- Gangguan simetris ( gangguan 3 fasa )

- Gangguan tak simetris


fasa fasa
fasa fasa ke tanah
fasa ke tanah
GANGGUAN HUBUNG SINGKAT

Bila terjadi gangguan tak simetris akan menimbulkan
Ketidak seimbangan arus maupun tegangan.

Untuk memecahkan masalah diatas maka digunakan

TEORI KOMPONEN SIMETRIS
SISTEM 3 FASA SEIMBANG
@ ARUS MASING MASING FASA DAN
@ TEGANGAN FASA ( LINE ) SAMA

0
a
0 V E Z =
0
b
240 V E Z =
0
c
120 V E Z =
A
B
C
Z Z Z Z
Z Z
Z = I Ia
Z =
0
b
240 I I
Z =
0
c
120 I I
TEORI KOMPONEN SIMETRIS
TEORI INI DIKEMUKAKAN OLEH C L PORTESQUE ( 1918 )
CARANYA ADALAH DENGAN MENGURAIKAN VEKTOR
3 FASA YANG TAK SEIMBANG MENJADI 3 PASANG
VEKTOR YANG SEIMBANG :

# KOMPONEN URUTAN POSITIP
# KOMPONEN URUTAN NEGATIP
# KOMPONEN URUTAN NOL
0
120
0
120
Va1
Vb1
Vc1
Va2
Vc2 Vb2
Va0
Vb0
Vc0
KOMPONEN URUTAN POSITIP ( INDEK 1 )

TERDIRI DARI 3 PASOR YANG SAMA BESAR
NYA , DAN ALING BERBEDA FASA SEBESAR
120 SATU SAMA LAINNYA
( URUTAN SAMA DENGAN PASOR ASLINYA )




KOMPONEN URUTAN NEGATIP ( INDEK 2 )

TERDIRI DARI 3 PASOR YANG SAMA DAN
BERBEDA FASA 120
( URUTANNYA BERLAWANAN DENGAN
VEKTOR ASLINYA )



KOMPONEN URUTAN NOL ( INDEK 0 )

TERDIRI DARI 3 PASOR YANG SAMA DAN
SEFASA .


OPERATOR a
Suatu operator yang berfungsi untuk memutar vektor dengan
Sudut 120 dan berlawanan arah dengan arah jarum jam ,
0
120 1Z = a
0
120 1Z = a
0 2
240 1Z = a
0
120
0
240
0 3
360 1Z = a
0 1
360 sin 360 cos 360 1
866 , 0 5 , 0
240 sin 240 cos 240 1
866 , 0 5 , 0
120 sin 120 cos 120 1
0 0 0 3
0 0 0 2
0 0 0
j
j a
j
j a
j
j a
+
= + = Z =

= + = Z =
+
= + = Z =
0 1
2
= + + a a
HUBUNGAN KOMPONEN SIMETRIS DENGAN
BESARAN FASA
0 b0 a0
a2
2
c2
a2 b2
a2 a2
a1 c1
a1
2
b1
a1 a1
V V V
V a V
aV V
V V
aV V
V a V
V V
c
= =
=
=
=
=
=
=
c0 c2 c1 c
b0 b2 b1 b
a0 a2 a1 a
V V V V
V V V V
V V V V
+ + =
+ + =
+ + =
a0 a2
2
a1 c
a0 a2 a1
2
b
a0 a2 a1 a
V V a aV V
V aV V a V
V V V V
+ + =
+ + =
+ + =
SYNTHESIS
a0 a2
2
a1 c
a0 a2 a1
2
b
a0 a2 a1 a
V V a aV V
V aV V a V
V V V V
+ + =
+ + =
+ + = TEGANGAN
a0 a2
2
a1 c
a0 a2 a1
2
b
a0 a2 a1 a
I I a aI I
I aI I a I
I I I I
+ + =
+ + =
+ + =
ARUS
.


