Anda di halaman 1dari 68

Perhitungan pencahayaan

gedung pascasarjana lt.2

Oleh:
1. Aidil Akbar 1303181002
2. Andrean Rangga Kusuma 1303181022
3. Roicha Dwi Hastuti 1303181026
4. Septian Fredy Pamungkas 1303181027
TOILET PRIA TOILET TANGGA
WANITA DARURAT
1.02

RUANG DIREKTUR

2.99

4.01
R.WAKIL
DIREKTUR
1

2.70

8.02
RUANG RAPAT 1

R.WAKIL
DIREKTUR
2

2.70 4.01
KETERANGAN
SIMBOL
R.WAKIL
DIREKTUR
3
LOBBY NAMA GAMBAR JUMLAH

2.70
LAMPU
LED
158
21.52 3.46
R. SEKRETARIS DIREKSI
LAMPU
1.25
TL 143
RUANG
RAPAT 2 6.47
LANTAI 1
SAKLAR
26
LIFT 1

GANDA
2.70 TANGGA
KANTOR 1
2.97 SAKLAR
LIFT 2

TUNGGAL 8
KANTOR 3
PINTU
TANGGA DARURAT
1 27
3.00 1.99
PINTU
PERPUSTAKAAN

2 3
KOTAK
GUDANG

KANTOR 2
6.00 KONTAK 20
LIFT 5

LIFT 4 LIFT 3
4.01 FASA
3.48
LINE
TOILET WANITA
TANGGA DARURAT
TOILET PRIA

1.00
NETRAL
GUDANG 1
TOILET
WANITA TOILET PRIA LINE

3.00 1.10 1.00 1.00 1.00 3.00 10.50 2.98 GROUND


LINE

23.57
TEMBOK

KETERANGAN

DENAH LANTAI 2 A3
POLITEKNIK ELEKTRONIKA SKALA 1 : 234 DSTJ :
NEGERI SURABAYA DGBR : DPRS : 1 D3 T ELEKTRO INDUSTRI A
KATALOG

SELESAI
GAMBAR
GAMBAR
GAMBAR
Toilet pria - Luas = 15.21m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(250*15.21)/(0.9*0.8)
5281.25
1
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
2.77 5281.25/(1200*1) = 4.40
- N lampu = Narmatur x n
4.40*1 = 4.40
FOTO
- Watt lampu = 18
Hanya digunakan 3 lampu
Jenis lampu : Master Pl-c /4p-840 - W total = 18*3 = 54 watt
Toilet pria - Luas = 15.21m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(250*15.21)/(0.9*0.8)
5281.25
1
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
2.77 5281.25/(1200*1) = 4.40
- N lampu = Narmatur x n
4.40*1 = 4.40
FOTO
- Watt lampu = 18
Hanya digunakan 3 lampu
Jenis lampu : Master Pl-c /4p-840 - W total = 18*3 = 54 watt
Toilet Wanita

