Anda di halaman 1dari 121

All Seasons

°CLIMATE COMFORT
Heating

Air Conditioning

Hybrid Applied Systems

Refrigeration
Overview of possible chapters for
technical training

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction
2. System build up
3. System Operation
4. Installation
5. Commissioning and test run
6. Maintenance
7. Troubleshooting
8. Practical Session
9. Technical Data
10. Accessory List

All Seasons °CLIMATE COMFORT Name: 30 March 2018 2


TOP SECRET
1. Introduction SECRET
INTERNAL USE ONLY
PUBLIC

Which opportunities in residential heating market?


Daikin Altherma hybrid heat pump solution for gas boiler replacement
market
Hybrid = combination of two energy sources

HP system
Gas boiler

HP outdoor unit Gas boiler Space heating / cooling


1,8 - 5kW / 1,8 - 8kW 9 - 33kW DHW heating

Refrigerant
gas cold
water
All Seasons °CLIMATE COMFORT Name: 30 March 2018 3
TOP SECRET
1. Introduction SECRET
INTERNAL USE ONLY
PUBLIC

Daikin Altherma solution for gas boiler replacement market

New build

All Seasons °CLIMATE COMFORT Name: 30 March 2018 4


TOP SECRET
1. Introduction SECRET
INTERNAL USE ONLY
PUBLIC

Daikin Altherma solution for gas boiler replacement market

Renovation
New build
Change emitters

All Seasons °CLIMATE COMFORT Name: 30 March 2018 5


TOP SECRET
1. Introduction SECRET
INTERNAL USE ONLY
PUBLIC

Daikin Altherma solution for gas boiler replacement market

Renovation
New build
Change emitters Keep emitters

Oil boiler Gas boiler


replacement replacement

All Seasons °CLIMATE COMFORT Name: 30 March 2018 6


TOP SECRET
1. Introduction SECRET
INTERNAL USE ONLY
PUBLIC

1. Introduction

End user benefits

1 Save money versus new gas condensing boiler

2 Low investment – use existing equipment

Installer benefits

1 One HP solution for all renovation applications

2 Easy and fast installation of RES

Wolesaler benefits

1 Low stock value covering all replacement applications

All Seasons °CLIMATE COMFORT Name: 30 March 2018 7


TOP SECRET
2. System build up SECRET
INTERNAL USE ONLY
PUBLIC

All Seasons °CLIMATE COMFORT Name: 30 March 2018 8


TOP SECRET
2. System build up SECRET
INTERNAL USE ONLY
PUBLIC

Similar to the wall hung boilers all connections are located at the bottom of
the indoor unit.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 10


TOP SECRET
2. System build up SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

expansion
vessel ( 10 L )

PCB board

3-way circulating pump


valve

All Seasons °CLIMATE COMFORT Name: 30 March 2018 11


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Depending on the position of the 3-way-valve, the gas condensing boiler can
either be bypassed or not. The heat pump can either operate or not, depending
on the active operation mode.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 12


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Three different heating modes of operation and a DHW operation mode are
possible ( heat pump only / hybrid / gas boiler only )

I. Heat pump operation only

All Seasons °CLIMATE COMFORT Name: 30 March 2018 13


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

II. Hybrid operation mode ( in which both the heat pump and
the gas condensing boiler are operating )

All Seasons °CLIMATE COMFORT Name: 30 March 2018 14


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

III. Gas condensing boiler operation mode only

All Seasons °CLIMATE COMFORT Name: 30 March 2018 16


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

IV. .a. DHW only

All Seasons °CLIMATE COMFORT Name: 30 March 2018 17


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

IV. . b. DHW + heating

Note: The system can continue generating heat in the heat pump operation
during DHW-tapping. Depending on the active mode, this happens as
follows:

All Seasons °CLIMATE COMFORT Name: 30 March 2018 18


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

1. During heat pump only operation: keep heat pump operation and bypass the
boiler.

2. During hybrid operation: keep heat pump operation at initial intermediate set
flow temperature and bypass the boiler.

3. During gas boiler only operation: space heating will no longer be provided.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 19


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Additional facts concerning the pump operation

1. The pump is a high efficiency pump and PWM controlled.

2. It operates with focus on the parameter settings:


Para Mode Range Factory setting
8-0b Heat pump mode 10~20, 13 L/min
8-0c Hybrid mode 10~20, 10 L/min
8-0d Gas boiler mode 10~20, 10 L/min