0
120
0
120
Va1
Vb1
Vc1
Va2
Vc2 Vb2
Va0
Vb0
Vc0
Va
Vb
Vc
Bila komponen simetrisnya diketahui
Dapat digambarkan vektor aslinya.
BESARNYA KOMPONEN URUTAN NOL
a0 c b a
a0 a2
2
a1
2
c b a
a0 a2
2
a1 c
a0 a2 a1
2
b
a0 a2 a1 a
3V V V V
3V ]V a a [1 a]V a [1 V V V
V V a aV V
V aV V a V
V V V V
= + +
+ + + + + + = + +
+ + =
+ + =
+ + =
) ........(4 ]......... V V [V
3
1
V
c b a a0
+ + =
0 a a 1
0 a a 1
2
2
= + +
= + +
BESARNYA KOMPONEN URUTAN Negatip
a0 a2
2
a1 c
a0 a2 a1
2
b
a0 a2 a1 a
V V a aV V
V aV V a V
V V V V
+ + =
+ + =
+ + =
a
a

....
....
1 ....
2
a0 a2
3
a1
2
c
a0
2
a2
3
a1
4
b
2
a0 a2 a1 a
aV V a V a aV
V a V a V a V a
V V V V
+ + =
+ + =
+ + =
0 3V 0
a]V a [1 ]V a a [1 ]V a a [1 aV V a V
a2
a0
2
a2
3 3
a1
2 4
c b
2
a
+ + =
+ + + + + + + + = + +
} {
3
1
2
2 c b a a
aV V a V V + + =
BESARNYA KOMPONEN URUTAN POSITIP
DENGAN CARA YANG SAMA DAN DENGAN MENGALIKAN
PERS ( 2 ) DENGAN BESARAN
2
......
......
1 ......
a
a

MAKA DIPEROLEH BESARNYA KOMPONEN URUTAN POSITIP


} {
3
1
2
1 c b a a
V a aV V V + + =
ANALYSIS
} aI I a {I
3
1
I
} I a aI {I
3
1
I
} I I {I
3
1
I
} aV V a {V
3
1
V
} V a aV {V
3
1
V
} V V {V
3
1
V
c b
2
a a2
c
2
b a a1
c b a a0
c b
2
a a2
c
2
b a a1
c b a a0
+ + =
+ + =
+ + =
+ + =
+ + =
+ + =
TEGANGAN
ARUS
IMPEDANSI URUTAN
PENGERTIAN IMPEDANSI URUTAN PADA SISTEM TENAGA LISTRIK
BERBEDA DENGAN PENGERTIAN KOMPONEN URUTAN PADA ARUS
DAN TEGANGAN

IMPEDANSI URUTAN ADALAH SEBAGAI BERIKUT :

IMPEDANSI URUTAN POSITIP (Z1) ADALAH IMPEDANSI DARI
SIRKUIT 3 FASA YANG SIMETRIS YANG DIDAPAT DENGAN
MEMBERIKAN TEGANGAN URUTAN POSITIP DAN HANYA
MENGALIR ARUS URUTAN POSITIP SAJA

IMPEDANSI URUTAN NEGATIP (Z2) DAN IMPEDANSI URUTAN
NOL ( Z0 ) ADALAH IMPEDANSI YANG DIDAPAT SEPERTI HAL
DIATAS HANYALAH TEGANGAN DAN ARUS YANG MENGALIR
ADALAH URUTAN NEGATIP DAN NOL

IMPEDANSI URUTAN


PERALATAN LISTRIK YANG STATIS SEPERTI TRAFO
TENAGA. SALURAN TRANSMISI. ATAU DISTRIBUSI NILAI
IMPEDANSI URUTAN POSITIP SAMA DNGAN URUTAN
NEGATIP .
SEDANG PERALATAN YANG BERPUTAR SEPERTI
GENERATOR BESARNYA AGAK BERBEDA , SEDANG
IMPEDANSI URUTAN NOL SANGAT BERBEDA DENGAN
IMPEDANSI URUTAN POSITIP DAN NEGATIP .