LAMPU 1

LAMPU 2

1.28 FOTO

0.85 LAMPU 1 LAMPU 2


Toilet Wanita
- Luas = 6m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(250*6)/(0.9*0.8)
2083.3
1.28 - F1 lumen = 850
- n =1
- N total =Ftotal/(Flumen*n)
2083.3/(850*1) = 2.45
- N lampu = Narmatur x n
2.45*1 = 2.45
- Watt lampu = 13
0.85 Hanya digunakan 2 lampu
Jenis lampu : Master Pl-c /4p-840 - W total = 13*2 = 26 watt
Toilet Wanita
- Luas = 6m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd) – F lampu 2
(250*6)/(0.9*0.8) - 1700
383.3
1.28
- F1 lumen = 470
- n =1
- N total =Ftotal/(Flumen*n)
383.3/(470*1) = 0.82
- N lampu = Narmatur x n
0.82*1 = 0.82
- Watt lampu =8
0.85
Hanya digunakan 1 lampu
Jenis lampu : Master TL Mini Super 80
- W total = 8*1 = 8 watt
Tempat Wudhu
- Luas = 7.72m^2
- E = 150
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(150*7.72)/(0.9*0.8)
1608.75
1.28 - F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
1608.75/(1200*1) = 1.34
- N lampu = Narmatur x n
1.34*1 = 1.34
1 - Watt lampu = 18
Hanya digunakan 1 lampu
Jenis lampu : Master Pl-c /4p-840
- W total = 18*1 = 18 watt
Lorong depan toilet
- Luas = 8.70m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*8.70)/(0.9*0.8)
1208.33
- F1 lumen = 1200
1.28
- n =1
- N total =Ftotal/(Flumen*n)
1208.33/(1200*1) = 1.01
- N lampu = Narmatur x n
1.01*1 = 1.01
1.1 - Watt lampu = 18
Hanya digunakan 1 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 18*1 = 18 watt
Lorong belakang perpustakaan
- Luas = 45.41m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*45.41)/(0.9*0.8)
6306.94
3.1
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
6306.94/(1200*1) = 5.26
- N lampu = Narmatur x n
3,2
5.26*1 = 5.26
FOTO
- Watt lampu = 18
Hanya digunakan 1 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 18*5 = 90 watt
Koridor belakang perpustakaan
- Luas = 45.41m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*45.41)/(0.9*0.8)
6306.94
3.1
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
6306.94/(1200*1) = 5.26
- N lampu = Narmatur x n
3.54
5.26*1 = 5.26
FOTO - Watt lampu = 18
Hanya digunakan 5 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 18*5 = 90 watt
Tangga darurat
- Luas = 49m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*49)/(0.9*0.8)
2 6805.56
- F1 lumen = 2400
- n =2
- N total =Ftotal/(Flumen*n)
6805.56/(2400*2) = 1.42
- N lampu = Narmatur x n
3
1.42*2 = 2.84
- Watt lampu = 30
Hanya digunakan 2 lampu
Jenis lampu : Master Tl-D super 80 g13
- W total = 30*2 = 60 watt
Perpustakaan

LAMPU 1

LAMPU 2

5 FOTO

10.5
Perpustakaan

LAMPU 1

5
LAMPU 2

FOTO

10.5
Perpustakaan
- Luas = 122.5m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*122.5)/(0.9*0.8)
51041.67
5
- F1 lumen = 1400
- n =5
- N total =Ftotal/(Flumen*n)
51041.67/(1400*2) = 7.29
- N lampu = Narmatur x n
10.5 7.29*5 = 36.5
- Watt lampu = 16
Hanya digunakan 25 lampu
Jenis lampu : Master Tl-d HF super 80
G13 - W total = 16*25 = 400 watt
Perpustakaan
- Luas = 122.5m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd) – F lampu 25
(300*122.5)/(0.9*0.8) - 35000
16041.67
5- F1 lumen = 321.28
- n =1
- N total =Ftotal/(Flumen*n)
16041.67/(321.28*1) = 49.97
- N lampu = Narmatur x n
14.30*3 = 49.97
10.5
- Watt lampu =7
Hanya digunakan 50 lampu
Jenis lampu : Master Led Spot LV 12V
- W total = 7*50 = 350 watt
Koridor samping perpustakaan
- Luas = 44 m^2
1
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
10.5 (100*44)/(0.9*0.8)
6111.11
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
6111.11/(1200*1) = 5.09
- N lampu = Narmatur x n
5.09*1 = 5.09
- Watt lampu = 18
Hanya digunakan 6 lampu
Jenis lampu : Master PL-C /4P-840
- W total = 18*6 = 108 watt
Koridor samping perpustakaan
- Luas = 44 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*44)/(0.9*0.8)
6111.11
1- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
10.5 6111.11/(1200*1) = 5.09
- N lampu = Narmatur x n
5.09*1 = 5.09
FOTO
- Watt lampu = 18
Hanya digunakan 6 lampu
Jenis lampu : Master PL-C /4P-840
- W total = 18*6 = 108 watt
Ruang penelitian dosen
- Luas = 49m^2
- E = 350
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(350*49)/(0.9*0.8)
23819.44
3 - F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
23819.44/(2625*2) = 4.54
- N lampu = Narmatur x n
4.54*2 = 9.1
- Watt lampu = 28
3 Hanya digunakan 8 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*8 = 224 watt
Koridor depan perpustakaan