3. If the flow rate drops and there is a risk for 7H error, the pump speeds up.

4. The minimum flow rate is 5 L/min.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 20


TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler specifications

Tapping rates

DHW Output CH
Model (l/min) (kW)
∆T=50 ∆T=35 ∆T=25
EHYKOMB33AA
9 12,8 18 7 - 32 (*)
RHYKOMB33AA 9 12,8 18 7 - 32 (*)

All Seasons °CLIMATE COMFORT Name: 30 March 2018 21


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

The way by which the switching between the different heating operation modes
is optimized can be economical or ecological and has to be set by the installer.

1. Economical: Minimize energy costs


2. Ecological: Reduce Primary Energy consumption

All Seasons °CLIMATE COMFORT Name: 30 March 2018 22


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Instant DHW heat exchanger Heating heat exchanger

All Seasons °CLIMATE COMFORT Name: 30 March 2018 23


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 24


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section


CH Flow

DHW Gas / Air


OUT Mixture

Cold Water CH
IN Return

Flue Gas / Condensate boiler


All Seasons °CLIMATE COMFORT Name: 30 March 2018 25
3. System Operation TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 26


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Control temp. sensors NTC (12 kΩ)

NTC 1. Flow
- Boiler thermostat adjustable 30 - 90° C
- Max. temp. safety control 105° C
- Keep hot facility (Eco/comfort mode)

NTC 2. Return
- Control ▲- t ° C
- Antifrost thermostat 5 and 3° C

NTC3 (hot water pipe)


- Control DHW flow 40 - 65° C
- Adjustable 40 - 65° C
All Seasons °CLIMATE COMFORT Name: 30 March 2018 27
TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Operation Central Heating

 Room thermostat demand


 Pump active
 Fan active
 Ignition
 Gas valve opens
 Burner active
 Safety + function control by NTC 1
 Flow control by NTC 2

All Seasons °CLIMATE COMFORT Name: 30 March 2018 28


TOP SECRET
3. System Operation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Operation Domestic Hot Water

 DHW demand
 Flow switch closed 2.1 L/min
requested
 Pump inactive
 Fan active
 Ignition
 Gas valve active
 Burner active
 Temp. control by NTC 3
 Safety control by NTC 1

All Seasons °CLIMATE COMFORT Name: 30 March 2018 29


TOP SECRET
4. Equipment Selection SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Outdoor unit EVLQ05CAV3


EVLQ08CAV3

Indoor unit EHYHBH05AA


EHYHBH08AA
EHYHBX08AA

Gas condensing boiler EHYKOMB33AA

All the boilers are delivered with factory settings for natural gas!
All Seasons °CLIMATE COMFORT Name: 30 March 2018 30
TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Gas boiler section

The minimum requested space at the right hand side of the unit is 350 mm.
( for service to have access to the main pcb of the heat pump section )
All Seasons °CLIMATE COMFORT Name: 30 March 2018 31
TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Note: The mounting rail is included in the


accessory box of the gas boiler.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 32


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

b Heating return
a Heating flow

All Seasons °CLIMATE COMFORT Name: 30 March 2018 33


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 35


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Internal connection

All Seasons °CLIMATE COMFORT Name: 30 March 2018 36


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Internal connection

All Seasons °CLIMATE COMFORT Name: 30 March 2018 37


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Electrical connection

All Seasons °CLIMATE COMFORT Name: 30 March 2018 38


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Changing the gas type

All the boilers are delivered in natural gas!

All Seasons °CLIMATE COMFORT Name: 30 March 2018 39


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

-The condensate siphon has to be filled


previously

- Recommendation: the further


condensate drain pipe should be in DN32

All Seasons °CLIMATE COMFORT Name: 30 March 2018 40


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Flue system

- principally designed for operation independent of room air


- it is equipped with a connection 60/100 mm.
- the appropriate test adapter is included.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 41


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

The hybrid condensing


wall hung boilers are
certified for:

C13,
C33,
C43,
C53,
C63,
C83

type flue gas systems.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 42


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Please note that the amount of bends / elbows will influence the max. length of the
flue system.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 43


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Example 1 ( C13 )

9,7m - 4m = 5,7m maximal useable length.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 44