IMPEDANSI URUTAN GENERATOR
RANGKAIAN IMPEDANSI URUTAN POSITIP. NEGATIP DAN NOL
DARI GENERATOR :
PERSAMAAN DARI KETIGA URUTAN KOMPONEN SIMETRIS
0 a0 a0 a0
2 a2 a2 a2
1 a1 a1 a1
Z I E V
Z I E V
Z I E V
=
=
=
1
N
2
N
0
N
1
I
2
I
0
I
1 a
E
2 a
E
0 a
E
1 a
V 2 a
V
0 a
V
. . . . . ( 1 )
a a1
a0 a2
E E
0 E E
=
= =
0 a0 a0
2 a2 a2
1 a1 a1 a1
Z I 0 V
Z I 0 V
Z I E V
=
=
=
TEGANGAN YANG DIBANGKITKAN GENERATOR SEIMBANG
SEHINGGA
MAKA PERSAMAAN ( 1 ) MENJADI
. . . . . ( 2 )
A
C
0 a0
c b a n
3I 3I
I I I I
= =
+ + =
. . . . . ( 3 )
TEGANGAN URUTAN NOL
) 3Z (Z I E
Z I Z 3I E
Z I E Z I V
n g0 a0 a0
g0 a0 n a0 a0
g0 a0 a0 n n a0
=
=
+ =
0 g
Z
0 g
Z
0 g
Z
B
0 g
Z
0 a
E
0 b
E
0 c
E
0 a
I
0 b
I
0 c
I
0
3
a
n
I
I
n
Z
.. . . . ( 4 )


g0
Z
a0
E
0 a
I
n
Z
SEHINGGA RANGKAIAN IMPEDANSI URUTAN NOL DAPAT
DIGAMBARKAN SBB;
g0
Z
a0
E
a0
I
a0
I
Tidak mengalir
Titik netral tidak ditanahkan
IMPEDANSI TRAFO DAYA 2 KUMPARAN
SAMBUNGAN URUTAN NOL URTAN POSITIP&NEGATIP
L
H
L H
L H
ZL
ZH
ZL ZH
3ZnH
ZL ZH
ZL ZH
ZL ZH
ZL ZH 3ZnH 3ZnL
ZL ZH
ZL ZH
H
H
H
H
H
H
L
L
L
L
L
L
L
L
L
L
L
L
L
H
H
H
H
H
H
H
ZL ZH L H
ZL ZH L H
ZL ZH L H
ZL ZH L H
ZL ZH L H
ZL ZH L H
ZL ZH L H
ZL ZH L H
ZnL
ZnH
ZnH
PENGHANTAR
RANGKAIAN
H
RANGKAIAN T
1
Z
2
Z
0
Z
2
XC
1
2
XC
1
2
XC
2
2
XC
0
2
XC
2
2
XC
0
2
Z
1
2
Z
1
2
Z
2
2
Z
0
2
Z
2
2
Z
0
1
XC
2
XC
0
XC
URUTAN POSITIP URUTAN NEGATIP
URUTAN NOL
URUTAN POSITIP URUTAN NEGATIP URUTAN NOL


A
B
C
PERSAMAAN HUBUNG SINGKAT PADA GENERATOR
( Generator diandaikan dalam keadaan tanpa beban )
1. HUBUN SINGKAT 3 FASA
Kondisi awal pada titik
Gangguan ;
0 V V V
c b a
= = = . . . (5)
) V V (V
3
1
V
) aV V a (V
3
1
V
) V a aV (V
3
1
V
c b a 0
c b
2
a 2
c
2
b a 1
+ + =
+ + =
+ + =
(6)
DENGAN MEMASUKAN PERS. (5) KE (6) :
1
1
1 1 1 1
1 1 1 1
Z
E
I 0 Z I E
0 Z I E V
= =
= =
0 I 0 Z
0 Z I
0 Z I V
2 Z
2 2
2 2 2
= =
=
= =
ARUS PADA FASA a :
1
1
1 0 2 1 a
Z
E
0 0 I I I I I
=
+ + = + + =
0 I 0 Z
0 Z I V
0 0
0 0 0
= =
= =
1
1
c
1
1
2
b
1
1
a
Z
E
a I
Z
E
a I
Z
E
I
=
=
=
J ADI ; , , , , , , , (7)


. . . . . . . (8)