LAMPU 1

LAMPU 2

3
FOTO

7
Koridor depan perpustakaan

3 LAMPU 1

LAMPU 2

7 FOTO
Koridor depan perpustakaan
- Luas = 143.50 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*1143.50)/(0.9*0.8)
19930.56
3
- F1 lumen = 1750
- n =1
- N total =Ftotal/(Flumen*n)
19930.56/(1750*1) = 11.39
7 - N lampu = Narmatur x n
11.39*1 = 11.39
- Watt lampu = 24
Hanya digunakan 3 lampu
Jenis lampu : Master TL-5 HO G-5
- W total = 24*3 = 72 watt
Koridor depan perpustakaan
- Luas = 143.50 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd) – lampu TL
(100*1143.50)/(0.9*0.8) - 5250
14680.56
-3 F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
14680.56/(1200*1) = 12.23
- N lampu = Narmatur x n
7 12.23*1 = 12.23
- Watt lampu = 18
Hanya digunakan 12 lampu
Jenis lampu : Master PL-T /4P-840
- W total = 18*12 = 216 watt
Lorong depan toilet
- Luas = 6.75m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
0.4 (100*6.75)/(0.9*0.8)
937.50
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
3 937.50/(850*1) = 1.10
- N lampu = Narmatur x n
1.10*1 = 1.10
FOTO - Watt lampu = 13
Hanya digunakan 1 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 13*1 = 13 watt
Lorong depan toilet
- Luas = 6.75m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*6.75)/(0.9*0.8)
937.50
0.4 - F1 lumen = 850
- n =1
- N total =Ftotal/(Flumen*n)
937.50/(850*1) = 1.10
- N lampu = Narmatur x n
3 1.10*1 = 1.10
FOTO - Watt lampu = 13
Hanya digunakan 1 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 13*1 = 13 watt
Toilet laki-laki 2
- Luas = 7.02m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(250*7.02)/(0.9*0.8)
2437.50
1.2 - F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
2437.50/(1200*1) = 2.03
- N lampu = Narmatur x n
2.03*1 = 2.03
- Watt lampu = 18
1
Hanya digunakan 2 lampu
Jenis lampu : Master Pl-C /4p-840
- W total = 18*2 = 36 watt
Toilet perempuan 2

LAMPU 1

LAMPUSlide
34 2

FOTO
1

1
Toilet perempuan 2
- Luas = 5.48m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd) – lampu LED
(250*6)/(0.9*0.8)-1700
202.78
- F1 lumen = 470
- n =1
1
- N total =Ftotal/(Flumen*n)
202.78/(470*1) = 0.43
- N lampu = Narmatur x n
0.43*1 = 0.43
- Watt lampu =8
Hanya digunakan 1 lampu
Jenis lampu : Master
1 TL Mini Super 80 - W total = 8*1 = 8 watt
Toilet perempuan 2
- Luas = 5.48m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd) – lampu LED
(250*6)/(0.9*0.8)-1700
202.78
- F1 lumen = 470
1- n =1
- N total =Ftotal/(Flumen*n)
202.78/(470*1) = 0.43
- N lampu = Narmatur x n
0.43*1 = 0.43
- Watt lampu =8
Hanya digunakan 1 lampu
1
Jenis lampu : Master TL Mini Super 80 - W total = 8*1 = 8 watt
Toilet perempuan 2
- Luas = 5.48m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(250*5.48)/(0.9*0.8)
1902.78
- F1 lumen = 850

