Anda di halaman 1dari 134

STANDAR SPLN S5.

001: 2008
Lampiran Surat Keputusan Direksi
PT PLN (PERSERO) PT PLN (PERSERO) No.168.K/DIR/2009

TELEINFORMASI DATA UNTUK


OPERASI JARINGAN TENAGA LISTRIK

PT PLN (PERSERO)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160
STANDAR SPLN S5.001: 2008
Lampiran Surat Keputusan Direksi
PT PLN (PERSERO) PT PLN (PERSERO) No.168.K/DIR/2009

TELEINFORMASI DATA UNTUK


OPERASI JARINGAN TENAGA LISTRIK

PT PLN (PERSERO)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160
PT PLN (PERSERO)

TELEINFORMASI DATA UNTUK


OPERASI JARINGAN TENAGA LlSTRIK

Disusun oleh:

Kelompok Bidang SCADA dengan


Surat Keputusan Direksi
PT PLN (PERSERO) No.094.K/DIR/2006

Kelompok Kerja
Kaidah Rancangan Dasar Sistem SCADA Untuk
Operasi Jaringan tenaga Listrik
dengan Surat Keputusan General Manager
PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan
No. 006.K/LITBANG/2007

Diterbitkan oleh : PT
PLN (PERSERO)
JL. Trunojoyo Blok M-1 /135, Kebayoran Baru
Jakarta Selatan 12160

Diterbitkan oleh :

PT PLN (PERSERO)
Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160
Susunan Kelompok Bidang SCADA Standardisasi
Surat Keputusan Direksi PT PLN (PERSERO) No: 094.K/DIR/2006

1. Ir. Nur Pamudji, M.Eng, MPM : Sebagai Ketua merangkap Anggota


2. Ir. Harry Hartoyo, MM, MPM : Sebagai Wakil Ketua merangkap Anggota
3. Ir. Hernadi Buhron : Sebagai Sekretaris merangkap Anggota
4. Novrizal Erdiansyah, ST : Sebagai Wakil Sekretaris merangkap Anggota
5. Ir. Solida : Sebagai Anggota
6. Ir. Sudibyo : Sebagai Anggota
7. Agus H Maulana, ST : Sebagai Anggota
8. Ir. Joko Pramono : Sebagai Anggota
9. Ir. A. Sugeng Sugarjito : Sebagai Anggota
10. Ir. Yarid Pabisa : Sebagai Anggota
11. Ir. Ruly Chaerul : Sebagai Anggota
12. Ir. Herry Santoso : Sebagai Anggota
13. Ir. Yanuar I. Prakoso : Sebagai Anggota
14. Ir. Hesti Sayoga : Sebagai Anggota
15. Ir. Deany EA Rumengan : Sebagai Anggota

Susunan kelompok kerja


Kaidah Rancangan Dasar Sistem SCADA Untuk Operasi Jaringan
Tenaga Listrik
Surat Keputusan General Manager PT PLN (Persero) Litbang Ketenagalistrikan
No: 006.K/LITBANG/2007

1. Ir. Solida : Sebagai Ketua merangkap Anggota


2. Novrizal Erdiansyah, ST : Sebagai Sekretaris merangkap Anggota
3. Ir. A. Sugeng Sugarjito : Sebagai Anggota
4. Ir. Ruly Chaerul : Sebagai Anggota
5. Tri Hardimasyar, ST : Sebagai Anggota
6. Ir. Yarid Pabisa : Sebagai Anggota
7. Ir. Joko Pramono : Sebagai Anggota
8. Ir. Denden Ruhdani : Sebagai Anggota
SPLN S5.001: 2008

Daftar Isi

Daftar Isi ............................................................................................................................ i


Daftar Table ........................................................................................................................ ii
Daftar Gambar ................................................................................................................... iii
Prakata .............................................................................................................................. iv
1 Ruang Lingkup ............................................................................................................. 1
2 Tujuan ........................................................................................................................ 1
3 Acuan Normatif ......................................................................................................... 1
4 Istilah dan Definisi ........................................................................................................ 1
4.1 Alarm ................................................................................................................... 1
4.2 Control center ...................................................................................................... 1
4.3 Distribution control center (DCC) .......................................................................... 1
4.4 Feeder colouring ..................................................................................................... 2
4.5 Gardu hubung.................................................................................................... 2
4.6 Gardu tengah..................................................................................................... 2
4.7 Earth Fault Indicator (EFI) ...................................................................................... 2
4.8 Inter distribution control center (IDCC) ................................................................. 2
4.9 Inter regional control center (IRCC) ...................................................................... 2
4.10 Keypoint ............................................................................................................ 2
4.11 National control center (NCC) ............................................................................... 2
4.12 Regional control center (RCC) .............................................................................. 2
4.13 Supervisory control and data acquisition (SCADA) ............................................. 2
4.14 Telecontrol .................................................................................................................................... 2
4.15 Telesignal............................................................................................................ 2
4.16 Telemetering ..................................................................................................... 2
4.17 Teleprotection .............................................................................................. 3
5 Umum 3
5.1 Fasilitas SCADA ........................................................................................... 3
5.2 Teleinformasi data ......................................................................... 3
5.3 Struktur informasi. .................................................................................................. 3
5.4 Simbol dan warna ......................................................................................... 3
6 Perbatasan Kebutuhan Teleinformasi Data ................................................................................. 3
6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC.. ................... 4
6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC ...................... 10

Lampiran A –Daftar Teleinformasi (Transmisi) ................................................................... 6


Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi
Gardu Induk) .............................................................................................. 10
Lampiran C – Daftar Teleinformasi (Distribusi) ................................................................................ 80
Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan
Distribusi) .......................................................................................................................................... 86
Lampiran E – Struktur Informasi ......................................................................................................................... 105
Lampiran F – Simbol dan Warna ....................................................................................................................... 118

i
SPLN S5.001: 2008

Daftar Tabel

Tabel 1. Struktur informasi .............................................................................................109


Tabel 2. Level tegangan .................................................................................................... 111
Tabel 3. Nama bay atau feeder ..........................................................................................................................................112
Tabel 4. Kode tegangan dari primer dan sekunder trafo ..........................................................................112
Tabel 5. Kode nama peralatan/alarm/elemen ..............................................................113
Tabel 6. Warna tampilan ..............................................................................................113

Daftar Gambar

Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a) ................................ 4


Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b) ................................ 4
Gambar 3. Batas wewenang antara RCC dengan DCC............................................. 5
Gambar 4. Struktur informasi khusus (bay diameter) ..................................................115
Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker) ..................................116
Gambar 6. Simbol gambar ...........................................................................................116
Gambar 7. Tampilan status ..........................................................................................................................117

ii
SPLN S5.001: 2008

Prakata

Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996,
dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan
mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian,
yaitu:

1. S3.001: 2008 Peralatan SCADA sistem tenaga listrik


2. S5.001: 2008 Teleinformasi data untuk operasi jaringan tenaga listrik
3. S5.002: 2008 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik
4. S4.001: 2008 Pengujian sistem SCADA
5. S6.001: 2008 Perencanaan dan pembangunan sistem SCADA
6. S7.001: 2008 Operasi dan pemeliharaan sistem SCADA

Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2008 dan
direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA.

Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi
data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan
pemeliharaan yang memiliki hubungan dengan sistem SCADA.

Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan
pemeliharaan sistem SCADA di PT PLN (PERSERO) secara nasional.

iii
SPLN S5.001: 2008

TELEINFORMASI DATA
UNTUK OPERASI JARINGAN TENAGA LISTRIK

1 Ruang Lingkup

Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan
penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan
pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data
untuk kepentingan operasi dan mencakup sistem transmisi dan sistem distribusi.

Standar ini berlaku untuk sistem SCADA:


- National Control Center, disingkat NCC;
- Inter Regional Control Center, disingkat IRCC;
- Regional Control Center, disingkat RCC;
- Inter Distribution Control Center, disingkat IDCC;
- Distribution Control Center, disingkat DCC.

2 Tujuan

Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam
penerapan teleinformasi data bagi kebutuhan operasi sistem transmisi dan sistem
distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini
merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem
SCADA yang telah ada.

3 Acuan Normatif

Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam


pembuatan standar SCADA: Teleinformasi Data Untuk Operasi Jaringan Tenaga Listrik.
- SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol – Bagian 1:
Pertimbangan Umum – Seksi 1: Prinsip Umum;
- Keputusan Menteri Energi dan Sumberdaya Mineral Nomor:
150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali;

4 Istilah dan Definisi

4.1 Alarm

Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena
fungsi yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk
merespon secara benar. Indikasi alarm berupa audible atau visual, atau keduanya.

4.2 Control center

Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.


SPLN S5.001: 2008

4.3 Distribution control center (DCC)


Pusat kendali jaringan distribusi.

4.4 Feeder colouring


Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan.

4.5 Gardu hubung

Gardu yang mempunyai fungsi utama melakukan manuver antar feeder.

4.6 Gardu tengah


Gardu yang merupakan titik tengah beban atau titik tengah feeder.

4.7 Earth Fault Indicator (EFI)


Penunjukan arah dari indikator gangguan tanah.

4.8 Inter distribution control center (IDCC)


Pusat kendali yang terhubung dengan beberapa distribution control center.

4.9 Inter regional control center (IRCC)


Pusat kendali yang terhubung dengan beberapa regional control center.

4.10 Keypoint
Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih.

4.11 National control center (NCC)

Pusat kendali yang terhubung dengan beberapa inter regional control center.

4.12 Regional control center (RCC)


Pusat kendali jaringan transmisi tegangan tinggi.

4.13 Supervisory control and data acquisition (SCADA)


Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara
geografis. [ IEC 870-1-3 ]

4.14 Telecontrol
Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik
telekomunikasi. [IEV 371-01-01]
CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran,
proteksi dan fasilitas tripping, tidak menggunakan pesan suara.

4.15 Telesignal
Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan
teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-
04]


SPLN S5.001: 2008

4.16 Telemetering
Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV
371-01-03]

4.17 Teleprotection
Peralatan komunikasi yang diperlukan oleh sistem proteksi yang berfungsi untuk
pengamanan peralatan sistem tenaga listrik.

5 Umum

5.1 Fasilitas SCADA

Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point
dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan
dilakukan pengujian sebelum diintegrasikan ke sistem transmisi atau sistem distribusi
tenaga listrik.

5.2 Teleinformasi data

Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi
data untuk operasi jaringan tenaga listrik dapat dilihat pada Lampiran A –
Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi
(Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi).
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi, maka
master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi
yang digunakan mengacu pada teleinformasi data transmisi dan distribusi.
Teleinformasi data untuk kepentingan operasi jaringan tenaga listrik ditampilkan pada
workstation dispatcher.
Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi
datanya harus mengacu pada SPLN S5.001: 2008 Teleinformasi data untuk operasi
jaringan tenaga listrik dan SPLN S5.002: 2008 Teleinformasi data untuk pemeliharaan
instalasi sistem tenaga listrik.

5.3 Struktur informasi

Event dan alarm merupakan pemberitahuan kepada dispatcher atau operator tentang
kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data
historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada Lampiran E –
Struktur Informasi.

5.4 Simbol dan warna

Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor
dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat
informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut
mudah dikenali oleh dispatcher. Simbol dan warna dapat dilihat pada Lampiran F
– Simbol dan Warna.

6 Perbatasan Kebutuhan Teleinformasi Data

Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh
kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas
antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan
perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan
DCC. 
mudah dikenali oleh dispatcher. Simbol dan warna dapat dilihat pada Lampiran F
– Simbol dan Warna.

6 Perbatasan Kebutuhan Teleinformasi Data


SPLN S5.001: 2008
Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh
kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas
antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan
perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan
DCC.
6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC

Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan
tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti gambar 1
dan gambar 2.
a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar.

BUSBAR TET/TT

IRCC

RCC

BUSBAR TT

Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a)

b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker.


B U S B A R T E T /T T

BUSBAR
TT

IR C C

RCC

BUSBAR
TT

Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b)


SPLN S5.001: 2008

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC


Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk
ditunjukkan pada gambar 3.

BUSBAR TT

L /R

P Q
V
I
RCC

DCC

BUSBAR TM

Gambar 3. Batas wewenang antara RCC dengan DCC

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum
dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi
data dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan
SOP yang berlaku di daerah tersebut.