. . . . . . . (9)
JADI ARUS HUBUNG SINGKAT 3 FASA :
1
1
HS3
Z
E
I =
3FASA
E1
I1
N1
F1
Z1G
Z1G
E1
a
b
c
Ia
Ib
Ic
Va =Vb =Vc = 0
. . . . . . (10)
Diagram satu garis dan
rangkaian urutannya D
Diagram vektor untuk
Gangguan 3 fasa


A
B
C
2. HUBUN SINGKAT 2 FASA
Kondisi awal pada titik
Gangguan ;
0 I
I I
V V
a
c b
c b
=
=
=
3) ........(1 V V , maka
a)V (a a)V (a
V V a aV
V aV V a
maka , V V , karena
V V a aV V
V aV V a V
2 1
2
2
1
2
0 2
2
1
0 2 1
2
c b
0 2
2
1 c
0 2 1
a
b
=
=
+ + =
+ +
=
+ + =
+ + =
DENGAN MENGGUNAKAN RUMUS RUMUS
KOMPONEN SIMETRIS MAKA ARUS HUBUNG
SINGKAT DUA FASA DIPEROLEH ;
ARUS HUBUNG SINGKAT 2 FASA ;
......(21) ..........
Z Z
E 3
I
2 1
1
hs2
+
=
2 fasa
Zg
E1
Z1g Z2g
I1 I2
N1 N2
F2 F1
VCF
Ic
Ib
a
b
c
Vektor diagram
Diagram satu garis
Diagram urutan


A
B
C
3. HUBUN SINGKAT 1 FASA TANAH
Kondisi awal pada titik
Gangguan ;
0 V
0 I I
a
c b
=
= =
Menentukan komponen
Komponen simetris ;
a a c b a 0
a a c b
2
a 2
a a c
2
b a 1
I
3
1
0) (I
3
1
) I I (I
3
1
I
I
3
1
0) (I
3
1
) aI I a (I
3
1
I
I
3
1
o) (I
3
1
) I a aI (I
3
1
I
= + = + + =
= + = + + =
= + = + + =
....(25) .......... .......... I
3
1
I I I
a 0 2 1
= = =
J ADI :
DENGAN MENGGUNAKAN RUMUS RUMUS KOMPONEN
SIMETRIS MAKA ARUS GANGGUAN SATU FASA KE
TANAH DAPAT DIPEROLEH
Arus hubung singkat 1 fasa ke tanah :
(30) ........
Z Z Z
3E
I
3 2 1
1
hs1
+ +
=
1 fasa
Zg
E1
Z1g
Z2g
I1 I2
N1 N2
F2
F1
a
b
c
Vektor diagram
Diagram satu garis
Diagram urutan
Z0g
I0
N0
F0
Ia
VbF
VcF
SATUAN PERUNIT ( PU )
RANGKAIAN 3 FASA :


b
2
b
b
2
b
b
b
b
b
b
b
b
b
b
b b b
MVA
KV
VA
V
V 3
VA 3
V
I 3
V
Z
V 3
VA
I
I V 3 VA
=
= =
=
=
2
b
b
seb
KV
MVA
Z Z(pu)
r) Nilai(Dasa
narnya) Nilai(sebe
Nilai(pu)
=
=
]
lm MVA
br MVA
[ ]
lm KV
br KV
[ lm Z br Z
MVA
KV
Z
KV 3
1000 MVA
I
b
b
2
b
b
pu pu
b
2
b
b
b
b
b
=
=

