Transient Surges Analysis in

Medium -Low Voltage


Networks
Director
I.E. MS.c PhD. Francisco Jos Romn Campos

Codirector
I.E. MS.c PhD. Francisco Santamaria Piedrahta

Luis Eduardo Perdomo Orjuela


TOPICS

1.Introduction
2.Surge arrester IEEE model
3.Calculating surge arrester 115 4,16
[kV] Delta Wye
4.Simulations EMTP - ATP
5.Future work
INTRODUCTION

This Study

Surge arrester model IEEE


Surge arrester selection to
SE 115kV / 4,16 kV
Analysis overvoltage in SE

Introduction Generator Surges Comparison Future


IEEE MODEL SURGE ARRESTER

Introduction Generator Surges Comparison Future


IEEE MODEL SURGE ARRESTER
Voltage per Unit of Voltage per Unit of
Current [kA] 10 [kA], 8/20 s for 10 [kA], 8/20 s for
A0 A0
0,01 0,875
0,1 0,963 0,769
1 1,05 0,85
2 1,088 0,894
4 1,125 0,925
6 1,138 0,938
8 1,169 0,956
10 1,188 0,969
12 1,206 0,975
14 1,231 0,988
16 1,25 0,994
18 1,281 1
20 1,313 1,006

Introduction Generator Surges Comparison Future


SURGE ARRESTERS

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
Nominal voltage VLL = 115 kV
Maximun voltage Um = 123 kV (IEC 60071 -1)

1. MCOV

= = , []

2. TOVC

= , = , []

3. TOV10
,
= , = , []

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G

1. The specified time fault clearing for a second


, []
= = = ,
, []

(. )
= = , []
,

, ,
= = ,
,

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G

1. R0 = 100*d/n = 108
2. L0 = 0,2*d/n = 0,216 H
3. R1 = 65*d/n = 70,2
4. L1 = 15*d/n = 16,2 H
5. C = 100*n/d = 92,59 pF

d = 1,08 m
n=1

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - L
Nominal voltage VLL = 115 kV
Maximun voltage Um = 123 kV (IEC 60071 -1)

1. MCOV
= []
2. TOVC
= , = , []
3. TOV10
,
= , = , []

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - L

1. The specified time fault clearing for a second


, []
= = = ,
[]

(. )
= = , []
,

, ,
= = ,

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - L

1. R0 = 100*d/n = 139,7
2. L0 = 0,2*d/n = 0,2784 H
3. R1 = 65*d/n = 90,805
4. L1 = 15*d/n = 20,955 H
5. C = 100*n/d = 71,58 pF

d = 1,397 m
n=1

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS
Zinc Oxide Surge Arrester PEXLIM P-X ABB
Max.
System Rated Max. Continuous TOV
Voltage voltage operating voltage Capability Max. Residual voltage with current wave
IEC IEEE 1 [s] 10 [s] 30/60 [s] 8/20 [s]
MCOV 1 kA 2 kA 3 kA 5 kA 10 kA 20 kA 40 kA
Um [kV Ur [kV Uc [kV [kV [kV [kV [kV [kV [kV [kV [kV [kV [kV
rms] rms] rms] rms] rms] rms] peak] peak] peak] peak] peak] peak] peak]
123 90 72 72 104 99 176 182 187 195 205 225 246
96 77 77 11 105 188 194 199 208 219 240 263
102 78 82 118 112 199 207 212 221 233 255 279
108 78 84 125 118 211 219 224 234 246 270 295
114 78 92 132 125 223 231 237 247 260 284 312
120 78 98 139 132 234 243 249 260 273 299 328
129 78 104 149 141 252 261 268 279 294 322 353
132 78 106 153 145 258 267 274 286 301 329 361
138 78 111 160 151 270 279 286 299 314 344 377
144 78 115 167 158 281 291 299 312 328 359 394
150 78 121 174 165 293 304 311 325 342 374 410

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] L - N
Nominal voltage VLL = 4,16 kV
Maximun voltage Um = 7,2 kV (IEC 60071 -1)

1. MCOV
, []
= = , []

2. TOVC
,
= , = , []

3. TOV10
, ,
= , = , []

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] L - N

1. The specified time fault clearing for a second


, []
= = = ,
, []

(. )
= = , []
,

, ,
= = ,
,

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] L - N

1. R0 = 100*d/n = 21
2. L0 = 0,2*d/n = 0,0412 H
3. R1 = 65*d/n = 13,65
4. L1 = 15*d/n = 3,15 H
5. C = 100*n/d = 476,19 pF

d = 0,21 m
n=1

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] N - G
Nominal voltage VLL = 115 kV
Maximun voltage Um = 123 kV (IEC 60071 -1)

