Dounreay
Thurso
Mybster
REINFORCED NETWORK
Stornoway Cassley
Dunbeath
400kV Substations
Lairg
THE SHETLAND ISLANDS
275kV Substations
Brora
400kV CIRCUITS
Shin
275kV CIRCUITS
Tummel
Errochty Errochty Power Station
Clunie
Lunanhead
Fiddes
Lyndhurst
TRANSMISSION
Inveraray
7.5GW nuclear
Glenrothes
Sloy Leven
Devonside Westfield
Redhouse
Dunoon
Spango Devol
Helensburgh
Strath leven
Bonnybridge
Grangemouth
Iverkeithing
Erskine Cumbernauld Bathgate Whitehouse
Inverkip Lambhill
Easterhouse
Livingston Kaim es
Currie
Newarthill
Clydes
Neilston Mill
Hunterston
Berwick
Farm
Series Capacitors
Wishaw
Hun terston Busby Strathaven Blacklaw
Kil winning Whitelee East
Kilmarnock Kilbride
Salt coats Town Linmill
South
Eccle s
Carradale Meadowhead Galashiels
Kilmarnock
Coalburn
South
Ayr SP TRANSMISSION LTD.
Coylt on
Elvanfoot H awic k
Maybole
Blyth
Fourstones
Newton
Stewart
Tynemouth
Chapelcross Harker South Shields
Stella
Lackenby
Heysham Quernmore
Poppleton Osbaldwick
Thornton
Bradford
Stanah West Kirkstall
Skelton Creyke Beck
Padiham Grange Mo nk
Fryston Saltend North
Saltend South
Penworth am
Pentir
Dinorwig
Capenhurst
Deeside
Ferry
Frodsham
Macclesfield
Jordanthorpe
Chesterfield
Brinsworth
Norton Lees
High
Marnham
Cottam
Staythorpe
Legacy
Ffestiniog
Trawsfynydd
Willi ngton
Ratcliffe
Bicke r
Fenn
Drakelow Walpole
Rugeley Spalding
North
Penn
Bushbury
Willenhall Bustleholm
Nechells
Hams
Hall
Enderby
Norwich
Main
Ocker
Hill Coventry
Oldbury
Kitwell Berkswell
Sizewell
Burwell
Feckenham Main
Bishops Grendon Eaton
Wood Socon
Patford Bramford
Bridge
East
Hinkley Point
Sellindge
Bridgwater
Alverdiscott
Bolney
Taunton Nursling E de F
Ninfield
Dungeness
Marchwood Lovedean
Axminster
Mannington Fawley Botley Wood
Exeter
Chickerell
Langage Abham
Landulph
Indian
Que ens
ISSUE B 12-02-09 41/177619 C Collins Bartholomew Ltd 1999
Test Network
25GW demand
11 generators
No Load Response
F = 49.19 Hz
Full H – Three Machines selected for FR to achieve 49.19 Hz (approx 49.2Hz) - Red
25GW demand
11 generators
H/2 – Two Machines selected for FR as in Base Case – Minimum Frequency 49.124Hz
1320MW Loss – Effect of Inertia and Frequency
Response with Load Response
H/2 – Two Machines selected for FR as in Base Case – Minimum Frequency 49.124Hz - Green
25GW demand
15 generators
Full H, 6 Machines providing Frequency Response, 480 MW of load reduction at 4 seconds f = 49.203Hz
Full H, 3 Machines Providing Frequency Response (in 1320 MW case frequency above 49.2Hz)
Since the Control Systems would rely on a df/dt control, which is a noise amplifying
process some consideration will need to be given to adequate filtering
In order to reduce complexity and following discussions with manufacturers it is
suggested that such a facility would only be applicable to plant in Limited Frequency
Sensitive Mode of operation.
The ability of Generators to recover following contribution to System Inertia needs to be
examined in more detail.
To minimise wear on the generator, it is suggested a dead band is introduced to the df/dt
term.