SPLN S5.001: 2008

LAMPIRAN A – DAFTAR TELEINFORMASI (TRANSMISI)

A-1: Telesignal

Single (S) Suggested


or Double Alarm (A) or
No Kode Fungsi Implementasi
(D) Event
Indication /Indication (I)
Kopel,
Feeder, Trafo,
1 BI Bus isolator switch closed/opened Diameter, D I
Capasitor,
Reaktor

2 CAM Capasitor Auto/Manual Capasitor D I

Kopel,
Feeder, Trafo,
3 CB Circuit breaker closed/opened Diameter, D I
Capasitor,
Reaktor
4 CD Control disable switch RTU D I
Gardu induk,
Kopel,
5 CSO Check synchronizing override D I
Feeder,
Diameter
6 DCBC Dummy breaker closed/opened Gardu induk D I
Kopel,
Feeder, Trafo,
7 ES Earth Switch Closed/Opened Diameter, D I
Capasitor,
Reaktor
8 GUC Generator unit run/stop Generator D I
9 LFA Load frequency available/not available Generator D I
10 LFC Load frequency control on/off switch Generator D I
11 LFR Load frequency request on/off Generator D I
12 LI Line isolator switch closed/opened Feeder, Trafo D I
Gardu induk,
Kopel,
Feeder, Trafo,
13 LR Local remote D I
Diameter,
Capasitor,
Reaktor
14 LRT Local remote switch for tapchanger Trafo D I
15 PSO Power station operated Generator D I
Distribution
16 RACK Circuit Breaker Rack-In/Rack-Out D I
Transformer
17 RMT Reset Master Trip Gardu induk D I
Gardu induk,
Kopel,
18 SAM Synchronization Auto/Manual D I
Feeder, Trafo,
Diameter
19 TC Tap changer raise/lower Trafo D I
20 TCC Tap changer auto/manual Trafo D I
21 TFAM Transformer Fan Auto/Manual Transformer D I
22 AQR Automatic power factor regulator active Generator S I
23 AR Circuit breaker auto reclose Feeder S I


SPLN S5.001: 2008

Single (S) Suggested


or Double Alarm (A) or
No Kode Fungsi Implementasi
(D) Event /
Indication Indication
(I)
24 ARO Auto reclose off Feeder S I
25 AVR Automatic voltage regulator on/off Generator S I
Kopel,
Feeder, Trafo,
26 BF Bay fault dc Diameter, S A
Capasitor,
Reaktor
Kopel,
Feeder, Trafo,
27 BRF Breaker fault Diameter, S A
Capasitor,
Reaktor
Kopel,
Feeder, Trafo,
Diameter,
28 CBTR Circuit breaker trip S A
Capasitor,
Reaktor,
Generator
29 COM Communication faulty Gardu induk S A
30 CSP Check synchronizing in progress Gardu induk S I
31 GOV Free acting governor active Generator S I
Trafo
32 GTT Generator transformer trip S A
Generator
33 LFF Load frequency control unit failure Generator S A
34 OVR Over voltage relay operate Busbar S A
35 P1BP Busbar protection Busbar S A
36 P1CD Current defferential Feeder S A
37 P1DEF Directional earth fault Feeder S A
Trafo,
38 P1DIF Differential Capasitor, S A
Reaktor
39 P1REF Restricted earth fault Trafo S A
40 P1Z1 Distance protection zone 1 Feeder S A
41 P1Z2 Distance protection zone 2 Feeder S A
42 P1Z3 Distance protection zone 3 Feeder S A
Kopel,
Feeder, Trafo,
43 P2GFR Ground fault relay S A
Capasitor,
Reaktor
Kopel,
Feeder, Trafo,
44 P2OCR Over current relay S A
Capasitor,
Reaktor
45 P3DTT Direct transfer trip Diameter S A
46 PTF Protection faulty Gardu induk S A
47 PHA Peripheral alarm Gardu induk S A
48 RA Reactor alarm Reactor S A
49 RF Reactor failure Reactor S A
50 RT Reactor Trip Reactor S A
51 RTUA RTU alarm RTU S A
52 SYNF Synchronizing failure Gardu induk S A
53 TAF Tranformer AVR failure Trafo S A
54 TCA Tap changer alarm Trafo S A
55 TCH Tap changer high limit Trafo S A


SPLN S5.001: 2008

Single (S) Suggested


or Double Alarm (A) or
No Kode Fungsi Implementasi
(D) Event/Indication
Indication (I)
56 TCL Tap changer low limit Trafo S A
57 TEA Temperature alarm Trafo S A
58 TET Temperature trip Trafo S A
59 TRA Transformer alarm Trafo S A
60 TRT Transformer trip Trafo S A
61 TTR Teleprotection trip receive Feeder S I
62 TTT Teleprotection trip transmit Feeder S I
63 UT Unit trip Generator S A
64 UVR Under voltage relay Busbar S A
65 VACF Vac failure Gardu induk S A
66 VDCF Vdc failure Gardu induk S A
67 VS Voltage status Busbar S I
68 SIB Software interlocking bypass Gardu Induk S A
69 IEDF IED Faulty Gardu Induk S A
70 SOTF Switch on to fault Gardu Induk S A
71 MTO Master Trip Operate Gardu Induk S A
72 TCT Tap changer trip Trafo S A

Keterangan:
A = Announciation of abnormal condition (audible alarm, flashing display, etc)
I = Event/Indication (normal condition)

A-2: Telemeasurement

No Kode Fungsi Implementasi

1 F Frekuensi Gardu induk

Feeder, InterBus Transformer, Generator


2 I Arus
Transformer, Kopel

3 P Daya Aktif Feeder, Transformer, Generator

4 POAQ Real power setting Generator

5 PRAQ Maksimum power variation setting Generator

Feeder, Transformer, Generator,


6 Q Daya Reaktif
Capasitor, Reaktor

Feeder, InterBus Transformer, Generator,


7 V Tegangan
Busbar


SPLN S5.001: 2008

A-3: Tap changer position

No Kode Fungsi Implementasi

1 TPI Tap Position indication Transformer

A-4: Remote control digital

No Kode Fungsi Implementasi

Kopel, Feeder, Transformer,


1 BI Bus isolator switch closed/opened
Capasitor, Reaktor, Diameter

Kopel, Feeder, Transformer,


2 CB Circuit breaker closed/opened
Capasitor, Reaktor, Diameter

3 CSO Check synchronizing override Gardu induk

4 DCBC Dummy circuit breaker closed/opened RTU

5 GUC Generator Unit Run/Stop Generator

6 LFR Load frequency request on/off Generator

7 TC Tap changer raise/lower Interbus Transformer

8 TCC Tap changer auto/manual Interbus Transformer

A-5: Remote control analog

No Kode Fungsi Implementasi

1 N Load frequency control N_level Generator

2 POOP Real power set point Generator

3 PROP Maksimum power variation set point Generator


SPLN S5.001: 2008

LAMPIRAN B – BIDANG TRANSMISI (TELEINFORMASI PADA


BERBAGAI KONFIGURASI GARDU INDUK)

