The Strategy of Fire Prevention
• Pump system comprise two jockey pumps of 125 m3/hr rate, four
diesel driven pump of 1050 m3/hour & two electric pumps of 1050
m3/hour capacity.
FIRE WATER NETWORK
• The fire water network comprise the fire water hydrant line covering all areas.
• Fire water double headed hydrant with landing valve are installed to provide
water at 7 kg/cm2 pressure at the outlet.
• Fire hose box with two delivery hose, two branches are provided at each hose
box installed near each hydrant.
• Fire water hose reel are provided as a means of first aid fire fighting to control
small fire.
• Fire water line is provided with isolation valve at the hydrant & at main fire
water line.
• Two tower mounted remote controlled monitors are installed art the jetty head
on 15 m tower.
• The discharge capacity of tower monitor is 360 m3/hr at 8 kg/cm2.
• The spray type is either jet or fog with locking device with 360 degree.
• Tower monitor can be operated from the main panel in jetty control room or
from the slave panel on the jetty head lower deck.
• Four double headed hydrants with hose box and accessories are also provide
at jetty head .
• Foam system will stop after 3 minutes & need to be manually restarted
if required.
INERGEN -FIXED FLOODING SYSTEM IN
MAIN CONTROL ROOM
• Carbon dioxide gas smothers the fire, that is cut off the oxygen supply
by way of its oxygen depletion potential.
• After the fire is extinguished the doors of the concerned GTG are
opened to stimulate the escape of gas from the area.
• WATER MONITOR 04
• INERGEN SYSTEM 02
• NITROGEN SYSTEM 02
DESCRIPTION OF FIRE, GAS & SPILL
DETECTION
• The fire, gas & spill detection facility is installed on the LNG terminal
identifies 14 areas for constant monitoring .These areas are :
• Jetty head
• Trestle & unloading drain drum
• LNG TANK T101 & T102
• LNG TANK T103 & T104
• Recondenser
• LNG HP pumps
• BOG compressors
• Shell & Tube vaporizers
• Process drain drum
• Submerged combustion vaporizers
• Fuel gas heater
• Metering station
• Pig launcher & metering station
• TTLF
DESCRIPTION OF FIRE ,GAS & SPILL
DETECTION
• The area identification is displayed on the mimic panel in the main
control room. Depending upon the risk in above mentioned area,
various detection devices are located for detecting gas leak, fire, LNG
spill. For gas leak detection alarms at 20%& 60% LEL alarm comes in
the MCR. The gas detector are catalytic & will lead to emergency
shutdown via two gas detectors sensing 60% LEL voting system. The
fire detectors are of UV/IR type and any two of which in a given plant
area will automatically activate that area’s fire water deluge system.
• Manual call points are installed in the plant areas & building to
communicate fire by breaking of the glass.
FIRE ALARM & DETECTION DETAILS
• MCP/SPB 79
• PAGING SYSTEM 44
• Nearby industries have fire tender with full fledged fire fighting
team.
Monitor
Hydrant
Water spray
Foam Flooding System
CO2 Flooding System
Mercedeze Benz
FT-01 Mercedes Benz
23
Swaraj Mazda
FT-02 Swaraj Mazda
25
Portable water cum foam monitor