=
ARUS DASAR :
IMPEDANSI DASAR :
br = baru lm = lama
BILA :
lm MVA
br MVA
lm Z br Z
lm KV br KV
b
b
pu pu
b b
=
=
CONTOH ( 1 ) ; TRAFO DAYA 3 FASA
15 MVA
XT = 10% = 0,1 PU
13,8 KV 138 KV
2
) ( ) (
2
) (
2
) (
]
13,8KV
138KV
[ sisi13,8KV X 138KV X
127 0,1
15MVA
138KV
sisi138KV X
1,27 0,1
15MVA
13,8KV
sisi13,8KV X
=
= =
= =
O O
O
O
Rasio Tegangan Kwadrat
CONTOH ( 2 ) ; TRAFO DAYA 3 FASA
15 MVA
XT = 10% = 0,1 PU
13,8 KV
138 KV
20 MVA
Xg = 30%
30%
138KV
20MVA
286
KV
MVA
X Xg
286 ]
13,8
138
[ 2,86 Xg
13,8KV 2,86 0,3
20MVA
13,8KV
Xg
2 2
b
b
seb (%)
2
(
2
(
= = =
= =
= =
KV 20MVA;13,8 30%
138KV : 20MVA 30% Xg
=
=
G
50MVA
22%
50MVA
10%
G
T1
70KV
Z=15+J 40
T2
2,5MVA
10%
20KV
Z=6,79+J 8,8
DIKETAHUI SUATU SISTEM SEPERTI GAMBAR
BILA MVAb =100 ;KVb =SESUAI DENGAN TEGANGAN NOMINAL NYA .
TENTUKAN ARUS DASAR ( ib) , IMPEDANSI DASAR ( Zb ) , SERTA
IMPEDANSI J ARINGAN DALAM PERUNIT.
MVAb =100

PADA SISTEM 70 KV :
49
100
70
Z
825A
3 70
100 1000
I
2
b
b
= =
=

=
PADA SISTEM 20 KV :
4
100
20
Z
2887A
3 20
100 1000
I
2
b
b
= =

=
IMPEDANSI DALAM PU :
j0,20pu
25
100
j0,10 X
j0,82pu 0,31
49
j40 15
Z
j0,20pu
50
100
j0,10 X
j0,44pu
50
100
j0,22 Xg
T2
AB
t1
= =
+ =
+
=
= =
= =
j2,2pu 1,7
4
j8,8 6,79
Z
CD
+ =
+
=
RANGKAIAN EKUIVALEN URUTAN POSITIP ;
E
1pu
Xg XT1 ZAB
ZCD
XT1
J 0,44 J 0,20 0,31+j0,82
J 0,20
1,7+j2,2
F1 F2 F3 F4 F5
TENTUKAN BESARNYA ARUS HUBUNG SINGKAT
DI F1 , F2 , F3 . F4 , F5 .
PROSEDUR KALKULASI ARUS HUBUNG SINGKAT
DI SISTEM TEGANGAN TINGGI
1. GAMBAR SISTEM TERSEBUT DALAM KUTUB TUNGGAL .
2. BERI DATA DARI SELURUH KOMPONEN YANG ADA :
= TEGANGAN SETIAP SEKSI DALAM KV
= IMPEDANSI GENERATOR DAN TRAFO DAYA
YANG DINYATAKAN DALAM % ( PU ).
= IMPEDANSI DARI SALURAN TRANSMISI
DISTRIBUSI DALAM OHM/KM ATAU TOTAL OHM
3. TENTUKAN :MVAb ; KVb ; Ib
4. TENTUKAN J ENIS GANGGUAN ; 3fasa ; 2 fasa ; 1 fasa ke tanah
5. GAMBAR RANGKAIAN IMPEDANSI MENURUT KOMPONEN
SIMETRIS : POSITIP ; NEGATIP ; DAN NOL YANG DINYATAKAN
DALAM PU .
6. SEDERHANAKAN RANGKAIAN IMPEDANSI URUTAN : GUNAKAN
RUMUS TRANSFORMASI DELTA KE BINTANG DAN
BINTANG KE DELTA
7. HITUNG ARUS HUBUNG SINGKAT DALAM PU KEMUDIAN
DIUBAH KE DALAM AMPER .
A Y
Y A
AC BC AB
BC AC
C
AC BC AB
BC AB
B
CA BC AB
AC AB
A
Z Z Z
Z Z
Z
Z Z Z
Z Z
Z
Z Z Z
Z Z
Z