TA-01: Konfigurasi umum pada 1½ breaker

TA-01
KONFIGURASI UMUM PADA 1½ BREAKER

BAY REAKTOR BAY GENERATOR

P LFC
Q (Po,Pr,N)
V

P
Q Q
I
BUSBAR - A

L/R L/R

L/R L/R L/R

L/R L/R L/R

BUSBAR - B
V
P
L/R Q
P P
Q Q
V V L/R
I I
BAY TRANSMISI BAY IBT BAY TRAFO TENAGA

10
SPLN S5.001: 2008

Teleinformasi Data Untuk Konfigurasi Umum Pada 1½ Breaker


Group Bay Data No Kode Fungsi Tipe Jmh
TM 1 F Frekuensi 1
29 COM Communication alarm A 1
46 PTF Protection faulty A 1
47 PHA Peripheral alarm A 1
51 RTUA RTU alarm A 1
52 SYNF Synchronizing failure A 1
TSS 65 VACF Vac failure A 1
66 VDCF Vdc failure A 1
GARDU 68 SIB Software interlocking bypass A 1
INDUK 69 IEDF IED faulty A 1
70 SOTF Switch on to fault A 1
71 MTO Master Trip Operate A 1
4 CD Control disable switch I 1
5 CSO Check synchronizing override I 1
TSD
6 DCBC Dummy breaker closed/opened I 1
13 LR Local remote I 1
3 CSO Check synchronizing override 1
RCD
4 DCBC Dummy breaker closed/opened 1
TM 7 V Tegangan 2
26 BF Bay fault DC A 2
34 OVR Over voltage relay operate A 2
BUSBAR
TSS 35 P1BP Busbar protection A 2
64 UVR Under voltage relay A 2
67 VS Voltage status A 2
27 BRF Breaker fault A 3
TSS 28 CBTR CB trip A 3
30 CSP Check synchronizing in progress I 3
1 BI Bus isolator switch I 6
DIAMETER 3 CB Circuit breaker closed/opened I 3
TSD
5 CSO Check synchronizing override I 3
13 LR Local remote I 3
1 BI Bus isolator switch 6
RCD
2 CB Circuit breaker closed/opened 3
BAY 2 I Arus 1
TRANSMISI 3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
TSS 23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
40 P1Z1 *) Distance zone 1 A 1
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1

44 P2OCR Over current relay A 1

11
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
TSD 12 LI Line isolator switch closed/opened I 1
TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
BAY IBT
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
3 CB Circuit breaker closed/opened I 1
12 LI Line isolator switch closed/opened I 1
TSD 13 LR Local remote I 1
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
2 CB Circuit breaker closed/opened I 1
RCD 7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
26 BF Bay fault DC A 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
BAY
43 P2GFR Ground fault relay A 1
TRAFO
TENAGA TSS 44 P2OCR Over current relay A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
TSD 12 LI Line isolator switch closed/opened I 1
BAY TM 6 Q Daya reaktif 1
REAKTOR TSS 26 BF Bay fault DC A 1
38 P1DIF Differential A 1

43 P2GFR Ground fault relay A 1

12
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


44 P2OCR Over current relay A 1
49 RF Reactor failure A 1
TSD 12 LI Line isolator switch closed/opened I 1
2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
19 AQR Automatic power factor regulator on/off I 1
25 AVR Automatic voltage regulator on/off I 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
TSS
31 GOV Free acting governor active I 1
32 GTT Generator transformer trip A 1
BAY
33 LFF Load frequency control unit failure A 1
GENERATOR
63 UT Unit trip A 1
8 GUC Generator unit run/stop I 1
9 LFA Load frequency control available I 1
10 LFC Load frequency control on/off switch I 1
TSD
11 LFR Load frequency request on/off I 1
12 LI Line isolator switch closed/opened I 1
15 PSO Power set on/off switch I 1
5 GUC Generator unit run/stop 1
RCD
6 LFR Load frequency request on/off 1
1 N Load frequency control N_level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder
A = Alarm
I = Indikasi
Untuk LFC ditampilkan di tabel LFC Generator.
Rincian Teleinformasi diatas adalah rincian per bay.

13
SPLN S5.001: 2008

TA-02: Konfigurasi umum pada double busbar

TA-02

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BAY REAKTOR BAY GENERATOR

P LFC
Q (Po,Pr,N)
V

P
Q Q
I
BAY KOPEL

L/R L/R L/R

BUSBAR - A

BUSBAR - B

L/R L/R L/R

P
Q
L/R
P P
Q Q
V V
I I
BAY TRANSMISI BAY TRAFO TENAGA BAY IBT

14
SPLN S5.001: 2008

Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar


Group Bay Data No Kode Fungsi Tipe Jmh
GARDU TM 1 F Frekuensi 1
INDUK 29 COM Communication alarm A 1
46 PTF Protection faulty A 1
47 PHA Peripheral alarm A 1
51 RTUA RTU alarm A 1
52 SYNF Synchronizing failure A 1
TSS 65 VACF Vac failure A 1
66 VDCF Vdc failure A 1
68 SIB Software interlocking bypass A 1
69 IEDF IED faulty A 1
70 SOTF Switch on to fault A 1
71 MTO Master Trip Operate A 1
TSD 4 CD Control disable switch I 1

15
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


5 CSO Check synchronizing override I 1
6 DCBC Dummy breaker closed/opened I 1
13 LR Local remote I 1
3 CSO Check synchronizing override 1
RCD
4 DCBC Dummy breaker closed/opened 1
TM 7 V Tegangan 2
26 BF Bay fault DC A 2
34 OVR Over voltage relay operate A 2
BUSBAR
TSS 35 P1BP Busbar protection A 2
64 UVR Under voltage relay A 2
67 VS Voltage status A 2
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR CB trip A 1
TSS
30 CSP Check synchronizing in progress I 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
KOPEL
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
TSD
5 CSO Check synchronizing override I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
TSS 37 P1DEF Directional earth fault A 1
BAY 40 P1Z1 *) Distance zone 1 A 1
TRANSMISI 41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
TSD 5 CSO Check synchronizing override I 1
12 LI Line isolator switch closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

16
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
BAY IBT 55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
TSD 13 LR Local remote I 1
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
1 BI Bus isolator switch 2
2 CB Circuit breaker closed/opened 1
RCD
7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
TSS 43 P2GFR Ground fault relay A 1
BAY
44 P2OCR Over current relay A 1
TRAFO
TENAGA 57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
1 BI Bus isolator switch I 2
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1
BAY TM 6 Q Daya reaktif 1

17
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


REAKTOR 26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS 38 P1DIF Differential A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
49 RF Reactor failure A 1
1 BI Bus isolator switch I 2
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1
2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 1
25 AVR Automatic voltage regulator on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 1
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 1
BAY
63 UT Unit trip A 1
GENERATOR
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
8 GUC Generator unit run/stop I 1
9 LFA Load frequency control available I 1
TSD
10 LFC Load frequency control on/off switch I 1
11 LFR Load frequency request on/off I 1
13 LR Local remote I 1
15 PSO Power set on/off switch I 1
1 BI Bus isolator switch 2
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 1
6 LFR Load frequency request on/off 1
1 N Load frequency control N level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder
A = Alarm
I = Indikasi
Untuk LFC ditampilkan di tabel LFC Generator.
Rincian Teleinformasi diatas adalah rincian per bay