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Example 2 ( C33 )

10m - 2 x 4m = 2m maximal useable length

conclusion - take the 80/125mm


All Seasons °CLIMATE COMFORT Name: 30 March 2018 45
TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 46


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 47


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 48


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Gas boiler section

Outdoor unit
X1Y:1-2 2 Signal
L/N 230V + PE User interface
1-2-3 +PE
X1M:1,2,3
+PE
X1M
X5M
1,2,3 +PE
1,2

L/N 230V + PE ( optional )


X1M
Main switch 31, 32 +PE X2M
M2S – 2 way valve
7,8 or 9 field side NO / NC
box LT / HT Signal ( optional )
X5M 230V
3, 4

A1P X39A
Wire from
factory Heat pump section Future M3S – 3 way
delivered valve for external DHW
tank
X2

L/N 230V +PE) X2


2, 4 Boiler section
All Seasons °CLIMATE COMFORT Name: 30 March 2018 49
TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

In door unit

All Seasons °CLIMATE COMFORT Name: 30 March 2018 50


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 51


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 52


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 53


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Indoor unit switch box

All Seasons °CLIMATE COMFORT Name: 30 March 2018 54


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Indoor unit switch box


Hybrid controller

All Seasons °CLIMATE COMFORT Name: 30 March 2018 55


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Indoor unit switch box


optional

- to connect a shut off valve

All Seasons °CLIMATE COMFORT Name: 30 March 2018 56


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Indoor unit switch box


optional

- to connect a 3 port valve

All Seasons °CLIMATE COMFORT Name: 30 March 2018 57


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Outdoor unit
power supply and interconnection

All Seasons °CLIMATE COMFORT Name: 30 March 2018 58


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Flow- and return pipe heating side

Factory-made connections are carried out in DN 22 CU


Further pipe work has to be done in DN 25 or bigger!

All Seasons °CLIMATE COMFORT Name: 30 March 2018 59


TOP SECRET

5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Bypass valve

The bypass valve (DN 25) is obligatory necessary and has to be integrated
at the most remote possible point in the heating circuit.

Device performance Size bypass valve


6 – 8 kW DN 20

The minimum requested water volume between the indoor unit and the bypass
valve ( and back ) has to be 10 liters.

Other piping restrictions

Max. distance between 3 way-valve and hydrokit: 3m


Max. distance between hydrokit and sanitary tank: 10 m
All Seasons °CLIMATE COMFORT Name: 30 March 2018 60
TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Setting up an outdoor unit

» Use two stripes bases (see drawing).


» Arrange a faultless drain of the condensate. (For example:
gravel bed between the bases – made of fist sized gravels
until the frost free zone).

The device should be installed at least 30 cm above the soil.

It can also be used a frame or a wall console (see price list). Please consider
when using a wall console, that vibration noises can be transmitted to the house
wall.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 61


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 62


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Setting up an outdoor unit

Distance between unit and wall 25 cm


recommended
ROTEX accessory
EKFT008CA
Nr.140541

580 mm Air direction

Wall windproof
Min. 200mm 300

Min. 600mm 283


frostfree area

850 mm
80 mm

Drainage necessary in case of an solid ground


Protection pipe
Protection pipe DN 100 / use max. 15° elbows only

All Seasons °CLIMATE COMFORT Name: 30 March 2018 63


TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Refrigerant pipes
The refrigerant pipes consist of a liquid- and a gas pipe.
Diameter gas pipe 5/8“ = 15,9 mm
Diameter liquid pipe 1/4“ = 6,4 mm
Max. piping length between outdoor unit and hydro-box: 20 m
Min. piping length between outdoor unit and hydro-box: 3m
Max. height difference between outdoor unit and hydro-box: 20 m
The additional charging can maximum be 0,02kg*(20-10) = 0,2 kg.

Please pay special ATTENTION to the following:


1. Only install the refrigerant pipes offered by Daikin / ROTEX, so that the
sleeves fit, which are supplied with the device.
2. Install the pipes in the ground always in an empty tube ( Ø 100 mm ) – only
use 15° bows. When installing the refrigerant pipes under the screed, please
always consider that the bricking has to be sealed up on site.
3. For excluding water entry into preinstalled pipes, they have to be closed
tightly.
All Seasons °CLIMATE COMFORT Name: 30 March 2018 64
TOP SECRET
5. Installation SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

The outdoor unit has to be supplied with power at least 6h before commissioning
( protection of the compressor ).

