The RS burners series covers a firing range from 81 to 2290 kW, and it has been designed
for use in hot or superheater water boilers, hot air or steam generators, diathermic oil
boilers.
Operation is "two stage progressive"; the burners are fitted with a microprocessor control
panel which supplies indication of operation and diagnosis of fault cause.
Optimisation of sound emissions is guaranteed by the use of fans with reverse curve
blades and sound deadening material incorporated in the air suction circuit.
The elevated performance of the fans and combustion head, guarantee flexibility of use
and excellent working at all firing rates.
The exclusive design ensures reduced dimensions, simple use and maintenance. A wide
range of accessories guarantees elevated working flexibility.
TS0046UK03
TECHNICAL DATA
Auxiliary electrical power kW 0,12 0,12 0,12 0,12 0,3 0,3 0,4 1
Protection level IP 44
Motor electrical power kW 0,25 0,42 0,45 0,65 1,1 1,5 2,2 4,5
Rated motor current A 2,1 2,9 2 - 1,2 3 - 1,7 4,8 - 2,8 5,9 - 3,4 8,8 - 5,1 15,8 - 9,1
Motor start up current A 10 11 9,5 - 5,5 13,8 - 8 25 - 14,6 27,7 - 16 57,2 - 33,2 126 - 73
Motor protection level IP 40 54
Sound power W -- -- -- -- -- -- -- --
CO Emission mg/kWh < 40
NOx Emission mg/kWh < 130
Directive 90/396 - 89/336 - 73/23 - 92/42 EEC
Conforming to EN 676
Certification CE 0085AP0733 CE 0085AP0734 CE 0085AP0735 CE 0085AP0944 CE 0085AP0945 CE 0085AP0946 CE 0085AT0042
Reference conditions:
Temperature: 20°C
Pressure: 1000 mbar
Altitude: 100 m a.s.l.
Noise measured at a distance of 1 meter.
Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, the
technical data, the equipment and the accessories can be changed.
This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shall
not be divulged, nor duplicated in whole or in part.
2
FIRING RATES
100 10
90 9
RS 38 RS 50
80 8
70 7
RS 28
60 6
50 5
40 4
30 3
hPa (mbar)
20 2
mm H2O
10 1
0 0
-10 -1
0 100 200 300 400 500 600 Mcal/h
150 15
140 14
130 13
RS 190
120 12
110 11
RS 130
100 10
RS 100
90 9
RS 70
80 8
70 7
60 6
50 5
40 4
30 3
hPa (mbar)
20 2
mm H2O
10 1
0 0
-10 -1
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 Mcal/h
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 kW
3
FUEL SUPPLY
GAS TRAIN
The burners are fitted with a butterfly valve to regulate the fuel
delivery on 1st and 2nd stage, controlled by a variable profile
cam servomotor.
Fuel can be supplied either from the right or
left hand sides.
14 6 9 13 8 5 3 2 1
P2 Pressure downstream from the regulator
P2 P3
P3 Pressure upstream from the filter
L L1
L Gas train supplied separately, with the code given in the table
L1 Installer’s responsibility
12
P1
11 4
15
10 7
14 9 13 6 8 P2 5 3 2 1
P3
L L1
4
Gas trains are approved by
standard EN 676 together
Example of gas train “MULTIBLOC” with the burner.
type MBD
Øi
Z
X
5
PRESSURE DROP DIAGRAM
The diagrams indicate the minimum pressure drop of the burners with the various gas trains that
can be matched with them; at the value of these pressure drop add the combustion chamber
pressure.