18
SPLN S5.001: 2008

TA-03: Konfigurasi umum pada single busbar

TA-03

KONFIGURASI UMUM PADA SINGLE BUSBAR

BAY REAKTOR BAY GENERATOR

LFC
P
Q (Po,Pr,N)
V

P
Q Q
I

L/R L/R

BUSBAR

L/R L/R L/R

P
Q L/R
P P
Q Q
V V
I I
BAY TRANSMISI BAY TRAFO TENAGA BAY IBT

19
SPLN S5.001: 2008

Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar


Group Bay Data No Kode Fungsi Tipe Jmh
GARDU TM 1 F Frekuensi 1
INDUK 29 COM Communication alarm A 1
46 PTF Protection faulty A 1
47 PHA Peripheral alarm A 1
51 RTUA RTU alarm A 1
52 SYNF Synchronizing failure A 1
TSS
65 VACF Vac failure A 1
66 VDCF Vdc failure A 1
68 SIB Software interlocking bypass A 1
69 IEDF IED faulty A 1
70 SOTF Switch on to fault A 1
71 MTO Master Trip Operate A 1
TSD 4 CD Control disable switch I 1
5 CSO Check synchronizing override I 1
6 DCBC Dummy breaker closed/opened I 1

20
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


13 LR Local remote I 1
3 CSO Check synchronizing override 1
RCD
4 DCBC Dummy breaker closed/opened 1
TM 7 V Tegangan 1
26 BF Bay fault DC A 1
34 OVR Over voltage relay operate A 1
BUSBAR
TSS 35 P1BP Busbar protection A 1
64 UVR Under voltage relay A 1
67 VS Voltage status A 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR CB trip A 1
TSS
30 CSP Check synchronizing in progress I 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
KOPEL
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 1
TSD
5 CSO Check synchronizing override I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
TSS
40 P1Z1 *) Distance zone 1 A 1
BAY
41 P1Z2 *) Distance zone 2 A 1
TRANSMISI
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 1
TSD 5 CSO Check synchronizing override I 1
12 LI Line isolator switch closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1
BAY IBT TC 1 TPI Tap position indication I 1
TM 2 I Arus 1

21
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


3 P Daya aktif 1
6 Q Daya reaktif 1
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 1
TSD 13 LR Local remote I 1
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
1 BI Bus isolator switch 1
2 CB Circuit breaker closed/opened 1
RCD
7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
TSS 43 P2GFR Ground fault relay A 1
BAY
44 P2OCR Over current relay A 1
TRAFO
TENAGA 57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
1 BI Bus isolator switch I 1
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1
BAY TM 6 Q Daya Reaktif 1
REAKTOR TSS 26 BF Bay fault DC A 1
27 BRF Breaker fault A 1

22
SPLN S5.001: 2008

Group Bay Data No Kode Fungsi Tipe Jmh


28 CBTR Circuit breaker trip A 1
38 P1DIF Differential A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
49 RF Reactor failure A 1
1 BI Bus isolator switch I 1
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1
2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 1
25 AVR Automatic voltage regulator on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 1
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 1
BAY
63 UT Unit trip A 1
GENERATOR
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 1
8 GUC Generator unit run/stop I 1
9 LFA Load frequency control available I 1
TSD
10 LFC Load frequency control on/off switch I 1
11 LFR Load frequency request on/off I 1
13 LR Local remote I 1
15 PSO Power set on/off switch I 1
1 BI Bus isolator switch 1
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 1
6 LFR Load frequency request on/off 1
1 N Load frequency control n level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder
A = Alarm
I = Indikasi
Untuk LFC ditampilkan di tabel LFC Generator.
Rincian Teleinformasi diatas adalah rincian per
bay

23
SPLN S5.001: 2008

TB-01: Generator combined cycle pada konfigurasi 1½ breaker

GENERATOR COMBINED CYCLE TB-01

PADA KONFIGURASI 1½ BREAKER

LFC
Joint Control
(Po,Pr,N)

P P P P
Q Q Q Q
V V V V

P P P
Q Q Q
I I I BUSBAR- A

BUSBAR- B

Teleinformasi Data Untuk Generator Combined Cycle Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 3
3 P Daya aktif 7
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 7
7 V Tegangan 4
TSS 22 AQR Automatic power factor regulator on/off I 4
25 AVR Automatic voltage regulator on/off I 4
26 BF Bay fault DC A 3

24
SPLN S5.001: 2008

Data No Kode Fungsi Tipe Jmh


30 CSP Check synchronizing in progress I 3
31 GOV Free acting governor active I 4
32 GTT Generator transformer trip A 3
33 LFF Load frequency control unit failure A 1
63 UT Unit trip A 4
3 CB Circuit breaker closed/opened I 2
8 GUC Generator unit run/stop I 4
9 LFA Load frequency control available I 1
TSD 10 LFC Load frequency control on/off switch I 1
11 LFR Load frequency request on/off I 1
12 LI Line isolator switch closed/opened I 3
15 PSO Power set on/off switch I 4
5 GUC Generator unit run/stop 4
RCD
6 LFR Load frequency request on/off 1
1 N Load frequency control N level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

25
SPLN S5.001: 2008

TB-02: 2 generator terhubung ke MTR 3-belitan pada konfigurasi 1½ breaker

TB-02
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN
PADA KONFIGURASI 1½ BREAKER

LFC LFC
(Po,Pr,N) (Po,Pr,N)

P P
Q Q
V V

P
Q
I

BU
SBAR - A

BUSBAR - B

26
SPLN S5.001: 2008

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi


1½ Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 3
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 3
7 V Tegangan 2
22 AQR Automatic power factor regulator on/off I 2
25 AVR Automatic voltage regulator on/off I 2
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
TSS
31 GOV Free acting governor active I 2
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 2
63 UT Unit trip A 2
3 CB Circuit breaker closed/opened I 2
8 GUC Generator unit run/stop I 2
9 LFA Load frequency control available I 2
TSD 10 LFC Load frequency control on/off switch I 2
11 LFR Load frequency request on/off I 2
12 LI Line isolator switch closed/opened I 1
15 PSO Power set on/off switch I 2
5 GUC Generator unit run/stop 2
RCD
6 LFR Load frequency request on/off 2
1 N Load frequency control N level 2
RCA 2 POOP Real power set point 2
3 PROP Maksimum power variation set point 2

