Simulasi Pemeliharaan Transformator
Simulasi Pemeliharaan Transformator
Simulasi
Pemeliharaan Trafo
1
SIMULASI PEMELIHARAAN
TRANSFORMATOR DISTRIBUSI
TRAFO MERUPAKAN SUATU ALAT UNTUK
MEMINDAHKAN ENERGI LISTRIK DARI SATU TEMPAT KE
TEMPAT LAIN DNG TEGANGAN BERBEDA MELALUI SUATU
GANDENGAN MAGNIT YG BEKERJA BERDASARKAN
PRINSIP ELEKTRO MAGNETIS
MISAL :
1. TRAFO DIST 20 / 0.4kV – 100 kva
2
PEMERIKSAAN TRAFO
3
I.1 PEMERIKSAAN ELEKTRIK
4
2. PEMERIKSAAN TAP CHANGER
PADA SETIAP POSISI
3. UNTUK TRANSFORMATOR
1 PHASA PERIKSA
OPERATING MEKANIS
PADA CB NYA
4. UNTUK TRANSFORMATOR
YG TELAH LAMA TIDAK
DIPAKAI ( + 1 TAHUN )
SEBELUM DI BERI TEG
DIPERIKSA TEGANGAN
TEMBUS MINYAK.
5
II.2 BREATHER (SILICA GEL)
6
III. PERSIAPAN PENGOPERASIAN TRAFO
7
IV. PEMELIHARAAN TRANSFORMATOR
8
IV.1.2 PEMERIKSAAN TEMBUS TEGANGAN MINYAK TRAFO
9
MINYAK TRAFO HARUS MEMENUHI
KARAKTERISTIK SBB:
1. HARUS MEMPUNYAI KEKUATAN ISOLASI (DIELEC
TRIC STRENGTH) BESAR.
2. HARUS MEMPUNYAI EFEK PENDINGIN YANG BAIK
ATAU KEKENTALAN YANG RENDAH.
10
MINYAK TRAFO LAMBAT LAUN AKAN MENGALAMI
PENCEMARAN SESUAI DENGAN UMUR PAKAI-NYA.
PENYEBAB HAL TERSEBUT DIATAS ADALAH :
PENYERAPAN UAP AIR DARI LUAR
MATERIAL DARI LUAR YANG MASUK KEDALAM
TANGKI.
11
LANGKAH UNTUK MENGHINDARI OKSIDASI
TSB ADALAH :
MENGHINDARKAN HUBUNGAN LANGSUNG MINYAK DENGAN
UDARA. UNTUK ITU DIBUAT KONSERVATOR YG BERFUNGSI
MENCEGAH KONTAK LANGSUNG ANTARA MINYAK YANG
PANAS DALAM TANGKI DGN UDARA LUAR.
UAP AIR JUGA MENCEMARI MINYAK TRAFO, OLEH
SEBAB ITU DI PASANG DEHYDRATING BREATHER
YANG DIISI SILICA GEL.
TANGKI YANG TERTUTUP RAPAT DAN DIISI DENGAN
NITROGEN.
TANGKI YANG TERTUTUP RAPAT DAN DIISI MINYAK
SAMPAI PENUH.
12
STANDART PENGETESAN MINYAK TRAFO
IEC.156
MINYAK BARU SEBELUM DIOLAH 30 Kv/2,5 mm
S
13
PERALATAN PENGETESAN TEGANGAN
TEMBUS MINYAK TRAFO
Break Down Voltage (BDV) Test
14
IV. 3 PEMERIKSAAN BAGIAN PENJEPIT
DAN KATUP / VALVE
MISAL :
TERMINAL BUSHING.
GROUNDING TRAFO.
15
IV.4 PEMERIKSAAN ASSESORIS
TRAFO
PEMERIKSAAN ASSESORIS TRAFO SANGAT PERLU
DILAKUKAN KARENA UNTUK MENGETAHUI APAKAH
MASIH BEKERJA DENGAN BAIK, SEHINGGA DAPAT
MENCEGAH GANGGUAN-GANGGUAN SECARA DINI.
ANTARA LAIN :
1. THERMOMETER OIL DOUBLE CONTACT.
2. THERMOMETER WINDING DOUBLE CONTACT.
3. BUCHOLZ RELAY.
4. BREATHER.
5. OIL LEVEL.
6. FAN / KIPAS ANGIN.
16
IV.5. PEMERIKSAAN BAGIAN DALAM TRAFO
17
IV.5.4. PEMERIKSAAN TAP
CHANGER
PEMERIKSAAN PADA TAP CHANGER ANTARA LAIN:
a. APAKAH ADA BEKAS DISCHANGER / HANGUS.
b. APAKAH TIMBUL KARAT.
c. KONTAK – KONTAK MEKANIS.
18
CARA PEMELIHARAAN TRAFO DIST
1. PERSIAPKAN PERKAKAS KERJA UNTUK PEMELIHARAAN TRAFO.