+ +

=
+ +

=
+ +

=

A C C B B A
B
AC
A C C B B A
A
BC
C A C B B A
C
AB
Z Z Z Z Z Z
Z
Z
Z Z Z Z Z Z
Z
Z
Z Z Z Z Z Z
Z
Z

+ +
=
+ +
=
+ +
=

RUMUS TRANSFORMASI
ZAB
ZBC
ZAC
A
B
C
ZA
A
B
ZB
ZC
C
SISTEM
R TR
TS
S
LINE
G H
0GR
2GR
1GR
X
X
X
TR
X
0GH
2GH 1GH
X
X X =
TS
X
0TS
2TS
1TS
X
X
X
1. RANGKAIAN URUTAN POSITIP ;
BUS N1
X
F1
GR
X
1
TR
X
1GH
X
TS
X
1GS
X
E
E
E
RANGKAIAN EKUIVALEN URUTAN POSITIP
E
X
F1
1R
I
1L
I
1L
X
1R
X
N1
1
1L 1R
1R
1L
1
1L 1R
1L
1R
1GS TS 1GH 1R
TR 1GR 1L
I
X X
X
I
I
X X
X
I
X X X X
X X X
+
=
+
=
+ + =
+ =
X
F1
N1
1R 1L
1R 1L
1
X X
X X
X
+
=
1
I
R TR
TS
S
LINE
SISTEM
G H
0GR
2GR
1GR
X
X
X
TR
X
0GH
2GH 1GH
X
X X =
TS
X
0TS
2TS
1TS
X
X
X
1. RANGKAIAN URUTAN NEGATIP ;
BUS N2
X
F2
GR
X
2
TR
X
2GH
X
TS
X
2GS
X
RANGKAIAN EKUIVALEN URUTAN NEGATIP
X
F2
2R
I
2L
I
2L
X
2R
X
N2
2
2L 2R
2R
2L
2
2L 2R
2L
2R
2GS TS 2GH 2R
TR 2GR 2L
I
X X
X
I
I
X X
X
I
X X X X
X X X
+
=
+
=
+ + =
+ =
X
F2
N2
2R 2L
2R 2L
2
X X
X X
X
+
=
2
I
R TR
TS
S
LINE
SISTEM
G H
0GR
2GR
1GR
X
X
X
TR
X
0GH
2GH 1GH
X
X X =
TS
X
0TS
2TS
1TS
X
X
X
1. RANGKAIAN URUTAN NOL ;
BUS N0
X
F0
GR
X
0
TR
X
0GH
X
TS
X
0GS
X
OPEN
N0
F0
X
0R
X
0L
X
0L
I 0R
I
X
F0
N0
RANGKAIAN EKUIVALEN URUTAN NOL
0
0L 0R
0L
0R
0
0R 0L
0R
0L
0GH TS 0R
TR 0GR 0L
I
X X
X
I
I
X X
X
I
X X X
X X X
+
=
+
=
+ =
+ =
0
I 0
X
0R 0L
0R 0L
0
X X
X X
X
+
=
0L 2L 1L HS1
0R 2R 1R HS1
0 2 1
HS1
I I I (kiri) I
I I I (kanan) I
X X X
3E
I
+ + =
+ + =
+ +
=
DIKETAHUI SUATU SISTEM SEPERTI GAMBAR
A
% 10
X
X X
0TC
2TC 1TC
=
=
=
10% X
20%
X X
0GC
2GC 1GC
=
=
=
B
C
10% X
20%
X X
0GA
2GA 1GA
=
=
=
% 10
X
X X
0TA
2TA 1TA
=
=
=
40Km
50Km
/Km 1,2 X
/Km 0,4 X
0L
2 1L
O =
O = =
L
X
150KV
TENTUKAN :1. BESARNYA ARUS HUBUNG SINGKAT 3 FASA ; 2 FASA DAN
1 FASA KE TANAH
2. DISTRIBUSI ARUS PADA SAAT GANGGUAN 1 FASA DI C
3. TEGANGAN PADA BUS C .
50MVA
50MVA
Lembar Latihan
Lembar jawaban
Impedansi Generator,Trafo dan Transmisi.
j0,3pu j0,1 j0,2 GT X GT X
Trafo Gen - Xtotal
j0,1pu j10% T X T X T X
j0,2pu j20% G X G X
A 2 A 1
A 0 A 2 A 1
A 2 A 1
= + = =
+
= = = =
= = =
j0,3pu j0,1 j0,2 GT X GT X
Trafo Gen - Xtotal
j0,1pu j10% T X T X T X
j0,2pu j20% G X G X
B 2 B 1
C 0 C 2 C 1
C 2 C 1
= + = =
+
= = = =
= = =
j0,1067pu
450
j48
j48 j1,2 40 AB X
j0,0355pu
450
j16
j16 j0,4 40 AB X AB X
450
50
150
X
0
2 1
2
d
= =
= =
= =
= = =
= =
Xtotal Generator Trafo
di A
Xtotal Generator Trafo
di C
X Transmisi A - B