1 - n =1
- N total =Ftotal/(Flumen*n)
1902.78/(850*1) = 2.2
- N lampu = Narmatur x n
2.2*1 = 2.2
- Watt lampu = 13
Hanya digunakan 2 lampu
1
Jenis lampu : Master Pl-C /4p-840 - W total = 13*2 = 26 watt
Koridor depan gudang
- Luas = 25.81 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*25.81)/(0.9*0.8)
3.4 3584.75
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
3584.75/(1200*1) = 2.99
- N lampu = Narmatur x n
1
2.99*1 = 2.99
- Watt lampu = 18
Hanya digunakan 3 lampu
Jenis lampu : Master PL-T /4P-840
- W total = 18*3 = 54 watt
Koridor depan gudang
- Luas = 25.81 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*25.81)/(0.9*0.8)
3.4 3584.75
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
3584.75/(1200*1) = 2.99
- N lampu = Narmatur x n
1
2.99*1 = 2.99
FOTO - Watt lampu = 18
Hanya digunakan 3 lampu
Jenis lampu : Master PL-T /4P-840
- W total = 18*3 = 54 watt
Gudang 1
- Luas = 5.48m^2
- E = 250
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(250*5.48)/(0.9*0.8)
1901.25
1 - F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
1901.25/(1200*1) = 1.58
- N lampu = Narmatur x n
1.58*1 = 1.58
1 - Watt lampu = 18
Hanya digunakan 1 lampu
Jenis lampu : Master Pl-C /4p-840
- W total = 18*1 = 18 watt
Tangga darurat
- Luas = 16.38m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*16.38)/(0.9*0.8)
2275
1 - F1 lumen = 2400
- n =1
- N total =Ftotal/(Flumen*n)
2275/(2400*1) = 0.95
3
- N lampu = Narmatur x n
0.95*1 = 0.95
- Watt lampu = 30
Hanya digunakan 1 lampu
Jenis lampu : Master Tl-D super 80 g13
- W total = 30*1 = 30 watt
Gudang
- Luas = 36m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*36)/(0.9*0.8)
15000
2.56 - F1 lumen = 1925
- n =2
- N total =Ftotal/(Flumen*n)
15000/(1925*1) = 3.90
- N lampu = Narmatur x n
3.98*2 = 7.96
2.56 - Watt lampu = 21
Hanya digunakan 8 lampu
Jenis lampu : Master Tl-D super 80 g13
- W total = 21*8 = 168 watt
Ruang dosen
- Luas = 49m^2
- E = 350
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(350*49)/(0.9*0.8)
23819.44
3 - F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
23819.44/(2625*2) = 4.54
- N lampu = Narmatur x n
4.54*2 = 9.1
- Watt lampu = 28
3
Hanya digunakan 8 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*8 = 1792 watt
Tangga
- Luas = 3.08m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*3.08)/(0.9*0.8)
0.4
427.78
- F1 lumen = 930
- n =1
- N total =Ftotal/(Flumen*n)
1 42.78/(930*1) = 0.46
- N lampu = Narmatur x n
0.46*1 = 0.46
- Watt lampu = 12
Hanya digunakan 1 lampu
Jenis lampu : TL mini G-5
- W total = 12*1 = 12 Watt
Koridor depan lift
- Luas = 21.20 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*21.20/(0.9*0.8)
2944.44
3 - F1 lumen = 930
- n =1
- N total =Ftotal/(Flumen*n)
2944.44/(930*1) = 3.17
- N lampu = Narmatur x n
3.17*1 = 3.17
3 - Watt lampu = 24
Hanya digunakan 3 lampu
Jenis lampu : Master TL HO G-5
- W total = 24*3= 72 watt
Koridor depan lift
- Luas = 21.20 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*21.20/(0.9*0.8)
2944.44
3 - F1 lumen = 930
- n =1
- N total =Ftotal/(Flumen*n)
2944.44/(930*1) = 3.17
- N lampu = Narmatur x n
3.17*1 = 3.17
3 - Watt lampu = 24
Hanya digunakan 3 lampu
Jenis lampu : Master TL HO G-5
- W total = 24*3= 72 watt
Lobby ruang direktur