A static dead band value still requires evaluation but a value in the range of 0.003 Hz/s
is thought to be adequate based on the current experience – see attached slide
Deadband
High Level Proposals (1)
In order to limit the rate of change of frequency following a generation loss or load loss,
each Generating Unit, Power Park Module or DC Converter shall be required to
contribute towards System Inertia.
For Generating Units, DC Converters and Power Park Modules (including Power Park
Units thereof) which do not inherently have a capability to provide inertia to the
Transmission System, then each Generating Unit, DC Converter and Power Park Module
shall be fitted with a Control System to contribute towards system inertia.
Any such Control System should aim to control df/dt in order to reduce the rate of change
of active power and hence rate of change of system frequency. Such a Control System
would need to reflect and maximise the synthetic value of the Inertia Constant H.
High Level Proposals (2)
In addition, the Inertial Control System fitted to each Generating Unit, Power Park Module
and DC Converter shall:-
operate whenever the Generating Unit, DC Converter and Power Park Module (including
the Power Park Unit thereof) is selected to Limited Frequency Sensitive Mode of
operation.
have an adjustable dead band of between 0.001 Hz/s – 0.01Hz /s. The initial dead band
shall be set to 0.003 Hz/s
Include elements to limit the bandwidth of the output signal. The bandwidth limiting must
be consistent with the speed of response requirements and ensure that the highest
frequency of response cannot excite torsional oscillations on other plant connected to the
network. A bandwidth of 0-5Hz would be judged acceptable for this application. All other
control systems employed within the Generating Unit, Power Park Module (including the
Power Park Unit thereof) and DC Converter should also meet this requirement.
For the avoidance of doubt there is no requirement for the Inertial Control System to be
active when the Generating Unit, Power Park Module (including the Power Park Unit
thereof) or DC Converter is operating in Frequency Sensitive Mode.
Conclusions
Machine inertia significantly affects the rate of change of System Frequency
In a System containing dynamic frequency response, a low system inertia will result in a
lower minimum system frequency
There needs to be co-ordination between requirements for inertia, delivery of primary
response and delivery of secondary response – is 10% P, 10% S and 10% H still
adequate especially in an 1800MW scenario
It would be significantly more expensive to allow system inertia to be eroded (as new
Generation Technologies are introduced) and hold more fast acting response than
mandating the need for a control system to contribute towards system inertia.
The cost of fitting an inertial control is believed to be insignificant in comparison with
holding additional response.
Requirements for an inertial control need to reflect issues such as control system
dynamics, dead band and complexity
Some additional study work is required in respect of exact control system performance.
The Control System would only be required to be active when the Generator is operating
in Limited Frequency Sensitive Mode of operation.
National Grid has already started discussion with several turbine manufacturers to
determine settings.
References / Further Information
Contribution of Wind Energy Converters with Inertia Emulation to frequency control and
frequency stability in Power Systems – Stephan Wachtel and Alfred Beekmann –
Enercon – Presented at the 8th International Workshop on Large Scale Integration of
Wind Power into Power Systems as well as on Offshore Wind Farms, Bremen Germany,
14 – 15 October 2009.
Variable Speed Wind Turbines Capability for Temporary Over-Production – German
Claudio Tarnowski, Philip Carne Kjaer, Poul E Sorensen and Jacob Ostergaard
Study on Variable Speed Wind Turbine Capability for Frequency Response - German
Claudio Tarnowski, Philip Carne Kjaer, Poul E Sorensen and Jacob Ostergaard
GE Energy – WindINERTIATM Control fact sheet – Available on GE Website at :- http://www.ge-
energy.com/businesses/ge_wind_energy/en/downloads/GEA17210.pdf
Transmission Provider Technical Requirements for the Connection of Power Plants to the
Hydro-Quebec Transmission System – February 2006
Amendment Report SQSS Review Request GSR007 Review of Infeed Loss limits –
Prepared by the SQSS Review Group for Submission to the Authority – 10 th September
2009 available at:- http://www.nationalgrid.com/NR/rdonlyres/EF5C0829-1C5E-4258-8F73-70DC62C43F49/36936/SQSS1320Reportv10_final.pdf