Lembar jawaban
j0.1333pu
450
j60
j60 j1,2 50 BC X
j0,0444pu
450
j20
j20 j0,4 50 BC X BC X
0
2 1
= =
= =
= =
= = =
X Transmisi B-C
IMPEDANSI URUTAN POSITIP/NEGATIP
1
N
Y
1
E
j0,2 G X
A 1
=
j0,1 T X
A 1
=
j0,0355 AB X
1
=
j0,0444 BC X
1
=
X 1
F
j0,2 G X
C 1
=
j0,1 T X
C 1
=
Lembar jawaban
RANGKAIAN URUTAN NOL
j0,1
ki X
0
=
j0,1
TB X
0
=
j0,1
ka X
0
=
j0,1067
AB X
0
=
j0,1333
BC X
0
=
C
A B
0
N
0
F
X
0
F
0
N
j0,2007
ki X
0
j0,1
ka X
0
ki I
0
ka I
0
j0,2007pu
j0,1333
j0,1 j0,2067
j0,1 j0,2067
j0,1333 j0,1} j0,1067]// {[j0,1
BC X TB AB]//[X X T [X ki X
0 0 0 A 0 0
=
+
+

=
+ + =
+ + =
j0,1 ka X
0
=
Lembar jawaban
j478,866A j2,4882pu
j0,4019
1pu
j0,1 j0,0667 j0,0667
1pu
tot X tot X tot X
E
I
j0,0667pu
j0,1 j0,2007
j0,1 j0,2007
ka ki//X X tot X
0 2 1
0
0 0 0
= = =
+ +
=
+ +
=
=
+

= =
A
pu
I
6048 , 1436
4557 , 192 4646 , 7
4646 , 7
4882 , 2 3 3 1 I
0 hs
=
=
=
= =
ARUS HUBUNG SINGKAT 1FASA KE TANAH
Lembar jawaban
1
N
Y
1
E
X
1
F
ka I
1
ki I
1
j0,3 ka X
1
=
j0,3799
ki X
1
=
X
2
F
ka I
2
ki I
2
j0,3 ka X
2
=
j0,3799
ki X
2
=
2
N
X
0
F
ka I
0
ki I
0
j0,1 ka X
0
=
j0,2007
ki X
0
=
0
N
2 1 0
I I I = =
211,2965A
192,4557 1,0979
1,0979pu
2,4882
j0,6799
j0,3
I
j0,3 j0,3799
j0,3
ki I ki I
1
2 1
=
=
=
=
+
=
=
267,5718A
192,4557 1,3903
1,3903pu
2,4882
j0,6799
j0,3799
I
j0,3 j0,3799
j0,3799
ka I ka I
1
2 1
=
=
=
=
+
=
=
Lembar jawaban
159,2511A
192,4557 0,8275
0,8275pu
2,4882
j0,3007
j0,1
I
j0,1 j0,2007
j0,1
ki I
0 0
=
=
=
=
+
=
319,611A
192,4557 1,6607
1,6607pu
2,4882
j0,3007
j0,2007
I
j0,1 j0,2007
j0,2007
ka I
0 0
=
=
=
=
+
=
DISTRIBUSI ARUS URUTAN POSITIP / NEGATIP
A
B C
1
N
1
F
j0,3 j0,3
1,0979pu
ki I I
1 A
=
=
1,3909pu
ka I I
1 C
=
=
j0,0355pu j0,0444pu
211,2965A 1,0979pu
I I I
A C - B B - A
= =
= =
(478,866A)
2,4882pu
211,2965A
1,0979pu
I I I
C - B B - A A
=
=
= =
267,5718A
1,3909pu I
C
=
=
Lembar Jawaban
DISTRIBUSI ARUS URUTAN NOL
j0,1333 j0,1067
j0,1 j0,1 j0,1
B - A
I
0,2698pu I
A
= 0,5577pu I
B
=
1,6607pu I
C
=
0
F
0
N
478,866A
2,4882pu
0,8275pu ki I I
0 C - B
= =
159,2511A 0,8275pu ki I I
107,3310A j0,5577pu 0,8275pu
j0,3067
j0,2067
I
51,926A j0,2698pu 0,8275pu
j0,3067
j0,1
ki I
j1067 j0,1 j0,1
j0,1
I I
0 C B
B
0 B A A
= = =
= = =
= = =
+ +
= =