LAMPU 1

LAMPU 2

FOTO
Lobby ruang direktur

3.7

7.1
Lobby ruang direktur
- Luas = 140 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
3.7 (100*140/(0.9*0.8)
19444.44
- F1 lumen = 930
- n =1
- N total =Ftotal/(Flumen*n)
19444.44/(930*1) = 20.9
7.1 - N lampu = Narmatur x n
20.9*1 = 20.9
- Watt lampu = 12
Hanya digunakan 11 lampu
Jenis lampu :TL Mini G-5
- W total = 12*11= 121 watt
Lobby ruang direktur
- Luas = 140 m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd) – Lampu TL
(100*140/(0.9*0.8) - 11160
3.7
8284.44
- F1 lumen = 1200
- n =1
- N total =Ftotal/(Flumen*n)
8284.44/(1200*1) = 6.90
- N lampu = Narmatur x n
7.1
6.90*1 = 6.90
- Watt lampu = 18
Hanya digunakan 8 lampu
Jenis lampu :Maaster PL-C /2P
- W total = 18*8= 144 watt
Lorong ruang direktur
- Luas = 87m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*87)/(0.9*0.8)
12083.33
- F1 lumen = 850
7.1 - n =1
- N total =Ftotal/(Flumen*n)
12083.33/(850*1) = 14.22
- N lampu = Narmatur x n
14.22*1 = 14.22
- Watt lampu = 18
Hanya digunakan 15 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 18*15 = 270 watt
0.4
Lorong ruang direktur
- Luas = 87m^2
- E = 100
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(100*87)/(0.9*0.8)
12083.33
- F1 lumen = 850
7.1 - n =1
- N total =Ftotal/(Flumen*n)
12083.33/(850*1) = 14.22
- N lampu = Narmatur x n
14.22*1 = 14.22
FOTO
- Watt lampu = 18
0.4 Hanya digunakan 15 lampu
Jenis lampu : Master Pl-T /4p-840
- W total = 18*15 = 270 watt
Ruang pengarsipan (sekretaris direksi)
- Luas = 19.60m^2
- E = 300
3
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*19.60)/(0.9*0.8)