All Seasons °CLIMATE COMFORT Name: 30 March 2018 65


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 66


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 67


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

 *: If the required heat load is lower than the capacity, the heat pump can
provide, the boiler will function and provide the necessary back-up heating
capacity.
 **: If hybrid mode is activated, in order for the heat pump to be able to get

into stable operation, the heat pump will first be turned on and once in
stable operation, the boiler will come in as well.
 ***: DHW is provided by the boiler. The heat pump can still provide space

heating.
All Seasons °CLIMATE COMFORT Name: 30 March 2018 68
TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Indication of the functioning of the hybrid modules

The mode in which the hybrid is functioning, is not as such mentioned on the
user interface.

What is mentioned is - for heating and DHW mode – which hybrid modules
(heat pump or condensing gas boiler) are working at the moment, refer to the
table below. Apart from the heating mode, there’s also a domestic hot water
mode.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 69


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

2. Afterwards, the system layout will start up. The submenus “Standard”,
“Options” and “Confirm layout” can be set.

 The unit type, compressor type and indoor software type are read-only.
 For Unit control method, either LWT- or RT-control can be chosen. For
both options there can be specified to choose either for a fixed LWT or a
weather dependent one.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 70


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

The Options submenu looks as follows:

 if the system can prepare domestic hot water (set to “Yes” for instant DHW
production);
 if a DHW tank is installed in the system;
 which type of external sensor is installed (outdoor sensor/room sensor);
 if an external gas meter is used for power measurement.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 71


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Special Start-up of the system

There are several occasions which can cause a special start-up, where the unit
will switch in boiler only mode.

1. If ΔT between room temperature and room set point temperature > 5°C, the
“quick heat-up” function will start.

2. If the Leaving Water Temperature < 15 °C, the boiler will start up. The heat
pump will only come in when the temperature has increased up to 18°C.

3. If a low set point temperature is required (e.g. for screed dry out), the heat
pump will not be operated ( caused by LWT < 15 °C = similar to 2.)

All Seasons °CLIMATE COMFORT Name: 30 March 2018 72


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Special Start-up of the system

The flow rates has to be set accordantly to the requested system capacity.

1. Heat pump mode


2. Hybrid mode
3. Gas boiler mode

All Seasons °CLIMATE COMFORT Name: 30 March 2018 73


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Choice between economical or ecological optimization of savings

Therefor, in “Installer settings”, choose “System operation” and then choose


the corresponding “Savings mode”.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 74


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Choice between economical or ecological optimization of savings

Therefor, in “Installer settings”, choose “System operation” and then choose the
corresponding “Savings mode”.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 75


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

1. Economical mode
Requires: setting gas and electricity prices, daily schedule timer for electricity
prices!

All Seasons °CLIMATE COMFORT Name: 30 March 2018 76


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

The user interface allows the setting of a (fixed) gas price (0~999,00 ), and 3
electricity price ( 0~999,00 ) levels. A day/night tariff or a weekend tariff for the
electricity price can be set with a schedule timer Economical mode

The gas price and electricity prices must be set in the same currency, as
illustrated in the example below:

All Seasons °CLIMATE COMFORT Name: 30 March 2018 77


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Auto emergency

During emergency (the occurrence of a heat pump failure), the gas boiler can
serve as a back-up heater and either automatically or non-automatically take
over the heat load.

- If automatic: If e.g. the heat pump malfunctions, the boiler will take over
the heat load as if in sole boiler mode.

- If non-automatic: If e.g. the heat pump malfunctions, DHW and SH


operation will be turned off and they will need to be recovered manually
by the end-user. ( = default setting )

All Seasons °CLIMATE COMFORT Name: 30 March 2018 79


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Operation Readout
a ON/OFF-button 1 ON/OFF
b ̶ - button 2 Main display
c + - button 3 Room heating operation
d Domestic hot water function Off/Eco/On 4 Operation of hot water preparation
e Maintenance button 5 Domestic hot water-comfort function Eco
f Reset button 6 Domestic hot water-comfort function ON (continous)
7 Maintenance display
8 Flashes when an error is displayed

All Seasons °CLIMATE COMFORT Name: 30 March 2018 82


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

There is no need to change or set the parameters in the gas boiler.


