Anda di halaman 1dari 18

Potential Hazards with

Neutral Conductors

Click to Advance
Neutrals Are Current Carrying
Conductors

• Neutrals are grounded but carry current under load.


• The source of neutral current cannot always be
identified.

Click to Advance
Potential Hazards with Neutral
Conductors

• Breaking a neutral under load could create a


shock hazard.
• Individuals contacting a lifted neutral potentially
provide an alternate path to ground.
• A broken neutral or lifted neutral could result in a
shock or an arc.

Click to Advance
Energized Neutral Examples
• A neutral was misidentified and inadvertently opened
creating an arc (ORPS EM-SR-WSRC-FTANK-2005-
0009)

• A circuit was moved to a different distribution panel, but


the neutral was spliced in the original panel (ORPS EM-
RL-PHMC-PFP-2005-0011)

• An electrician received a shock after lifting a neutral from


its bus bar. The neutral received its power through an
emergency light that received power from another
distribution panel. (ORPS SC-PNSO-
PNNL=PNNLBOPER-2005-0018)

Click to Advance
Configuration That Requires
Additional Precautions:

Click to Advance
Component labels
For the purpose of this presentation, please review the following labels:

Circuit Breaker

Circuit A Ungrounded Conductor

Circuit B Ungrounded Conductor


Notes:
Grounded Conductor (Neutral Conductor)
• 3 current carrying
conductors in a
Ground raceway.
• Copper ground wire
omitted for simplicity.
Ballast / Fluorescent Light
• Highlighted in yellow
indicates energized.

Ballast / Fluorescent Light enclosure

Click to Advance
The Multi-Wire Branch Circuit is an
acceptable configuration according
to the National Electrical Code
(NEC) Section 210.4.

Click to Advance
This circuit has also been referred to as:
• The Edison Circuit
• Common Neutral Circuit
• Shared Neutral Circuit

Click to Advance
• These circuits are typically found on 120 / 240 volt
single phase systems, but can be found on 208Y /120
and 277Y / 480 volt systems as well.
• The Grounded Neutral wire carries the unbalanced
load current. (“Grounded Conductor”)

Click to Advance
Ckt
A

Click to Lock Out


Ckt
X Circuit
B
Click to “B”
Energize Circuits

The desired Ckt A


technique used to
remove a device Is
to cut the neutral
lead
The or disconnect
Neutral Will
Ckt B
the device
Remain leaving a
at Ground
neutral pigtail. (Click)
Potential

Ckt B
Ckt A

Click to Advance
Ckt
A

Ckt
B X
Avoid
Breaking The
If You Break The
Neutral Bundle, It
Neutral Bundle
You
Will Become
Energized
May See From
an Arc
in a Multi-Wire
Circuit “A”
when disconnecting
(Click)

Branch Circuit!

If You Contact The


Neutral Conductor
You May Feel A
Shock.
Click to Advance
Use the following guidance when the neutral conductor must be interrupted:
• Treat the neutral as energized even though the circuit is locked out at the
source. (Use PPE that is appropriate for the hazard, i.e. gloves and eye
protection)
• Measure absence of voltage to ground immediately after lifting leads when
more than one neutral is lifted from a device or when a splice is broken.

Click to Advance
Use the following guidance when the neutral
conductor must be interrupted:

 If known, Lock out both / all load breakers.


 If both circuit breakers in a multi-wire branch circuit are not known?
o Test the neutral circuit with a clamp-on type current detector to identify
if the neutral is carrying current before lifting neutral leads or breaking
a neutral connection.
NOTE: Current will exist only if one or more circuits sharing the neutral
have a load energized at the time of measurement.

Click to Advance
When a common neutral hazard is discovered at a device:
 Stop work and remove the hazardous condition or plan a new work
package considering known energized conductors.
 It should be corrected by installation of pigtails or other means, to maintain
continuity of the neutral wiring in accordance with NFPA 70 National
Electrical Code.

Click to Advance
Other general precautions include:

Label the doors of lighting and power panels where common neutrals are
known to exist. This will alert LOTO planners and workers of potential
problems.

Click to Advance
Other general precautions include:

Provide instructions in work packages where common neutrals are known to


exist to remind workers to be alert to wiring that may indicate a common
neutral and to maintain neutral circuit continuity.

Click to Advance
Other general precautions include:

Suspect a multi-wire branch circuit when three or more neutral conductors are
spliced together in a junction box, outlet box, or lighting fixture.

Click to Advance
Potential Hazards with
Neutral Conductors

Questions or Comments?
Contact Bobby Gray or Jerald Kinz

Click to End Show

Anda mungkin juga menyukai