1.25 8166.67
- F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
23819.44/(2625*2) = 1.56
- N lampu = Narmatur x n
1.56*2 = 3.1
- Watt lampu = 28
Hanya digunakan 4 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*4 = 112 watt
Ruang wakil direktur
- Luas = 45.50m^2
- E = 350
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(350*45.50)/(0.9*0.8)
22118.08
2.7
- F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
22118.08/(2625*2) = 4.21
- N lampu = Narmatur x n
4.21*2 = 8.4
3
- Watt lampu = 28
Hanya digunakan 8 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*8 = 224 watt
Ruang wakil direktur
- Luas = 45.50m^2
- E = 350
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(350*45.50)/(0.9*0.8)
22118.08
2.7
- F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
22118.08/(2625*2) = 4.21
- N lampu = Narmatur x n
4.21*2 = 8.4
3
- Watt lampu = 28
FOTO
Hanya digunakan 8 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*8 = 224 watt
Ruang wakil direktur 2
- Luas = 45.50m^2
- E = 350
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(350*45.50)/(0.9*0.8)
22118.08
2.7
- F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
22118.08/(2625*2) = 4.21
- N lampu = Narmatur x n
4.21*2 = 8.4
- Watt lampu = 28
3
Hanya digunakan 8 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*8 = 224 watt
Ruang wakil direktur 3
- Luas = 45.50m^2
- E = 350
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(350*45.50)/(0.9*0.8)
22118.08
2.7
- F1 lumen = 2625
- n =2
- N total =Ftotal/(Flumen*n)
22118.08/(2625*2) = 4.21
- N lampu = Narmatur x n
4.21*2 = 8.4
- Watt lampu = 28
3 Hanya digunakan 8 lampu
Jenis lampu : Master TL5 HE G5-840
- W total = 28*8 = 224 watt
Ruang Direktur
- Luas = 65.80m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*65.80)/(0.9*0.8)
27416.67
4.01 - F1 lumen = 3200
- n =2
- N total =Ftotal/(Flumen*n)
27416.67/(3200*2) = 4.28
- N lampu = Narmatur x n
4.28*2 = 8.56
3.01 - Watt lampu = 32
FOTO
Hanya digunakan 8 lampu
Jenis lampu : Master TL-D HF Super 80
G13 - W total = 32*8 = 256 watt
Ruang Direktur
- Luas = 65.80m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*65.80)/(0.9*0.8)
27416.67
4.01 - F1 lumen = 3200
- n =2
- N total =Ftotal/(Flumen*n)
27416.67/(3200*2) = 4.28
- N lampu = Narmatur x n
4.28*2 = 8.56
3.01 - Watt lampu = 32
FOTO
Hanya digunakan 8 lampu
Jenis lampu : Master TL-D HF Super 80
G13 - W total = 32*8 = 256 watt
Ruang rapat
- Luas = 65.80m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*65.80)/(0.9*0.8)
27416.67
4.01 - F1 lumen = 3200
- n =2
- N total =Ftotal/(Flumen*n)
27416.67/(3200*2) = 4.28
- N lampu = Narmatur x n
4.28*2 = 8.56
- Watt lampu = 32
3.01
Hanya digunakan 8 lampu
Jenis lampu : Master TL-D HF Super 80
G13 - W total = 32*8 = 256 watt
Ruang rapat
- Luas = 65.80m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*65.80)/(0.9*0.8)
27416.67
4.01 - F1 lumen = 3200
- n =2
- N total =Ftotal/(Flumen*n)
27416.67/(3200*2) = 4.28
- N lampu = Narmatur x n
4.28*2 = 8.56
- Watt lampu = 32
3.01 Hanya digunakan 8 lampu
Jenis lampu : Master TL-D HF Super 80
G13 - W total = 32*8 = 256 watt
Ruang rapat kecil
- Luas = 18.72m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*18.72)/(0.9*0.8)
7800
- F1 lumen = 2400
3.46
- n =1
- N total =Ftotal/(Flumen*n)
7800/(2400*1) = 3.25
- N lampu = Narmatur x n
3.25*1 = 3.25
- Watt lampu = 28
1.20
Hanya digunakan 4 lampu
Jenis lampu : Master TL-D Super 80 G13
- W total = 28*4 = 112 watt
Ruang kantor 1
- Luas = 73.50m^2
- E = 300
- Kp; kd = 0.9; 0.8
- F total =(EA/kp.kd)
(300*73.50)/(0.9*0.8)
30625
- F1 lumen = 3200
3.46
- n =2
- N total =Ftotal/(Flumen*n)
30625/(32*1) = 4.79
- N lampu = Narmatur x n
120 4.79*2 = 9.58
- Watt lampu = 32
Hanya digunakan 4 lampu
Jenis lampu : Master TL-D HF Super 80
G13 - W total = 32*8 = 256 watt
2. . Sketsa gambar instalasi listrik gedung pasca lantai 2
3. Lampiran
Keterangan pemakaian lampu