Just the burner set up ( capacity limitation, start-up behaviour, and ...... may has
to be changed ) or if we want to use a separate storage tank.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 83


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

The software is split into 2 levels and can be


set on the display :

1. User level :

- ON/Off + CH pressure
reading
- DHW Setting
(Eco/Comfort/Off)
- Reset

2. Installer / service level :


- Protected by access code.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 84


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 85


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 86


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 88


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 89


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Remark: the 8H error message will


only occur when the leaving
water temperature exceeds
95°C

All Seasons °CLIMATE COMFORT Name: 30 March 2018 90


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 93


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 97


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 98


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 100


TOP SECRET
6. Commissioning SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 101


TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section


- Open the display cover
- Unscrew both screws
- Remove front cover
- Remove the flue pipe
- Remove and clean the
condensate collector

All Seasons °CLIMATE COMFORT Name: 30 March 2018 102


TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 103


TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 104


TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

- Remove the front plate

All Seasons °CLIMATE COMFORT Name: 30 March 2018 105


TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

- Remount the front plate


Attention: Tighten bolts crosswise
- Install the condensate collector
and flue pipe
- Check all gas connections
- Remount the front cover
- Tighten both fixing screws

All Seasons °CLIMATE COMFORT Name: 30 March 2018 106


TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

A+B

P inlet
All Seasons °CLIMATE COMFORT Name: 30 March 2018 107
TOP SECRET
7. Maintenance SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

• Remove cap A.
• Place the probe of the CO2
measuring device into the flue gas
test point. A+B
• Check CO2 on max. power (H).
CO2 : 9,1 ± 0,5 %
• Check CO2 on min.. power (L).
“Value H” minus ~ 0,3 % but min. 8,6 %
• Adjust, if necessary the CO2
setting with the plastic screw B
(Torx T15).
• Replace the cap A and close the
flue gas test nipple.
P inlet
All Seasons °CLIMATE COMFORT Name: 30 March 2018 108
TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Heat pump section

Overview of (hybrid-specific) fault codes

If a boiler failure occurs, the hybrid user interface will detect and display a
boiler abnormality and insists to check the boiler. In order to assign the correct
address to the fault code, the user interface will refer to the boiler manual.

Figure : Boiler control panel indicating


a certain fault code
Figure : Hybrid user interface showing a boiler abnormality detection. To verify
the fault code, the boiler control panel must be checked together with the
hybrid boiler module manual.

All Seasons °CLIMATE COMFORT Name: 30 March 2018 109


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

When the controller finds an abnormal situation the boiler will be locked.

- The service LED will start to flash.

- A code (number) will be shown in


the left display.

- All codes are related to the source


of the fault. See fault code list

All Seasons °CLIMATE COMFORT Name: 30 March 2018 110


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

- 4 starts are possible before the burner turns into eror mode
- delay time between each new start is 15 sec

All Seasons °CLIMATE COMFORT Name: 30 March 2018 111


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

All Seasons °CLIMATE COMFORT Name: 30 March 2018 112


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Burner ignites noisily


Possible causes: Solution:

Spark gap app. 4.5 mm

All Seasons °CLIMATE COMFORT Name: 30 March 2018 113


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler section

Burner ignites noisily

Possible causes: Solution:

All Seasons °CLIMATE COMFORT Name: 30 March 2018 114


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

Service process Rotex brand Daikin brand

Spare parts DENV Spare Parts

Know how transfer Helpdesk (mail, …) & include field 1st line: Affiliate (ROG/DACI/DAF/DAUK)
investigation
2nd line: Rotex Service

Training Affiliate to contact Daikin Europe Academy,

Training execution: Rotex Service

Service Manual Cooperation of Rotex Service, EDC, Intergas, …

Distribution by Rotex (DENV put on extranet)

Claim treatment GIB (input & reply) & include field * Input; Affiliate
investigation
* Service: Rotex Service

* Quality: different factories

Hybrid = Intergas through Rotex Service, DICZ & DENV

Boiler = DTAS

CQM Organization: DENV

Reporting: Rotex Service (Intergas, DTAS, DENV, …)

GPSC Contact point: DENV Service (Rotex to attend)