1. MCOV
= , , = , []
2. TOVC
= , , = , []
3. TOV10
,
= , , = , []

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] N - G

1. The specified time fault clearing for a second


, []
= = = ,
, []

(. )
= = , []
,

, ,
= = ,
,

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] N - G

1. R0 = 100*d/n = 21
2. L0 = 0,2*d/n = 0,042 H
3. R1 = 65*d/n = 13,65
4. L1 = 15*d/n = 3,15 H
5. C = 100*n/d = 476,19 pF

d = 0,21 m
n=1

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS POLIM H..N
ABB

Max.
Continuous
operating Rated
voltage voltage Max. Residual voltage with current wave
IEC 8/20 [s]
5 kA [kV 10 kA [kV 20 kA [kV 40 kA [kV
Uc [kV rms] Ur [kV rms] peak] peak] peak] peak]
4 5 11,2 11,6 12,7 14,2
5 6,3 13,9 14,5 15,9 17,7

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
2.2E5
2E5
2.5E5
Nonlin 1.8E5 Nonlin
1.6E5
2E5
1.4E5

1.5E5 1.2E5
1E5

1E5 8E4
6E4
5E4 4E4
2E4
U [V]

U [V]
-2E4
-5E4 -4E4
-6E4
-1E5 -8E4
-1E5
-1.5E5 -1.2E5
-1.4E5
-2E5
-1.6E5
-1.8E5
-2.5E5
-2E5
-2.2E5
-2E4 -1.5E4 -1E4 -5E3 5E3 1E4 1.5E4 2E4 -2E4 -1.5E4 -1E4 -5E3 5E3 1E4 1.5E4 2E4
I [A] I [A]

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
250

*10 3

200

150

100

50

0
0 10 20 30 40 [us] 50
(f ile VaristorIEEE.pl4; x-v ar t) c:XX0004-XX0001 v :XX0001

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
500

*10 3

400

300

200

100

0
0 10 20 30 40 [us] 50
(f ile VaristorIEEE.pl4; x-v ar t) c:XX0004-XX0001 v :XX0001

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] L - N

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
1.8E4 1.4E4

1.6E4 Nonlin 1.2E4 Nonlin


1.4E4
1E4
1.2E4

1E4 8E3

8E3 6E3
6E3
4E3
4E3
2E3
2E3
U [V]

U [V]
-2E3
-2E3
-4E3
-4E3
-6E3
-8E3 -6E3

-1E4 -8E3
-1.2E4
-1E4
-1.4E4

-1.6E4 -1.2E4

-1.8E4 -1.4E4

-2E4 -1.5E4 -1E4 -5E3 5E3 1E4 1.5E4 2E4 -2E4 -1.5E4 -1E4 -5E3 5E3 1E4 1.5E4 2E4
I [A] I [A]

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
16

*10 3

13

10

-2
0 10 20 30 40 [us] 50
(f ile VaristorIEEE.pl4; x-v ar t) v :XX0002 c:XX0012-XX0002

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] L - G
50

*10 3

40

30

20

10

-10
0 10 20 30 40 [us] 50
(f ile VaristorIEEE.pl4; x-v ar t) v :XX0002 c:XX0012-XX0002

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 4,16 [kV] N - G

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] N - G
1.4E4 1.1E4
1E4
Nonlin Nonlin
1.2E4 9E3
8E3
1E4
7E3
8E3 6E3
5E3
6E3
4E3
4E3 3E3
2E3
2E3
1E3
U [V]

U [V]
-1E3
-2E3
-2E3
-4E3 -3E3
-4E3
-6E3
-5E3
-8E3 -6E3
-7E3
-1E4
-8E3
-1.2E4 -9E3
-1E4
-1.4E4 -1.1E4

-2E4 -1.5E4 -1E4 -5E3 5E3 1E4 1.5E4 2E4 -2E4 -1.5E4 -1E4 -5E3 5E3 1E4 1.5E4 2E4
I [A] I [A]

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] N - G
13
*10 3
11

-1
0 10 20 30 40 [us] 50
(f ile VaristorIEEE.pl4; x-v ar t) v :XX0003 c:XX0020-XX0003

Introduction Generator Surges Comparison Future


CALCULATING SURGE ARRESTERS 115 [kV] N - G
50

*10 3

40

30

20

10

-10
0 10 20 30 40 [us] 50
(f ile VaristorIEEE.pl4; x-v ar t) v :XX0003 c:XX0020-XX0003

Introduction Generator Surges Comparison Future


FUTURE WORK
1. Include in the first half the answer distribution
transformer along with surge arresters in the
presence of a traveling wave.
2. Implement model induced currents in the lines
developed by the EMC group of the
Universidad Nacional de Colombia

Introduction Generator Surges Comparison Future