Anda di halaman 1dari 43

DSEMPEÑO SISMICO

DE
ELEMENTOS PRESFORZADOS

MIGUEL TORRES
Unbonded post-tensioned precast concrete frame: (a) elevation;
(b) beam-column subassemblage; (c) idealized exaggerated displaced shape
Unbonded post-tensioned precast beam-column subassemblages
(from Priestley and MacRae 1996)
interior joint behavior
exterior joint behavior
photograph of interior joint
Unbonded post-tensioned precast beam-column subassemblages.
El-Sheikh et al. 1999, 2000

(a) moment-rotation behavior (b) analytical model


Partially post-tensioned precast beam-column subassemblages
(adapted from Kurama 2002)
Beam-Column Joint Model
Model including Slab Effects
Beam-Column Joint Model Beam-Column Joint Model Including
Including Beam Growth (IBG) Beam Growth and Slab Effect (IBGS)
ESTRUCTURA PROPTOTIPO

Seismic performance of post-tensioned precast concrete beam to


column connections with supplementary energy dissipation

H.A. Spieth, D. Arnold, M. Davies, J.B. Mander, A.J.Carr


DETALLE DE CONEXION VIGA-COLUMNA Y SECUENCIA DE
CONSTRUCCION DE SISTEMA DECA RGA LATERAL
Beam-Column connection detail of lateral load and gravity load system
Experimental lateral load only subassemblage test setup (Davies (2004))
Experimental lateral and gravity load subassemblage test setup (Arnold (2004))
RUAUMOKO model of lateral load only subassembly test setup
RUAUMOKO model of lateral and gravity load subassembly test setup
System force vs. drift of subassembly lateral load only system without supplemental
energy dissipators; maximum drift 2 %; comparison of experimental results with
RUAUMOKO simulation
(a) system with bolted energy dissipators (b) system with welded energy dissipators

System force vs. drift of subassembly lateral load only system; system with
supplemental energy dissipators; maximum drift 2 %; comparison of experimental
results with RUAUMOKO simulation
(a) first cycle (b) second cycle

System force vs. drift of subassembly lateral load only system with welded
supplemental energy dissipators; maximum drift 3 %; comparison of experimental
results with RUAUMOKO simulation
System force vs. drift of subassembly lateral load and gravity load system without
supplemental energy dissipators; maximum drift 2 %; comparison of experimental
results with RUAUMOKO simulation
(a) first cycle (b) second cycle

System force vs. drift of subassembly lateral load and gravity load system without
supplemental energy dissipators; maximum drift 4 %; comparison of experimental
results with RUAUMOKO simulation
RESPUESTA HISTERETICA DE ELEMENTO HIBRIDO PT
Conditions at the wall base at yielding of PT
steel (LLP) and at crushing of confined
concrete (CCC)
Concrete compressive stress-strain
PT steel stress-strain relationship considered in the fullscale
prototype wall (adapted from Kurama et al. 1997).
VISTA DEL PROYECTO
SISTEMA ESTRUCTURAL
MECANISMO DE ESTUDIO
Forces on an unbonded post-tensioned precast wall with
N replaced by equivalent force and moment
Wall limit states.
Prestress loss due to inelastic response
(adapted from Priestley and Tao 1993).
(used to derive Vdec)

Stress condition at the wall base at


decompression
Strain and stress conditions at the wall base at
effective linear limit due to concrete softening
(used to derive V ). ell-1
Stress conditions at the wall base at linear limit
due to gap opening (used to derive V ELL-2).
NUCLEO DE LA SECCION
DEL MURO PT
PORTICO RESISTENTE A MOMENTO PT
DETALLES DE ANCLAJE DEL PORTICO PT
Gracias

Anda mungkin juga menyukai