The value thus calculated represents the minimum required input pressure to the gas train.
mbar
7 55
40
40 BD 40
M
50
35 45 35
Combustion head and gas train
Combustion head
25 25
10
D4 30
MB
20 20 410
25 MBD
12 CT
41 2-4 12 CT
MBD 12 - 4
15 20 15 MBD 4
T
15 - 415 C
MBD 4 15
10 10
10
Pressure drop
Pressure drop
5 5
5
0 0 0
140 150 200 250 280 140 150 200 250 280
kcal/h X 1000 kcal/h X 1000
163 200 250 300 325 kW 163 200 250 300 325 kW
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 407 3970053 3000824 Accessory MBD 412 CT 3970197 - Incorporated
MBD 410 3970054 3000824 Accessory MBD 415 3970180 - Accessory
MBD 412 3970144 - Accessory MBD 415 CT 3970198 - Incorporated
RS 38 RS 38
G20 G25 LPG
45
ΔP 0 ΔP
mbar
7
41 40
mbar
D D
MB MB
40 40
30
Combustion head and gas train
35 35
25
T 30 30
2C
41
Combustion head
Combustion head
2- 10
1 D4
20 D4 MB
MB 25 25
CT
5 CT 20 20 - 412
15 - 41 412
415 MBD T
MBD 1 5 - 415 C
CT MBD
4
- 420 CT
420 15 15
20 - 4 2 0
MBD MBD 4
10
10 10
Pressure drop
Pressure drop
5
5 5
0 0 0
200 250 300 350 378 200 250 300 350 378 400
kcal/h X 1000 kcal/h X 1000
232 250 300 350 400 440 kW 232 250 300 350 400 440 kW
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 407 3970053 3000824 Accessory MBD 415 3970180 - Accessory
MBD 410 3970054 3000824 Accessory MBD 415 CT 3970198 - Incorporated
MBD 412 3970144 - Accessory MBD 420 3970181 3000822 Accessory
MBD 412 CT 3970197 - Incorporated MBD 420 CT 3970182 3000822 Incorporated
6
NATURAL GAS LPG
RS 50 RS 50
G20 G25 LPG
0
41
mbar
ΔP 50 ΔP
mbar
D
MB 60 07
60 D4
45 MB
Combustion head and gas train
35 45
Combustion head
Combustion head
T
2C
- 41 40 40
30 12
D4
MB 410
35 MBD
25
30 30
T
20 -4 15 C
415 25 12 CT
MBD 12 - 4
MBD 4
0-4 20 CT 20 20 41 5 - 415 CT
15 MBD 42 MBD
SE CT 15 0 CT
10 SE - 1200 MBD 420 - 42
MBC 1200
Pressure drop
Pressure drop
10 10
5
5
0 0 0
249 300 350 400 450 500 249 300 350 400 450 500
kcal/h X 1000 kcal/h X 1000
290 350 400 450 500 550 581 kW 290 350 400 450 500 550 581 kW
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 407 3970053 3000824 Accessory MBD 415 CT 3970198 - Incorporated
MBD 410 3970054 3000824 Accessory MBD 420 3970181 3000822 Accessory
MBD 412 3970144 - Accessory MBD 420 CT 3970182 3000822 Incorporated
MBD 412 CT 3970197 - Incorporated MBC 1200 SE 3970221 3000822 Accessory
MBD 415 3970180 - Accessory MBC 1200 SE CT 3970225 3000822 Incorporated
RS 70 RS 70
G20 G25 LPG
ΔP 50 ΔP 50
mbar
mbar
60
Combustion head and gas train
T
40 40 2C
41
50
12-
D4
MB
Combustion head
Combustion head
T 40 T
30 5C 30 5C
- 41 - 41
D 415 15
D 4 - 420 C
T
MB M B
0 CT 420 CT
- 42 B D S E
420 30 M
120
0
MBD SE -
1200
20 20 MBC
E CT
E-1 200 S 20
200 S
MBC 1
10 10
Pressure drop
Pressure drop
10
0 0 0
400 500 600 700 400 500 600 700
kcal/h X 1000 kcal/h X 1000
465 500 600 700 814 kW 465 500 600 700 814 kW
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 412 3970144 - Accessory MBD 420 3970181 - Accessory
MBD 412 CT 3970197 - Incorporated MBD 420 CT 3970182 - Incorporated
MBD 415 3970180 3000843 Accessory MBC 1200 SE 3970221 - Accessory
MBD 415 CT 3970198 3000843 Incorporated MBC 1200 SE CT 3970225 - Incorporated
7
NATURAL GAS LPG
RS 100 RS 100