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

27
SPLN S5.001: 2008

TB-03: 2 generator terhubung ke MTR 3-belitan pada konfigurasi double


busbar

TB-03
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN
PADA KONFIGURASI DOUBLE BUSBAR

LFC LFC
(Po,Pr,N) (Po,Pr,N)

P P
Q Q
V V

P
Q
I

L/R

BUSBAR - A

BUSBAR - B

28
SPLN S5.001: 2008

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi


Double Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 3
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 3
7 V Tegangan 2
22 AQR Automatic power factor regulator on/off I 2
25 AVR Automatic voltage regulator on/off I 2
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 2
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 2
63 UT Unit trip A 2
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 3
8 GUC Generator unit run/stop I 2
9 LFA Load frequency control available I 2
TSD
10 LFC Load frequency control on/off switch I 2
11 LFR Load frequency request on/off I 2
12 LR Local remote I 1
15 PSO Power set on/off switch I 2
1 BI Bus isolator switch 2
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 2
6 LFR Load frequency request on/off 2
1 N Load frequency control n level 2
RCA 2 POOP Real power set point 2
3 PROP Maksimum power variation set point 2

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

29
SPLN S5.001: 2008

TB-04: 2 generator terhubung ke MTR 3-belitan pada konfigurasi single busbar

TB-04
2 GENERATOR TERHUBUNG KE MTR 3-BELITAN
PADA KONFIGURASI SINGLE BUSBAR

LFC LFC
(Po,Pr,N) (Po,Pr,N)

P P
Q Q
V V

P
Q
I

L/R

BUSBAR

30
SPLN S5.001: 2008

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada


Konfigurasi single Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 3
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 3
7 V Tegangan 2
22 AQR Automatic power factor regulator on/off I 2
25 AVR Automatic voltage regulator on/off I 2
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 2
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 2
63 UT Unit trip A 2
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 3
8 GUC Generator unit run/stop I 2
9 LFA Load frequency control available I 2
TSD
10 LFC Load frequency control on/off switch I 2
11 LFR Load frequency request on/off I 2
13 LR Local remote I 1
15 PSO Power set on/off switch I 2
1 BI Bus isolator switch 1
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 2
6 LFR Load frequency request on/off 2
1 N Load frequency control n level 2
RCA 2 POOP Real power set point 2
3 PROP Maksimum power variation set point 2

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

31
SPLN S5.001: 2008

TB-05: 1 generator terhubung ke MTR 2-belitan pada konfigurasi 1½ breaker

TB-05
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI 1½ BREAKER

LFC
P (Po,Pr,N)
Q
V

P
Q
I
BUSBAR - A

BUSBAR - B

32
SPLN S5.001: 2008

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½


Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 1
25 AVR Automatic voltage regulator on/off I 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
TSS
31 GOV Free acting governor active I 1
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 1
63 UT Unit trip A 1
8 GUC Generator unit run/stop I 1
9 LFA Load frequency control available I 1
10 LFC Load frequency control on/off switch I 1
TSD
11 LFR Load frequency request on/off I 1
12 LI Line isolator switch closed/opened I 1
15 PSO Power set on/off switch I 1
5 GUC Generator unit run/stop 1
RCD
6 LFR Load frequency request on/off 1
1 N Load frequency control n level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

33
SPLN S5.001: 2008

TB-06: 1 generator terhubung ke MTR 2-belitan pada konfigurasi double


busbar

TB-06
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI DOUBLE BUSBAR

LFC
P (Po,Pr,N)
Q
V

P
Q
I

L/R

BUSBAR - A

BUSBAR - B

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi


Double Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 1
25 AVR Automatic voltage regulator on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 1
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 1
63 UT Unit trip A 1
TSD 1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1

34
SPLN S5.001: 2008

8 GUC Generator unit run/stop I 1


9 LFA Load frequency control available I 1
10 LFC Load frequency control on/off switch I 1
11 LFR Load frequency request on/off I 1
13 LR Local remote I 1
15 PSO Power set on/off switch I 1
1 BI Bus isolator switch 2
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 1
6 LFR Load frequency request on/off 1
1 N Load frequency control n level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

TB-07: 1 generator terhubung ke MTR 2-belitan pada konfigurasi single busbar

TB-07
1 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI SINGLE BUSBAR

LFC
P (Po,Pr,N)
Q
V

P
Q
I

L/R

BUSBAR

35
SPLN S5.001: 2008

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi


Single Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 1
25 AVR Automatic voltage regulator on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 1
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 1
63 UT Unit trip A 1
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 1
8 GUC Generator unit run/stop I 1
9 LFA Load frequency control available I 1
TSD
10 LFC Load frequency control on/off switch I 1
11 LFR Load frequency request on/off I 1
13 LR Local remote I 1
15 PSO Power set on/off switch I 1
1 BI Bus isolator switch 1
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 1
6 LFR Load frequency request on/off 1
1 N Load frequency control n level 1
RCA 2 POOP Real power set point 1
3 PROP Maksimum power variation set point 1

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

36
SPLN S5.001: 2008

TB-08: 2 generator terhubung ke MTR 2-belitan pada konfigurasi 1½ breaker

TB-08
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI 1½ BREAKER

LFC LFC
(Po,Pr,N) (Po,Pr,N)

P
Q
V

P
Q
I
BUSBAR - A

BUSBAR - B

37
SPLN S5.001: 2008

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½


Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 2
25 AVR Automatic voltage regulator on/off I 2
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
TSS
31 GOV Free acting governor active I 2
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 2
63 UT Unit trip A 2
3 CB Circuit breaker closed/opened I 2
8 GUC Generator unit run/stop I 2
9 LFA Load frequency control available I 2
TSD 10 LFC Load frequency control on/off switch I 2
11 LFR Load frequency request on/off I 2
12 LI Line isolator switch closed/opened I 1
15 PSO Power set on/off switch I 2
5 GUC Generator unit run/stop 2
RCD
6 LFR Load frequency request on/off 2
1 N Load frequency control n level 2
RCA 2 POOP Real power set point 2
3 PROP Maksimum power variation set point 2

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

38
SPLN S5.001: 2008

TB-09: 2 generator terhubung ke MTR 2-belitan pada konfigurasi double


busbar

TB-09
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI DOUBLE BUSBAR

LFC LFC
(Po,Pr,N) (Po,Pr,N)

P
Q
V

P
Q
I

L/R

BUSBAR - A

BUSBAR - B

39
SPLN S5.001: 2008

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi


Double Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 2
25 AVR Automatic voltage regulator on/off I 2
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 2
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 2
63 UT Unit trip A 2
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 3
8 GUC Generator unit run/stop I 2
9 LFA Load frequency control available I 2
TSD
10 LFC Load frequency control on/off switch I 2
11 LFR Load frequency request on/off I 2
13 LR Local remote I 1
15 PSO Power set on/off switch I 2
1 BI Bus isolator switch 2
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 2
6 LFR Load frequency request on/off 2
1 N Load frequency control n level 2
RCA 2 POOP Real power set point 2
3 PROP Maksimum power variation set point 2