ESV ESV communicated through DENV Service

ECHC Claim (financial) through DENV

All Seasons °CLIMATE COMFORT Name: 30 March 2018 115


TOP SECRET
8. Troubleshooting SECRET
INTERNAL USE ONLY
PUBLIC

DENV
EDC/MFG

DICZ Intergas
(OEM)

Hybrid (3 components)

Rotex Brand Daikin Brand


(It, Ger) (UK,FR)
Sales route DENV  ROG DENV  DAUK
DENV  DACI DENV  DAF
Sales Launch September 2013
After sales technical operations &
administration
Rotex Service Department

After sales planning, control &


DENV Service Division
administration
All Seasons °
CLIMATE COMFORT Name: 30 March 2018 116
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler specifications

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 117
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC
Indoor unit

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 118
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Outdoor unit HP specifications

NOMINAL CAPACITY AND NOMINAL INPUT

For combination Outdoor units EHYRLQ005 EHYRLQ008 EHYRLQ008


indoor units + Indoor units Indoor H/P module EHYHBH05 EHYHBH08 EHYHBX08
outdoor units Condition 1 Heating capacity Minimum kW 1,80 1,80 1,80
Nominal kW 4,40 7,40 7,40
Maximum kW 5,12 10,02 10,02
Cooling capacity Minimum kW --- --- 2,50
Nominal kW --- --- 6,86
Heating PI Nominal kW 0,87 1,66 1,66
Cooling PI Nominal kW --- --- 2,01
COP Nominal - 5,04 4,45 4,45
EER Nominal - --- --- 3,42
Condition 2 Heating capacity Minimum kW 1,80 1,80 1,80
Nominal kW 4,03 6,89 6,89
Maximum kW 4,90 9,53 9,53
Cooling capacity Minimum kW --- --- 2,50
Nominal kW --- --- 5,36
Heating PI Nominal kW 1,13 2,01 2,01
Cooling PI Nominal kW --- --- 2,34
COP Nominal - 3,58 3,42 3,42
EER Nominal - --- --- 2,29
Notes * Condition 1
- cooling Ta 35 C - LWE 18 C (DT=5 C)
- heating Ta DB/WB 7 C/6 C - LWC 35 C ( DT =
5 C)
* Condition 2
- cooling Ta 35 C - LWE 7 C ( DT = 5 C )
- heating Ta DB/WB
° 7 C/6 °C - LWC 45 ° C ( DT =
5 C) ° ° °
°

° ° °
° ° °
°
All Seasons °
CLIMATE COMFORT Name: 30 March 2018 119
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Outdoor unit HP specifications

TECHNICAL SPECIFICATIONS

Casing Colour Ivory white


Material <Polyester painted galvanised steel>
Dimensions Packing Height mm 797
Width mm 990
Depth mm 390
Unit Height mm 735
Width mm 832
Depth mm 307

Weight Machine Weight : ERLQ004* / ERLQ006* & ERLQ008* kg 54 / 56


Gross Weight : ERLQ004* / ERLQ006* & ERLQ008* kg 57 / 59
Packing Material EPS, CARTON
Weight kg 3
Heat exchanger Specifications Length mm 845
°
N of rows 2
Fin pitch mm 1,8
°
N of stages 32
Tube type <Hi-Xa(8)>
Fin Type <WF fin>
Treatment <Anti-corrosion treatment (PE)>
Fan Type <Propeller>
Quantity 1
Air flow rate (nominal at 230V) Heating m³/min 45 47 47
Cooling m³/min 52,5 52,5 52,5
Discharge direction <Horizontal>
Motor Quantity 1
Output W 53
Compressor Quantity 1
Motor Model 2YC36BXD#C 2YC45DXD#C 2YC45DXD#C
Type <Hermetically sealed swing compressor>
Operation range (1)
°
Heating Min CDB -25

°
(Heat pump) Max CDB 25

°
Cooling Min CWB 10

°
Max CWB 43

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 120
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Outdoor unit HP specifications