Lembar Jawaban
Arus Fasa di A
159,3705A 51,926 211,2965 I I I I
474,519A 51,926 211,2965 2 I 2I I
0 1 c b
0 1 a
= + = + = =
= + = + =
Arus Fasa di B
107,3310A 107,3310 0 I I I I
107,3310A 107,3310 0 I 2I I
0 1 c b
0 1 a
= + = + = =
= + = + =
Arus Fasa di C
52,04A 319,611 -267,5718 I I I I
854,7546A 319,611 267,5718 2 I 2I I
0 1 c b
0 1 a
= + = + = =
= + = + =
Arus Fasa di A-B
-159,3705A 51,926 -211,2965 I I I I
474,519A 51,926 211,2965 2 I 2I I
0 1 c b
0 1 a
= + = + = =
= + = + =
Arus Fasa di B-C
-52,0454A 59,2511 1 -211,2965 I I I I
581,8441A 59,2511 1 211,2965 2 I 2I I
0 1 c b
0 1 a
= + = + = =
= + = + =
Lembar Jawaban
474,519A
-159,3705A
-159,3705A
3Io=
155,778A
474,519A
-159,3705A
-159,3705A
581,8441A
-52,04A
-52,04A
854,7546A
52,04A
52,04A
3Io
958,8346A
3Io
321,993A
107,3310A
107,3310A
107,3310A
3Io
1436,60A
Distribusi Arus pada sistem untuk gangguan satu fasa ke tanah
di Bus C
3Io
3Io
Lembar Jawaban
Tegangan Fasa pada Bus C
KV 196,07 78,043 pu 196,07 0,9011 j0,248985 0,86602
j0,16670 j0,20854 0,36121 j0,291455 0,58291
j0,16670 150 0,41709 210 0,58291
j016607 90 0,41709 240 1 90 0,58291 120 1
V V a aV V
KV 16,04 78,035 pu 16,04 0,9011 j0,248985 0,86602
j0,16607 j0,20854 0,36121 j0,291455 0,58291
j0,16670 30 0,41709 30 0,58291
j0,16607 90 0,41709 120 1 90 0,58291 240 1
V aV V a V
0pu j0,16607 j0,41709 j0,58291 V V V V
j0,16607pu j0,1 1,6607 GTC .X I V
j0,41709pu j0,3 1,3909 GTC .X I V
j0,58291pu
j0,41709 1,0 j0,3 1,3909 1,0 GTC .X I E V
1pu 86,6KV
3
150KV
V
0 0
0 0
0 0 0 0
0 2
2
1 c
0 0
0 0
0 0 0 0
0 2 1
2
b
0 2 1 a
0 0 0
2 2 2
1 I 1
fasa
Z = Z = =
+ =
Z + Z =
Z Z + Z Z =
+ + =
Z = Z = =
+ + =
Z + Z =
Z Z + Z Z =
+ + =
~ = + + =
= = =
= = =
=
= = =
= = =
Lembar Jawaban
474,519A
-159,3705A
-159,3705A
3Io=
155,778A
474,519A
-159,3705A
-159,3705A
581,8441A
-52,04A
-52,04A
854,7546A
52,04A
52,04A
3Io
958,8346A
3Io
321,993A
107,3310A
107,3310A
107,3310A
3Io
1436,60A
Distribusi Arus pada sistem untuk gangguan satu fasa ke tanah
di Bus C
3Io
3Io
KV 196,07 78,043 V
KV 16,04 78,035 V
0 V
0
c
0
b
a
Z =
Z =
=