G20 G25 LPG
ΔP 70 90 ΔP 70
mbar
mbar
80
60 60
Combustion head and gas train
Combustion head
40 5- 40 CT
D 41 50 15
MB -4
C T 4 15 0 CT
- 420 D
MB 20 -
4 2
420 4
30 MBD 40
30 MB
D
CT
0 SE
120
30 0 0 S -
E
S E CT
12 00
20 MBC S E - 19
CT 20
00 SE 190
0
200 SE - 12 MBC
MBC 1 20
190 0 SE CT
00 SE -
Pressure drop
Pressure drop
10 MBC 19 10
10
0 0 0
600 700 800 900 1000 600 700 800 900 1000
kcal/h X 1000 kcal/h X 1000
700 800 900 1000 1100 1163 kW 700 800 900 1000 1100 1163 kW
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 415 3970180 3000843 Accessory MBC 1200 SE 3970221 - Accessory
MBD 415 CT 3970198 3000843 Incorporated MBC 1200 SE CT 3970225 - Incorporated
MBD 420 3970181 - Accessory MBC 1900 SE 3970222 3000825 Accessory
MBD 420 CT 3970182 - Incorporated MBC 1900 SE CT 3970226 3000825 Incorporated
RS 130 RS 130
G20 G25 LPG
ΔP 110 ΔP 110
140
mbar
mbar
Combustion head and gas train
120
90 90
110
80 80
100
Combustion head
Combustion head
70 90 70
T 80
60 -415 C 60
415
MBD 70
50 CT 50
- 420
420 60
415 C
T
MBD 415 -
40 40 MBD CT
50
4 2 0 - 420
MBD
30 40 30
SE CT
SE - 1200
SE CT SE - 1200
MBC 1200 30 MBC 1200
Pressure drop
Pressure drop
20 - 1900 SE CT 20
MBC 1900 SE
20
0 SE CT
10 MBC 3100 SE - 310 10
10
0 0 0
800 900 1000 1100 1200 1300 800 900 1000 1100 1200 1300
kcal/h X 1000 kcal/h X 1000
930 1000 1100 1200 1300 1400 kW 1512 930 1000 1100 1200 1300 1400 kW 1512
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 415 3970180 3000843 Accessory MBC 1200 SE CT 3970225 - Incorporated
MBD 415 CT 3970198 3000843 Incorporated MBC 1900 SE 3970222 3000825 Accessory
MBD 420 3970181 - Accessory MBC 1900 SE CT 3970226 3000825 Incorporated
MBD 420 CT 3970182 - Incorporated MBC 3100 SE 3970223 3000826 Accessory
MBC 1200 SE 3970221 - Accessory MBC 3100 SE CT 3970227 3000826 Incorporated
8
NATURAL GAS LPG
RS 190 RS 190
G20 G25 LPG
ΔP 140 ΔP
100 100
CT
Combustion head and gas train
mbar
0
- 42
20
D4 15
CT
80 MB 80 -4
100
D 415
MB 0C
T
- 42
Combustion head
Combustion head
20
D4
60 80 60 MB
CT CT
0 FC 60 0 FC
SE 5 SE 5
200 65 FC
CT
40 C- 1200 40 0F C-1 -1900 SE
50 F CT SE 5 65 FC
00 S
E 65 FC 1200 BC 19
00 SE
0 FC C
T
12 0 SE MBC M SE 8
MBC - 190 40 3100
65 FC 0 FC -
190 0 SE 10 0 SE 8
MBC 80 FC C
T MBC 3
Pressure drop
Pressure drop
20 100 SE 20
0 FC - 3
00 SE 8 20
MBC 31
0 0 0
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
kcal/h X 1000 kcal/h X 1000
1200 1279 1400 1500 1600 1700 1800 1900 2000 2100 kW 2290 1200 1279 1400 1500 1600 1700 1800 1900 2000 2100 kW 2290
Gas train Code Adapter Seal Control Gas train Code Adapter Seal Control
MBD 415 3970180 3000843 Accessory MBC 1200 SE 50 CT 3970225 3010128 Incorporated
MBD 415 CT 3970198 3000843 Incorporated MBC 1900 SE 65 FC 3970222 3000831 Accessory
MBD 420 3970181 - Accessory MBC 1900 SE 65 FC CT 3970227 3000831 Incorporated
MBD 420 CT 3970182 - Incorporated MBC 3100 SE 80 FC 3970223 3000832 Accessory
MBC 1200 SE 50 3970221 3010128 Accessory MBC 3100 SE 80 FC CT 3970228 3000832 Incorporated
note Please contact the Riello Burner Technical Office for different pressure levels from those
above indicated and refer to the technical manual for the correct choice of the spring.