TECHNICAL SPECIFICATIONS
Sound level Heating Sound power ( 4/6/8 ) dBA 61 / 61 / 62
(nominal) (Heat pump) Sound pressure (4/6/8) (2) dBA 48 / 48 / 49
Cooling Sound power dBA 63 / 63 / 63
Sound pressure (4/6/8) (2) dBA 48 / 49 / 50
Refrigerant Type <R-410A>
Charge EHYRLQ005 / EHYRLQ008 kg 1.45 / 1.60
Control <Expansion valve(electronic type)>
°
N of circuits 1
Refrigerant oil Type <FVC50K>
Charged volume l 0,75
Piping connections Liquid Type <Flare connection>
Diameter (OD) mm <6,35>
Gas Type <Flare connection>
Diameter (OD) mm <15,9>
Drain Quantity 2
Type hole
Diameter (OD) mm 1xØ15 + 1xØ20
Piping length Minimum m 3
Maximum m 30
Additional refrigerant charge kg/m 0,02 IF > 10 m

Height difference between outdoor unit and indoor unit Maximum m 20


Defrost method <Reverse cycle>
Defrost control <Sensor for outdoor heat exchanger temperature>
Capacity control method <Inverter controlled>
Standard accessories Item <Installation manual>
Quantity 1
Notes (1) See operation range drawing. (*) range increase by support backup heater. (**) range increase by support booster heater or backup heater.
(2) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment.

Refer to sound spectrum drawing for more information.

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 121
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Outdoor unit HP specifications

ELECTRICAL SPECIFICATIONS

Power supply Name <V3>


Phase 1
Frequency Hz 50
Voltage V <230>
Voltage range Minimum V <-10%>
Maximum V <+10%>
Current Nominal running current Cooling A -
Heating A -
Cooling A 18 (see Note (2) )
Starting current Heating A 18 (see Note (2) )
Maximum running current Cooling A 18
Heating A 18
Zmax Ω -
Minimum Ssc value kVA Equipment complying with EN/IEC 61000-3-12 (1)
Recommended fuses A 20
Wiring connections For power supply Quantity 3
Remark -
For connection with indoor Quantity 3
Remark No earth wire
Notes (1) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with
input current >16A and ≤75A per phase.

(2) : See figure A

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 122
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Indoor HP module specifications

EHYHBH05 EHYHBH08 EHYHBX08


Casing Colour White
Dimensions Unit Height mm 900
Width mm 450
Depth mm 165
Net weight kg 28
Main components Pump Type DC motor
nr. of speed Inverter conttrolled
Power input W 45
Water side Heat exchanger Type Brazed plate
qty 1
Water volume l 0,9 1,3
Water flow rate Min. l/min 5,0 11,0
Insulation material green felt green felt elastomeric foam
Expansion vessel Volume l 10
Max. water pressure bar 3
Pre pressure bar 1
Water Filter Diameter perforations mm 1
Material body : copper + brass / filter element : stainless steel
Water circuit Piping connections ø (1) inch G 1-1/4 (FEMALE)
Safety valve bar 3
Manometer Yes
Drain valve / Fill valve Yes
Shut off valves Yes
Air purge valve Yes
Refrigerant circuit Gas side ø mm 15,9
Liquid side ø mm 6,35
°
Operation range Space cooling C - - 10 ~ 43
Outdoor temperature °
(heat pump operation) Space heating (heat pump) C -25 ~ 25
°
Water temperature Space cooling C - - 5 ~ 22
°
Space heating C 15 ~ 55
Notes: (1) Value mentioned is connection after ball valves. Connection at unit is G1-1/4 FEMALE.

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 123
TOP SECRET
9. Technical Data SECRET
INTERNAL USE ONLY
PUBLIC

Gas boiler specifications

GAS MODULE

INDOOR UNIT *EHYKOMB33AA

Function Heating only

Thermal Load (Hi) Min. - Max. kW 7.5-32,7

Heating Power CH Min. - Max. 80/60 kW 7.9-31.9

Efficiency CH NCV 80/60 % 98

Efficiency CH NCV 40/30 (30%) % 107

Heating Power DHW Min. - Max. kW 7.9-31.9

Efficiency DHW NCV % 105

Casing Colour RAL9010

Dimensions Unit HeightxWidthxDepth mm 710x450x240

Weight Unit kg 36
Gas categories:

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 124
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Standard accessories
11. Accessory list

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 125
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list
Part.no. Article Description
Client

EKFGP6837 Terminal vertical PP/GLV 60/100 AR460


Dakdoorvoer PP/GLV 60/100 AR460
Roof Terminal PP/GLV 60/100 AR460

EKFGS0518 Solin Pb/GLV 60/100 18°-22°


Loodslab stuts Pb/GLV 60/100 18°-22°
Weather Slate Steep Pb/GLV 60/100 18°-22°

EKFGS0519 Solin Pb/GLV 60/100 23°-27°


Loodslab stuts Pb/GLV 60/100 23°-27°
Weather Slate Steep Pb/GLV 60/100 23°-27°

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 126
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories

Part.no. Article Description


Client

EKFGP7910 Solin réglable PF 60/100 25°-45°


Regelbare losse pan PF 60/100 25°-45°
Weather Slate Steep PF 60/100 25°-45°

EKFGS0523 Solin Pb/GLV 60/100 43°-47°


Loodslab stuts Pb/GLV 60/100 43°-47°
Weather Slate Steep Pb/GLV 60/100 43°-47°

EKFGS0524 Solin Pb/GLV 60/100 48°-52°


Loodslab stuts Pb/GLV 60/100 48°-52°
Weather Slate Steep Pb/GLV 60/100 48°-52°

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 127
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list
Part.no. Article Description
Client

EKFGS0525 Solin Pb/GLV 60/100 53°-57°


Loodslab stuts Pb/GLV 60/100 53°-57°
Weather Slate Steep Pb/GLV 60/100 53°-57°

EKFGF3231 Solin toit plat Alu 60/100 0°-15°


Losse pan plat dak Alu 60/100 0°-15°
Weather Slate Flat Alu 60/100 0°-15°

EKFGP7372 Solin toit plat Alu 60/100


Losse pan plat dak Alu 60/100
Weather Slate Flat Alu 60/100

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 128
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories

Part.no. Article Description


Client

EKFGP2978 Kit horizontal PP/GLV 60/100


Kit Muurdoorvoer PP/GLV 60/100
Wall Terminal Kit PP/GLV 60/100

EKFGP2977 Kit horizontal low profile PP/GLV 60/100


Kit low profile Muurdoorvoer PP/GLV 60/100
Wall Terminal Kit low profile PP/GLV 60/100

EKFGP4651 Conduit PP/GLV 60/100 x 500mm


Leiding PP/GLV 60/100 x 500mm
Extension PP/GLV 60/100 x 500mm

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 129
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list
Part.no. Article Description
Client

EKFGP4652 Conduit PP/GLV 60/100 x 1000mm


Leiding PP/GLV 60/100 x 1000mm
Extension PP/GLV 60/100 x 1000mm

EKFGP4664 Coude PP/GLV 60/100 30°


Bocht PP/GLV 60/100 30°
Elbow PP/GLV 60/100 30°

EKFGP4661 Coude PP/GLV 60/100 45°


Bocht PP/GLV 60/100 45°
Elbow PP/GLV 60/100 45°

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 130
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list
Part.no. Article Description
Client

EKFGP4660 Coude PP/GLV 60/100 90°


Bocht PP/GLV 60/100 90°
Elbow PP/GLV 60/100 90°

EKFGP4667 Élement de mesure en T avec inspection PP/GLV


60/100
T-inspectiemeetelement PP/GLV 60/100
Meas. Tee with Inspection Panel PP/GLV 60/100

EKFGP4631 Fixation Dn.100


Bevestiging Dn.100
Wall Bracket Dn.100

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 131
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list
Part.no. Article Description
Client

EKFGP1292 Kit horizontal PP/GLV 60/100 UK Only


Kit Muurdoorvoer PP/GLV 60/100
Wall Terminal Kit PP/GLV 60/100

EKFGP1293 Kit horizontal low profile PP/GLV 60/100 UK Only


Kit low profile Muurdoorvoer PP/GLV 60/100
Wall Terminal Kit low profile PP/GLV 60/100

EKFGP1294 Plume Managment Kit 60 UK Only

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 132
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list
Part.no. Article Description
Client

EKFGP1295 Flue Deflector 60 UK Only

EKFGP1284 PMK Elbow 60 90 UK Only

EKFGP1285 PMK Elbow 60 45° (2 pcs) UK Only

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 133
TOP SECRET
10. Accessories SECRET
INTERNAL USE ONLY
PUBLIC

Exhaust accessories
11. Accessory list

Part.no. Article Description


Client

EKFGP1286 PMK Extension 60 L=1000 incl. breaket UK Only

EK??? (tbc) Boiler connection 2xD80 parallel

All Seasons °
CLIMATE COMFORT Name: 30 March 2018 134