no. nama ruangan Kp Kd A(m2) E F F1 N Nlam W1 Wtotal Merk Lampu


ruang total=(E (LUME total=Ftotal/ pu = (Watt) =
A/kp.kd) N n (Flumen*n) Narm Nlamp
atur x ux
n W1
1 toilet laki laki 1 0.9 0.8 15.21 250 5281.25 1200 1 4.40 3 18 54 MASTER PL-C /4P-840
2 toilet permpuan 1 0.9 0.8 6.00 250 2083.33 850 2 1.23 2 13 26 MASTER PL-C /4P-840
0.9 0.8 6.00 250 383.33 470 1 0.82 1 8 8 MASTER TL Mini Super 80
3 lorong depan toilet 0.9 0.8 8.70 100 1208.33 1200 1 1.01 1 18 18 MASTER PL-T /4P-840
4 tempat wudhu 0.9 0.8 7.72 150 1608.33 1200 1 1.34 1 18 18 MASTER PL-C /4P-840
5 koridor belakang perpustakaan 0.9 0.8 45.41 100 6306.94 1200 1 5.26 5 18 90 MASTER PL-T /4P-840
6 tangga darurat 1 0.9 0.8 49.00 100 6805.56 2400 2 1.42 2 30 60 MASTER TL-D Super 80 G13
7 perpustakaan 0.9 0.8 122.50 300 51041.67 1400 5 7.29 25 16 400 MASTER TL-D HF Super 80 G13
0.9 0.8 122.50 300 16041.67 321 1 49.93 50 7 350 Master Led Spot LV 12V
8 koridor samping perpustakaan 0.9 0.8 44.00 100 6111.11 1200 1 5.09 6 18 108 MASTER PL-C /4P-840
9 ruang penelitian dosen 0.9 0.8 49.00 350 23819.44 2625 2 4.54 8 28 224 MASTER TL5 HE G5-840
10 depan perpustakaan 0.9 0.8 143.50 100 19930.56 1750 1 11.39 3 24 72 MASTER TL5 HO G5
0.9 0.8 143.50 100 14680.56 1200 1 12.23 12 18 216 MASTER PL-T /4P-840
no. nama ruangan Kp Kd A(m2) E F F1 N Nlam W1 Wtotal Merk Lampu
ruang total=(E (LUME total=Ftotal/ pu = (Watt) =
A/kp.kd) N n (Flumen*n) Narm Nlamp
atur x ux
n W1
11 lift 3-4
12 lorong depan toilet 0.9 0.8 6.75 100 937.50 850 1 1.10 1 13 13 MASTER PL-T /4P-840
13 toilet laki laki 2 0.9 0.8 7.02 250 2437.50 1200 1 2.03 2 18 37 MASTER PL-C /4P-840
14 toilet perempuan 2 0.9 0.8 5.48 250 1902.78 850 1 2.24 2 13 26 MASTER PL-C /4P-840
0.9 0.8 5.48 250 202.78 470 1 0.43 1 8 8 MASTER TL Mini Super 80
15 gudang 1 0.9 0.8 5.48 250 1902.78 1200 1 1.59 1 18 18 MASTER PL-C /4P-840
16 tangga darurat 0.9 0.8 16.38 100 2275.00 2400 1 0.95 1 30 30 MASTER TL-D Super 80 G13
17 gudang 0.9 0.8 36.00 300 15000.00 1925 2 3.90 8 21 168 MASTER TL5 HE G5
18 lift 5
19 koridor depan gudang 0.9 0.8 25.81 100 3584.75 1200 1 2.99 3 18 54 MASTER PL-T /4P-840
20 ruang dosen 0.9 0.8 49.00 350 23819.44 2625 2 4.54 8 28 224 MASTER TL5 HE G5-840
21 tangga 0.9 0.8 3.08 100 427.78 930 1 0.46 1 12 12 TL Mini G5
22 koridor didepan lift 1-2 0.9 0.8 21.20 100 2944.44 930 1 3.17 3 24 72 Master TL HO G-5
23 lift 1-2
24 lobby ruang direktur 0.9 0.8 140.00 100 19444.44 930 1 20.91 11 24 264 TL Mini G5