In LPG plants, Multibloc gas trains do not operate below 0°'a1C. They are only suitable for
gaseous LPG (liquid hydrocarbons destroy the seal materials).
MBC 1200 gas train: the minimum operating pressure (*) is higher or equal to 10 mbar. The gas
train has to be installed next to the burner (if needed, only with the adapters listed in the
catalogue) and it has to operate in its own working field.
MBC 1900-3100 gas train: the minimum operating pressure (*) is higher or equal to 15 mbar.
The gas train has to be installed next to the burner (if needed, with the adapters listed in the
catalogue) and it has to operate in its own working field.
(*) it is the upstream gas train pressure in full load operation conditions.
9
SELECTING THE FUEL SUPPLY LINES
The following diagram enables pressure drop in a pre-existing gas line to be calculated and to select the
correct gas train.
The diagram can also be used to select a new gas line when fuel output and pipe length are known. The
pipe diameter is selected on the basis of the desired pressure drop. The diagram uses methane gas as
reference; if another gas is used, conversion coefficient and a simple formula (on the diagram) transform
the gas output to a methane equivalent (refer to figure A). Please note that the gas train dimensions must
take into account the back pressure of the combustion chamber during operations.
Control of the pressure drop in an existing gas line or selecting a new gas supply line.
The methane output equivalent is determined by the formula fig. A on the diagram and the conversion
coefficient.
Once the equivalent output has been determined on the delivery scale ( V ), shown at the top of the
diagram, move vertically downwards until you cross the line that represents the pipe diameter; at this
point, move horizontally to the left until you meet the line that represents the pipe length.
Once this point is established you can verify, by moving vertically downwards, the pipe pressure drop
of on the botton scale below (mbar).
By subtracting this value from the pressure measured on the gas meter, the correct pressure value will
be found for the choice of gas train.
45 61 76 95 122 152 V
30 1 2 3 4 5 6 7 8 10 15,34 20 30 40 50 60 80 100 200 400 600 800 1000
22
15
12
9
6
3
6"
PIP
EL
EN
GT
H(
4"
m)
3"
2"
1/
2"
2
1"
2
1/
f
4
1"
3/
{
4
1 - G20
1/
f = 0,62 - G25
2
1,18 - G31
Figure A
PIPE DIAMETER
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 1 1,4 2 3 4 5 6 10 20
PRESSURE DROP (mbar)
10
VENTILATION
COMBUSTION HEAD
Flame dimensions
ax 2 D
Lm
3 in L
Lm
1,5
2 D max
Flame diameter (m)
1
Flame lenght (m)
D min
1 0,5
Example:
Burner thermal output = 2000 kW;
L flame (m) = 2,7 m (medium value);
0 0 D flame (m) = 0,8 m (medium value)
0 1 2 3 4
Burner output (MW)
11
ADJUSTMENT
Controlled variable
°C
gradually adapts the output to the bar
requested level, by varying between
two pre-set levels (see picture A).
