000 m, ambient temp if
above 35 Degrees C., Relative Humidity)
Internal and External degree of protection (e.g. IP 54 external and IP 40
internal, degree of protection when withdrawable units removed)
Form of construction (e.g. Form 1,2,3,4 including types)
LowVoltageSwitchgear
IECvsANSI
ItemsSubjecttoAgreementbetweenManufacturer
andUser
Accessibility for maintenance (e.g. Front only, Front/Rear)
Accessibility for cabling (e.g. Top or bottom, Front or Rear cable entry)
Conditions during erection, storage and transport
Coordination of protective devices.
Temperature rise requirements for equipment ratings above 3150 amps.
Site test requirements.
Ask for copy of the full set of Type Test Certificates covering all 8 Type Tests
required by the standard.
Ask for a Declaration of Conformity to the Low Voltage Directive when the
equipment is delivered.
LowVoltageSwitchgear
IECvsANSI
TheEIGHTTypeTestsRequiredbyIEC439
The standard lays down a comprehensive package of performance
requirements. These come under 8 headings and ALL must be verified
by type test irrespective of whether an assembly is to offered as a TTA
or as a PTTA. These are typically one time tests done at the time of
design, the standard does not require follow-up testing unless there is a
substantial design change, neither does the standard require third party
certification.
1 Dielectric Properties - Clause 8.2.2
2 IP degree of protection - Clause 8.2.7
3 Temperature Rise limits - Clause 8.2.1
4 Mechanical Operations Tests - Clause 8.2.6
5 Clearance and Creepage distances - Clause 8.2.5
6 Effectiveness of the protective circuit - Clause 8.2.4
7 Short Circuit Withstand strenght of the protective circuit (earth bar) Clause
8.2.4.2
8 Short Circuit Withstand strength of the main circuits (busbars, neutral) Clause
8.2.3
LowVoltageSwitchgear
IECvsANSI
RoutineTestsRequiredbyIEC439
Routine Tests are required to be performed on EVERY assembly, they are
carried out at the place of manufacture, the standard does not require
additional testing at the place of installation. Individual component
testing may be required as part of the assembly, however if the
component manufacturer routine tests components they do not need
further testing in the assembly.
The test procedures are left to the manufacturer and records of the
test results usually form part of the CE Technical File under the
Declaration of conformance.
MediumVoltageSwitchgear
IECvsANSI
ANSIstandardsaremore
constructionandapplication
oriented
IECstandardsaremore
performanceandtestingoriented
Ratedmaximumvoltage
Ratedinsulationlevels
Ratedcontinuouscurrent
Ratedshortcircuitcurrent
Compartmentalization
MediumVoltageSwitchgearIECvsANSI
EnclosureConstruction
Construction ANSI IEC
Sheet steel minimum thickness
Metallic material required no
Enclosure Material 0.30 cm for all barriers 0.19 cm
minimum thickness specified.
for doors and covers.
Phosphalizing or equivalent
Finish before painting. One coat min. of None specified.
corrosion resistant paint.
Meet dielectric test per ANSI and
Not required but can be provided
withstand maximum rated voltage
Bus Insulation by agreement between supplier
for 1 min. between phase and
and user.
outside surface.
ShortCircuitRatings
Item ANSI IEC
Uses asymmetrical factor S where Uses a expon. curve e to the -t/0.043
% DC Component S=I rms/I sc rms Approx. equals a decay factor Approx. equals an X/R
or X/R Ratio 50% DC component or an X/R of at 50 Hz of 13.6 and an X/R of 15.8
16.5. for 60 Hz tests.
Short Circuit Considered as 2.7 *K* the short Considered as 2.5* the short circuit
Making Current circuit interrupting rating. interrupting rating.
Max. Close and Latch Must withstand 2.7*K*I for 2 sec. 2 sec. withstand not required.
Single Phase Symmetric Interuption Four required at 1.15 *I One required at 1.0*I
12 8.0
12.5 630 1250
16.0 630 1250 1600
20.0 630 1250 1600
25 630 1250 1600 2000 2500
31.5 1250 1600 2000 2500 3150
40.0 1250 1600 2000 2500 3150
50.0 1250 1600 2000 2500 3150
Transient Recovery
1.88* Max. voltage rating. 1.72* Max. voltage rating.
Voltage Crest Value
Transient Recovery
Not specified. Limit is required.
Voltage Rise Time
Maximumtemperaturelimitfor Maximumtemperaturelimitfor
anysurfacessubjecttotouchis50 anysurfacessubjecttotouchis70
degreesC.
degreesC.
Temperaturerisetestdefinedas
Temperaturerisetestdefinedas
singlestructureordevicewith multiplestructuresordevices(if
ambienttemperaturedetermined intendedforuseassuch)mustbe
byapprovedsensorsinairone testedwithadjacentenergized
footawayfromstructurebeing cubicleswithambienttemperature
tested. determinedbyapprovedsensorsin
oilonemeterawayfromassembly
beingtested.
Summary
ANSIstandardsaremoreconstruction
andapplicationoriented.
IECstandardsaremoreperformance
andtestingoriented.
Tryingtodecidewhichstandardtouseis
notaseasyasitmayseem.
Specifyingequipmentthatwillconform
toacombinationofthestandardsiseven
moredifficult,ifnotimpossible.
Summary
Thestandardsaredifferent.Tryingto
proveoneisbetterthantheotherisan
exerciseinfutility.Bothcanbeproven
betterthantheother,itjustdependson
whichsideoftheargumentyouwantto
prove.
ItslikecomparingApplestoPears,they
arebothfruit,botharegoodforyou,but
theyarenotthesame,theylook,feeland
tastedifferentandgrowondifferent
Summary
Factorstoconsider
Localcodesandstandards
Operatorpreviousexperience
Application&location
Bestsuitedforthesystemoveralldesign
Deviceratingcoordination
Performance&reliability
Design&manufacturingqualitysystem
Engineeringsupport
Wheretogetmoreinformation