M.TECH(STRUCTURAL ENGG) CIVIL ENGG DEPT EXPERIMENTAL STUDY ON FIRE BEHAVIOUR OF STEEL MEMBERS PENETRATING CONCRETE WALLS CONTENTS INTRODUCTION TEST-SETUP CASTING OF TEST SETUP PROCEDURE TEST RESULTS SUMMARY AND DISCUSSION CONCLUSION REFERENCES INTRODUCTION There are many situations where concrete fire walls are used to divide a building into separate fire compartments. The purpose of providing such walls is to prevent the spread of
fire from one to another compartment.
The ability to prevent the fire spread is not only dependent on
the fire wall but also the penetrating members which have ability to conduct heat. Since steel is a good conductor its assumed that fire may spread
due to excessive rise in temperature in the steel member
Such practices are generally being discouraged with steel
members being stopped and supported on either side of wall.
TEST SET-UP The tests were conducted in a standard fire test furnace which internally measures 2.1 m width 1.8 m depth 2.1 m height shows an overall view of the furnace with two test specimens mounted in the side walls of the furnace. LAYOUT OF TEST SETUP CASTING TEST SPECIMEN A total of eight specimens were tested in a series of four tests, Each test having two specimens, with one specimen placed in one wall of the furnace and the other in the opposite wall. Each test specimen contained two steel plates, one with dimensions of 2 mm thick x 100 mm wide x 1200 mm long and the other having dimensions of 20 mm thick x 100 mm wide x 1200 mm long. Four specimens were cast in the horizontal position (i.e. with the steel plate vertical) . The concrete blocks for the other four specimens were cast with holes to allow grouting of the steel plates once they were located. DIFFERENT TYPES OF TEST SPECIMEN VOIDS GROUTED HORIZONTALY AND VERTICALLY DETAILS OF TEST SPECIMEN PROCEDURE The test is conducted by heating the specimen at different time. PVC cables and cardboard are used to investigate if ignition would occur. The specimen simulate the concrete wall and the steel plate simulate web or flange of Rolled section. The temperature in the furnace is raised to elevated temperature and the behavior of steel plates and the time- temperature graph is plotted. TEST RESULTS Plotted below are steel temperatures on each side of the wall whose thickness is 200mm. The plot corresponds for 60mins,120mins and 180mins. The maximum temperature rise at 25mm away from the unexposed face;
EXPOSURE DURATION TEMPERATURE
20MM PLATE 180 MINS 185°C 120MINS 140°C 60MINS 80°C 2MM PLATE 180MINS 85°C 120MINS 65°C 60MINS 45°C SUMMARY AND DISCUSSION The test results show a dramatic difference in steel temperature from fire to non-fire side. This reduction is due to the mechanism show below; It is considered that the test results are directly applicable to the roof situation being addressed. In all the tests the maximum recorded temperature at the unexposed side of the steel plate was less than 185 Celsius(after exposing for 180mins). Also the test showed regardless the specimen casted horizontally or vertically the max. temperature reached was similar. On non-exposed side of wall the steel members will only be affected locally by elevated temperature. Furthermore the temperature are such that the stiffness of the member will be hardly affected. The temperature in the furnace was not sufficient enough to cause ignition. This is because the temperature required for ignition are considerably higher than the insulation failure criteria as given in AS1530.4. Therefore we can conclude that the spread of fire will not occur. CONCLUSIONS The test results presented here illustrate the dramatic reduction in temperature from the fire to non-fire sides of steel members. The resulting temperatures of the non-fire side of the member are sufficiently low that fire spread will not occur. In the cases where the steel members has been designed to resist lateral forces required to restrain the top of the wall, lateral restraint to the wall will be maintained provided its strength exceeds the applied forces by more than 15%. If any additional loads imposed on top of wall by deforming roof members are taken into account then its not necessary for roof members to be fire protected. REFERENCES Bennetts I.D., Culton, M., and Goh, C.C., Behaviour of Steel Members When Penetrating Fire Walls, CESARE, VUT Report No. VUT/CESARE/BHP/2000/002, March 2000. Standards Australia, AS 1530.4, Methods for Fire Tests on Building Materials, Components and Structures, Part 4: Fire- resistance Tests of Elements of Building Construction, 1997. Poh, K. W., Modelling Elevated Temperature Properties of Structural Steel, BHP Research Report No. BHPR/SM/R/055, September 1996 Schwatz, K. J., and Lie, T. T., Investigating the Unexposed Surface Temperature Criteria of Standard ASTM E119, Fire Technology, 21, February 1985, pp. 169-180
HPTLC-UV Determination of Andrographolide in Andrographis Paniculata (InPharm Communique (Supplement) 2009, 2 (2), 51-54.) By: Himanshu Misra, Manish Soni, Darshana Mehta, B. K. Mehta and D. C. Jain)