Time
MAX
Output
MIN
Time
Picture A
All RS series burners are fitted with a new microprocessor control panel for the supervision during
intermittent operation.
For helping the commissioning and maintenance work, there are two main elements:
Switch The lock-out reset button is the central operating element for resetting the burner control
and for activating / deactivating the diagnostic functions.
The multi-color LED is the central indication element for visual diagnosis and interface
diagnosis.
Both elements are located under the transparent cover of lock-out reset button, as showed below.
Switch
There are two diagnostic choices, for indication of operation and diagnosis of fault cause:
- visual diagnosis :
- interface diagnosis :
by the interface adapter
and a PC with dedicated
software or by a
predisposed flue gas
COMPUTER analyzer (see paragraph
INTERFACE ADAPTER accessories).
or
FLUE GAS
ANALYSER
12
Indication of operation:
After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosis
according to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.
The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3
seconds.
LED off
3 sec. 3 sec. 3 sec.
START UP CYCLE
RS 28-38-50-100-130-190
0s The burner begins the firing cycle.
TL 2s The motor starts: pre-purge phase.
TR 43 s Ignition electrode sparks; safety valve VS and
2
M
adjustment valve VR open.
45 s The spark goes out.
43 45
53 s Output can be increased; start up cycle is concluded.
VR
VS 28
2°
M 3
1°
0
2°
1°
0
53
46
RMG
LED*
3
0
time (s)
13
WIRING DIAGRAMS
P P N V T6 T8 N V
IN IN
h2 VR VS h2 S T6A
S T6A
TR h1
TR h1 TS ϑP TL TS
ϑP TL ϑP
ϑP ϑP
ϑP
VR VS PG
PG P
P
S1 1,5 mm2
1,5 mm2
XP
PE N L
PE N L T8 T7 T6 B5 N L1
~ 50Hz 230V
h1 - Hour meter
h2 - Hour meter
50Hz 230V ~
h1 - Hour meter IN - Manual switch
h2 - Hour meter XP - Seal control plug
IN - Manual switch VPS X4 - 4 pin plug
MB - Burner auxiliary terminal board X6 - 6 pin plug
X4 - 4 pin plug X7 - 7 pin plug
X6 - 6 pin plug PG - Minimum gas pressure switch
X7 - 7 pin plug S - External lock-out signal
PG - Minimum gas pressure switch S1 - External lock-out signal on the seal control
S - External lock-out signal TR - High/low flame setting thermostat
TR - High/low flame setting thermostat TL - Threshold thermostat
TL - Threshold thermostat TS - Safety thermostat
TS - Safety thermostat VPS - Seal control
VR - Adjustment valve VR - Adjustment valve
VS - Safety valve VS - Safety valve
T6A - 6A fuse T6A - 6A fuse
P P N V T6 T8 N V
IN IN
h2 VR VS h2 S T6A
S T6A
TR h1
TR h1 TS ϑP TL TS
VR VS ϑP TL ϑP
PG ϑP ϑP
ϑP
P PG
P T6A
T6A
S1
1,5 mm2
1,5 mm2 XP
T8 T7 T6 B5 N L1 1,5 mm2 PE N L
1,5 mm2
PE N L
L3 PE L2 L1
~ 50Hz 230V
L3 PE L2 L1 ~ 50Hz 230V
~ ~
3N 50Hz 400/230V M
~
3N 50Hz 400/230V
~
3 50Hz 230V 3
M
~ VPS ~
3 50Hz 230V 3
h1 - Hour meter
h2 - Hour meter
h1 - Hour meter IN - Manual switch
h2 - Hour meter XP - Seal control plug
IN - Manual switch X4 - 4 pin plug
MB - Burner auxiliary terminal board X5 - 5 pin plug
X4 - 4 pin plug X6 - 6 pin plug
X5 - 5 pin plug X7 - 7 pin plug
X6 - 6 pin plug PG - Minimum gas pressure switch
X7 - 7 pin plug S - External lock-out signal
PG - Minimum gas pressure switch S1 - External lock-out signal on the seal control
