Samiya Zafar
Assistant Professor, EED NEDUET
M.Engg Fall Semester 2017
Application of Inverse Definite Minimum
Time Relay on a Distribution Feeder
Consider the same feeder with two buses A and B
where IDMT OC relays are to be used.
TOS,A = 0.07 s.
Thus, we get the required operating time of RA for
maximum fault at bus B:
TR,A max fault at B = 0.2 + 0.5 + 0.07 = 0.77 s
The TMS of RA can be found from the following
1) Start the setting from the relay at the tail end of the
system.
Schneider
MiCom P115
AEG PS 451
MiCom P115 is a 3 phase and earth fault non-
directional over current protection relay. The P115
must be configured to the system and application by
means of the appropriate settings. All current
settings refer to nominal current (1 A or 5 A).
The SIEMENS SIPROTEC 7SJ601 is a numerical over
current relay which, in addition to its primary use in
radial distribution power systems and motor
protection, can also be employed as backup for line,
transformer and generator differential protection.
It provides definite-time and inverse- time over current
protection.
The nominal CT currents applied to the SIPROTEC
7SJ601 can be 1 A or 5 A.
The microprocessor controlled, multifunctional over
current- time protection device AEG PS 451 is
suitable for definite time or inverse-time over
current protection of HV motors, transformers, and
power lines.
Parameters may be set either from the local control
panel or through the PC interface, as desired.
PLACEMENT A ND
SET T ING OF OVER
C URR ENT RELAYS ON
ETA P