0.9 0.8 140.00 100 9214.44 1200 1 7.68 8 18 144 MASTER PL-C /2P
no. nama ruangan Kp Kd A(m2) E F F1 N Nlam W1 Wtotal Merk Lampu
ruang total=(E (LUME total=Ftotal/ pu = (Watt) =
A/kp.kd) N n (Flumen*n) Narm Nlamp
atur x ux
n W1
25 lorong ruang direktur 0.9 0.8 87.00 100 12083.33 850 1 14.22 15 18 270 MASTER PL-T /4P-840
26 ruang sekretaris direksi 0.9 0.8 19.60 300 8166.67 2625 2 1.56 4 28 112 MASTER TL5 HE G5-840
27 ruang wakil direktur 0.9 0.8 45.50 350 22118.06 2625 2 4.21 8 28 224 MASTER TL5 HE G5-840
28 ruang wakil direktur 2 0.9 0.8 45.50 350 22118.06 2625 2 4.21 8 28 224 MASTER TL5 HE G5-840
29 ruang wakil direktur 3 0.9 0.8 45.50 350 22118.06 2625 2 4.21 8 28 224 MASTER TL5 HE G5-840
30 ruang direktur 0.9 0.8 65.80 300 27416.67 3200 2 4.28 8 32 256 MASTER TL-D HF Super 80 G13
32 ruang rapat 3 0.9 0.8 73.50 300 30625.00 3200 2 4.79 8 32 256 MASTER TL-D HF Super 80 G13
33 ruang rapat kecil 0.9 0.8 18.72 300 7800.00 2400 1 3.25 4 28 112 MASTER TL-D Super 80 G13
34 lorong toilet 3 0.9 0.8 4.70 100 652.78 850 1 0.77 1 13 13 MASTER PL-T /4P-840
35 toilet laki laki 3 0.9 0.8 16.38 250 5687.50 1200 1 4.74 3 18 54 MASTER PL-C /4P-840
36 toilet perempuan 3 0.9 0.8 13.57 250 4711.81 850 1 5.54 4 18 72 MASTER PL-C /4P-840
0.9 0.8 13.57 250 1311.81 470 1 2.79 2 8 16 MASTER TL Mini Super 80
37 tangga darurat 3 0.9 0.8 13.57 100 1884.72 2450 1 0.77 1 30 30 MASTER TL-D Super 80 G13
product description volt (v) watt cap color temp lumen (lm) CRI (ra)
(k)
MASTER PL-C /4P-840 240 18 G24q-2 2700 1200 82
MASTER TL Mini Super 80 240 8 G5 4000 1000 85
MASTER PL-T /4P-840 240 18 GX24Q-3 4000 1800 82
MASTER TL-D Super 80 G13 240 30 G13 3000 5240 85
MASTER TL-D HF Super 80 G13 240 16 G13 4000 5200 85
MASTER LEDspotLV AR111 12V G53 240 15 1CT / 6 4000 374 85
MASTER TL5 HE G5-840 240 28 G5 4000 2600 85
MASTER PL-T /4P-840 240 18 GX24q-2 4000 1200 82
MASTER TL5 HE G5 240 28 1SL / 40 4000 2625 85
TL Mini G5 240 12 1FM / 10X25CC 4100 930 60
MASTER TL5 HO G5 240 24 1SL / 40 4000 1750 85
MASTER PL-C /2P 240 18 G24d-2 4000 1200 82
MASTER PL-T /4P-840 240 18 G24q-2 4000 850 82
MASTER TL-D HF Super 80 G13 240 32 1SL / 25 4000 3200 85
MASTER TL5 HE G5-840 240 28 1SL / 40 4000 2400 85
MASTER PL-T /4P-840 240 13 GX24q-1 4000 850 82
MASTER PL-C /4P-840 240 18 G24q-2 4000 1200 82
MASTER TL Mini Super 80 240 8 1FM / 10X25CC 4000 470 85
MASTER TL-D Super 80 G13 240 30 1SL / 25 3000 2450 85

- terimakasih