S - External lock-out signal TR - High/low flame setting thermostat
TR - High/low flame setting thermostat TL - Threshold thermostat
TL - Threshold thermostat TS - Safety thermostat
TS - Safety thermostat VPS - Seal control
VR - Adjustment valve VR - Adjustment valve
VS - Safety valve VS - Safety valve
T6A - 6A fuse T6A - 6A fuse
14
RS 70-100-130-190 - without seal control RS 70-100-130-190 - with seal control
MB L1 L2 L3 N L 1 2 3 4 5 6 7 8 N V MB L1 L2 L3 N L 1 2 3 4 5 6 7 8 N V
P P N V T8 T6 N V
T6A TL TR T6A
TS S ϑP ϑP TL TR
TS S ϑP ϑP
ϑP ϑP
F IN VS VR F
PG IN PG
P VS VR P
L S1
L XP
N L N L
~ 50Hz
T8 T7 T6 B5 N L1
PE L1 L2 L3 230V ~ 50Hz 230V
PE L1 L2 L3
~
3N 50Hz 400/230V M
~
~
3 50Hz 230V 3 ~
3N 50Hz 400/230V M
~
~
3 50Hz 230V 3 VPS
The following table shows the supply lead sections and the type of fuse to be used.
EMISSIONS
mg/kWh
125 40
100
30
75
20
50
25 10
0 0
RS 28 RS 38 RS 50 RS 70 RS 100 RS 130 RS 190 RS 28 RS 38 RS 50 RS 70 RS 100 RS 130 RS 190
NOISE EMISSIONS
100
dB(A)
80
0
RS 28 RS 38 RS 50 RS 70 RS 100 RS 130 RS 190
15
OVERALL DIMENSIONS (mm)
BURNERS
RS 28 - 38 - 50 RS 70 - 100 - 130
E A E
A L F B C L F - F (1)
F (1)
H H
D V
M I V
D
N M I
O - O (1)
S
O - O (1)
RS 190
A E
B C L F - F (1) O - O (1)
V
D
I
M
BURNER SETTING
17
BURNER ACCESSORIES
Spacer kit
If burner head penetration into the combustion chamber needs reducing, varying thickness spacers
are available, as given in the following table:
Spacer kit
Burner Spacer thickness S (mm) Kit code
RS 28 - 38 - 50 90 3010095
RS 70 - 100 - 130 135 3010129
S
RS 190 102 3000722
If the burner requires continuous ventilation in the stages without flame, a special kit is available as
given in the following table:
Post-ventilation kit
To prolong ventilation for approximately 5 seconds after opening of thermostats chain, a special kit
is available.
Post-ventilation kit
Burner Kit code
RS 28 - 38 - 50 - 70 - 100 - 130 - 190 3010004
18
Sound proofing box
If noise emission needs reducing even further, sound-proofing boxes are available, as given in the
following table:
LPG kit
For burning LPG gas, a special kit is available to be fitted to the combustion head on the burner, as
given in the following table:
LPG kit
Burner Kit code for Kit code for
‘standard head’ ‘extended head’
RS 28 3010089 3010089
RS 38 3010090 3010090
RS 50 3010165 3010165
RS 70 3010097 3010098
RS 100 3010099 3010100
RS 130 3010101 3010102
RS 190 3010166 -
19
Vibration reduction kit
The kit allow you to improve flame stability in some applications, where the boiler/flue assembly
is liable to resonate.
The RS burners can be equipped with an exclusive electronic device “Status Panel” which continuously
monitors and displays all the burner operational modes and picks up any anomalies during the
operational cycle.
A “Ground fault interrupter kit” is available as a safety device for electrical system fault.
20
Interface adapter kit
To connect the flame control panel to a personal computer for the transmission of operation, fault
signals and detailed service information, an interface adapter with PC software are available.
A kit is available for use where the burner opening on the boiler is of excessive diameter.
21
GAS TRAIN ACCESSORIES
Adapters
When the diameter of the gas train is different from the set diameter of the burners, an adapter must
be fitted between the gas train and the burner. The following table lists the adapters for various
burners.
Adapters
Burner Gas train Dimensions Adapter code
22
Seal control kit
To test the valve seals on the gas train, a special “seal control kit” is available. The valve seal control
device is compulsory (EN 676) on gas trains to burners with a maximum output over 1200 kW. The
sealing control is type VPS 504.
Stabiliser spring
Accessory springs are available to vary the pressure range of the gas train stabilisers. The following
table shows these accessories with their application range.
Stabiliser springs
Gas train Spring Spring code
White from 4 to 20 mbar 3010381
MBC 1900
Red from 20 to 40 mbar 3010382
MBC 3100
Black from 40 to 80 mbar 3010383
MBC 5000
Green from 80 to 150 mbar 3010384
Please refer to the technical manual for the correct choice of spring.
23
SPECIFICATION
DESIGNATION OF SERIES
Series : R
Size
Auxiliary voltage :
230/50-60 230V/50-60Hz
110/50-60 110V/50-60Hz
ID:
Differential
switch
24
AVAILABLE BURNER MODELS
25
PRODUCT SPECIFICATION
Burner
Monoblock forced draught gas burner with two stage operation, fully automatic, made up of:
- Air suction circuit lined with sound-proofing material
- Fan with reverse curve blades (straight blades on the 190 model) high performance with low sound
emissions
- Air damper for air flow setting and butterfly valve for regulating fuel output on 1st and 2nd stage
controlled by a servomotor with variable cam
- Starting motor at 2800 rpm, three-phase 400V with neutral, 50Hz (available also single-phase, 230V,
50Hz for the RS 28 and 38 models)
- Combustion head, that can be set on the basis of required output, fitted with:
- stainless steel end cone, resistant to corrosion and high temperatures
- ignition electrodes
- ionisation probe
- gas distributor
- flame stability disk
- Minimum air pressure switch stops the burner in case of insufficient air quantity at the combustion
head
- Microprocessor-based flame control panel, with diagnostic functions
- Plug and socket for electrical connections (RS 28-38-50 models)
- Burner on/off selection switch
- 1st - 2nd stage manual switch
- Flame inspection window
- Slide bars for easier installation and maintenance
- Protection filter against radio interference
- IP 44 electric protection level.
Gas train
Fuel supply line, in the MULTIBLOC configuration (from a diameter of 3/4” until a diameter 2”) or
COMPOSED configuration (from a diameter of DN 65 until a diameter of DN 100), fitted with:
- Filter
- Stabiliser
- Minimum gas pressure switch
- Safety valve
- Valve seal control (for output > 1200 kW)
- One stage working valve with ignition gas output regulator.
Conforming to:
- 89/336/EEC directive (electromagnetic compatibility)
- 73/23/EEC directive (low voltage)
- 92/42/EEC directive (performance)
- 90/396/EEC directive (gas)
- EN 676 (gas burners).
Standard equipment
- 1 gas train gasket
- 1 flange gasket
- 4 screws for fixing the flange
- 1 thermal screen
- 4 screws for fixing the burner flange to the boiler
- Wiring loom fittings for the electrical connection (RS 28 - 38 - 50)
- 2 slide bar extensions (for extended head models and RS 190 model)
- Instruction handbook for installation, use and maintenance
- Spare parts catalogue.
26
27
Lineagrafica.it
RIELLO S.p.A. - Via Ing. Pilade Riello, 5 - 37048 San Pietro di Legnago (VR) Italy
Tel. ++39.0442630111 - Fax ++39.044221980
ISO 9001 Cert. n. 0061 Internet: http://www.rielloburners.com - E-mail: info@rielloburners.com
Since the Company is constantly engaged in the production improvement, the aesthetic and
dimensional features, the technical data, the equipment and the accessories can be changed.
This document contains confidential and proprietary information of RIELLO S.p.A.
Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.