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

40
SPLN S5.001: 2008

TB-10: 2 generator terhubung ke MTR 2-belitan pada konfigurasi single busbar

TB-10
2 GENERATOR TERHUBUNG KE MTR 2-BELITAN
PADA KONFIGURASI SINGLE BUSBAR

LFC LFC
(Po,Pr,N) (Po,Pr,N)

P
Q
V

P
Q
I

L/R

BUSBAR

41
SPLN S5.001: 2008

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single
Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 2
4 POAQ Real power setting 1
TM
5 PRAQ Maksimum power variation setting 1
6 Q Daya reaktif 2
7 V Tegangan 1
22 AQR Automatic power factor regulator on/off I 2
25 AVR Automatic voltage regulator on/off I 2
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
30 CSP Check synchronizing in progress I 1
31 GOV Free acting governor active I 2
32 GTT Generator transformer trip A 1
33 LFF Load frequency control unit failure A 2
63 UT Unit trip A 2
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 3
8 GUC Generator unit run/stop I 2
9 LFA Load frequency control available I 2
TSD
10 LFC Load frequency control on/off switch I 2
11 LFR Load frequency request on/off I 2
13 LR Local remote I 1
15 PSO Power set on/off switch I 2
1 BI Bus isolator switch 1
2 CB Circuit breaker closed/opened 1
RCD
5 GUC Generator unit run/stop 2
6 LFR Load frequency request on/off 2
1 N Load frequency control n level 2
RCA 2 POOP Real power set point 2
3 PROP Maksimum power variation set point 2

KETERANGAN:
Untuk LFC ditampilkan di tabel LFC Generator.

42
SPLN S5.001: 2008

TB-11: Interbus transformer (secondary side connected to 1½ breaker)

TB-11
INTERBUS TRANSFORMER
Secondary Side Connected to 1½ Breaker
BUSBAR (IRCC)

L/R

P
Q
BUSBAR - A V
I

Dioperasikan dari IRCC

Download to RCC
Dioperasikan dari RCC

BUSBAR - B

43
SPLN S5.001: 2008

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1½ Breaker)

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
53 TAF Tranformer avr failure A 1
TSS 54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
12 LI Line isolator switch closed/opened I 2
13 LR Local remote I 1
TSD
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
7 TC Tap changer raise/lower 1
RCD
8 TCC Tap changer auto/manual 1

44
SPLN S5.001: 2008

TB-12: Interbus transformer

(secondary side connected to double busbar)

INTERBUS TRANSFORMER Secondary TB-12


Side Connected to Double Busbar

BUSBAR (IRCC or RCC)

L/R

P
Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


by RCC

BUSBAR - A

BUSBAR - B

45
SPLN S5.001: 2008

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double


Busbar)

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1-2 *)
28 CBTR Circuit breaker trip A 1-2 *)
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
1 BI Bus isolator switch I 2-4 *)
3 CB Circuit breaker closed/opened I 1-2 *)
12 LI Line isolator switch closed/opened I 1-0 *)
TSD
13 LR Local remote I 1-2 *)
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
1 BI Bus isolator switch 2-4 *)
2 CB Circuit breaker closed/opened 1-2 *)
RCD
7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1

KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

46
SPLN S5.001: 2008

TB-13: Interbus transformer

(secondary side connected to single busbar)

TB-13
INTERBUS TRANSFORMER Secondary
Side Connected to Single Busbar
BUSBAR (IRCC or RCC)

L/R

P
Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


by RCC

BUSBAR

47
SPLN S5.001: 2008

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar)

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1-2 *)
28 CBTR Circuit breaker trip A 1-2 *)
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
1 BI Bus isolator switch I 1-3 *)
3 CB Circuit breaker closed/opened I 1-2 *)
12 LI Line isolator switch closed/opened I 1-0 *)
TSD
13 LR Local remote I 1-2 *)
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
1 BI Bus isolator switch 1-3 *)
2 CB Circuit breaker closed/opened 1-2 *)
RCD
7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1

KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

48
SPLN S5.001: 2008

TB-14: Interbus transformer

(secondary side connected to 1½ breaker dilengkapi shunt reaktor pada


kumparan tersier)

INTERBUS TRANSFORMER Secondary Side TB-14


Connected to 1½ Breaker Dilengkapi Shunt Reaktor
Pada Kumparan Tersier
BUSBAR (IRCC)

L/R
Q
P
Q
V
I
BUSBAR - A

Operation Responsibility
by IRCC

Operation Responsibility Download to RCC


by RCC

BUSBAR - B

49
SPLN S5.001: 2008

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1½ Breaker


Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 2
7 V Tegangan 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
53 TAF Tranformer avr failure A 1
TSS 54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
12 LI Line isolator switch closed/opened I 3
13 LR Local remote I 1
TSD
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
7 TC Tap changer raise/lower 1
RCD
8 TCC Tap changer auto/manual 1

50
SPLN S5.001: 2008

TB-15: Interbus transformer

(secondary side connected to double busbar dilengkapi shunt reaktor pada


kumparan tersier)

INTERBUS TRANSFORMER Secondary Side TB-15


Connected to Double Busbar Dilengkapi Shunt
Reaktor Pada Kumparan Tersier

BUSBAR (IRCC or RCC)

L/R

P
Q
Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


by RCC

BUSBAR - A

BUSBAR - B

51
SPLN S5.001: 2008

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar
Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 2
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1-2 *)
28 CBTR Circuit breaker trip A 1-2 *)
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
1 BI Bus isolator switch I 2-4 *)
3 CB Circuit breaker closed/opened I 1-2 *)
12 LI Line isolator switch closed/opened I 2-1 *)
TSD
13 LR Local remote I 1-2 *)
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
1 BI Bus isolator switch 2-4 *)
2 CB Circuit breaker closed/opened 1-2 *)
RCD
7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1

KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

52
SPLN S5.001: 2008

TB-16: Interbus transformer

(secondary side connected to single busbar dilengkapi shunt reaktor pada


kumparan tersier)

INTERBUS TRANSFORMER Secondary Side TB-16


Connected to Single Busbar Dilengkapi Shunt Reaktor
Pada Kumparan Tersier

BUSBAR (IRCC or RCC)

L/R

P
Q Q
V
I

Operation Responsibility
by IRCC or RCC

L/R

Operation Responsibility Download to RCC


by RCC

BUSBAR

53
SPLN S5.001: 2008

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar
Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh


TC 1 TPI Tap position indication I 1
2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 2
7 V Tegangan 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1-2 *)
28 CBTR Circuit breaker trip A 1-2 *)
30 CSP Check synchronizing in progress I 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
TSS 53 TAF Tranformer avr failure A 1
54 TCA Tap changer alarm A 1
55 TCH Tap changer high limit A 1
56 TCL Tap changer low limit A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
72 TCT Tap changer trip A 1
1 BI Bus isolator switch I 1-3 *)
3 CB Circuit breaker closed/opened I 1-2 *)
12 LI Line isolator switch closed/opened I 2-1 *)
TSD
13 LR Local remote I 1-2 *)
14 LRT Local/remote switch for tapchanger I 1
20 TCC Tap changer auto/remote I 1
1 BI Bus isolator switch 1-3 *)
2 CB Circuit breaker closed/opened 1-2 *)
RCD
7 TC Tap changer raise/lower 1
8 TCC Tap changer auto/manual 1

KETERANGAN:
*)
= (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

54
SPLN S5.001: 2008

TB-17: Bay trafo tenaga pada konfigurasi 1½ breaker

55
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh


3 P Daya aktif 1
TM
6 Q Daya reaktif 1
26 BF Bay fault DC A 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
43 P2GFR Ground fault relay A 1
TSS 44 P2OCR Over current relay A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
TSD 12 LI Line isolator switch closed/opened I 1

56
SPLN S5.001: 2008

TB-18: Bay trafo tenaga pada konfigurasi double busbar

TB-18
BAY TRAFO TENAGA
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A

BUSBAR - B

L/R
P
Q

TEGANGAN TINGGI

Batas wewenang

TEGANGAN MENENGAH

DOUBLE BUSBAR

57
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh


3 P Daya aktif 1
TM
6 Q Daya reaktif 1
26 BF bay fault DC A 1
27 BRF breaker fault A 1
28 CBTR circuit breaker trip A 1
38 P1DIF Differential A 1
39 P1REF restricted earth fault A 1
TSS 43 P2GFR ground fault relay A 1
44 P2OCR over current relay A 1
57 TEA temperature alarm A 1
58 TET temperature trip A 1
59 TRA transformer alarm A 1
60 TRT transformer trip A 1
1 BI bus isolator switch I 2
TSD 3 CB circuit breaker closed/opened I 1
13 LR local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

58
SPLN S5.001: 2008

TB-19: Bay trafo tenaga pada konfigurasi single busbar

BAY TRAFO TENAGA TB-19


PADA KONFIGURASI SINGLE BUSBAR

BUSBAR

L/R

P
Q

TEGANGAN TINGGI

Batas wewenang

TEGANGAN MENENGAH

DOUB LE BUSBAR

59
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh


3 P Daya aktif 1
TM
6 Q Daya reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
38 P1DIF Differential A 1
39 P1REF Restricted earth fault A 1
TSS 43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
57 TEA Temperature alarm A 1
58 TET Temperature trip A 1
59 TRA Transformer alarm A 1
60 TRT Transformer trip A 1
1 BI Bus isolator switch I 1
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1

60
SPLN S5.001: 2008

TB-20: Bay reaktor pada konfigurasi 1 ½ breaker

TB-20
BAY REAKTOR
PADA KONFIGURASI 1½ BREAKER

BUSBAR - A

BUSBAR - B

Reaktor

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi 1 ½ Breaker

Data No Kode Fungsi Tipe Jmh


TM 6 Q Daya Reaktif 1
26 BF Bay fault DC A 1
38 P1DIF Differential A 1
TSS 43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
49 RF Reactor failure A 1
TSD 12 LI Line isolator switch closed/opened I 1

61
SPLN S5.001: 2008

TB-21: Bay reaktor pada konfigurasi double busbar

TB-21
BAY REAKTOR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

Reaktor

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh


TM 6 Q Daya Reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS 38 P1DIF Differential A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
49 RF Reactor failure A 1
1 BI Bus isolator switch I 2
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

62
SPLN S5.001: 2008

TB-22: Bay reaktor pada konfigurasi single busbar

TB-22
BAY REAKTOR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR

L/R

Reaktor

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh


TM 6 Q Daya Reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS 38 P1DIF Differential A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
49 RF Reactor failure A 1
1 BI Bus isolator switch I 1
TSD 3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1

63
SPLN S5.001: 2008

TB-23: Bay capasitor pada konfigurasi double busbar

TB-23
BAY KAPASITOR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

Capasitor

Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh


TM 6 Q Daya Reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
38 P1DIF Differential A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
1 BI Bus isolator switch I 2
2 CAM Capasitor Auto/Manual I 1
TSD
3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

64
SPLN S5.001: 2008

TB-24: Bay capasitor pada konfigurasi single busbar

TB-24
BAY KAPASITOR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR

L/R

Capasitor

Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh


TM 6 Q Daya Reaktif 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
TSS
38 P1DIF Differential A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
1 BI Bus isolator switch I 1
2 CAM Capasitor Auto/Manual I 1
TSD
3 CB Circuit breaker closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1

65
SPLN S5.001: 2008

TB-25: Bay penghantar pada konfigurasi 1 ½ breaker

TB-25
BAY PENGHANTAR
PADA KONFIGURASI 1½ BREAKER

BUSBAR - A

BUSBAR - B

P
Q
V
I

66
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi 1 ½ Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
40 P1Z1 *) Distance zone 1 A 1
TSS
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
TSD 12 LI Line isolator switch closed/opened I 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder

67
SPLN S5.001: 2008

TB-26: Bay penghantar pada konfigurasi double busbar

TB-26
BAY PENGHANTAR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

P
Q
V
I

68
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
TSS
40 P1Z1 *) Distance zone 1 A 1
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
TSD 5 CSO Check synchronizing override I 1
12 LI Line isolator switch closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder

69
SPLN S5.001: 2008

TB-27: Bay penghantar pada konfigurasi single busbar

TB-27
BAY PENGHANTAR
PADA KONFIGURASI SINGLE BUSBAR
BUSBAR

L/R

P
Q
V
I

70
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
TSS
40 P1Z1 *) Distance zone 1 A 1
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
1 BI Bus isolator switch I 1
3 CB Circuit breaker closed/opened I 1
TSD 5 CSO Check synchronizing override I 1
12 LI Line isolator switch closed/opened I 1
13 LR Local remote I 1
1 BI Bus isolator switch 1
RCD
2 CB Circuit breaker closed/opened 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder

71
SPLN S5.001: 2008

TB-28: Bay penghantar paralel dengan reaktor pada konfigurasi double busbar

BAY PENGHANTAR PARALEL TB-28


DENGAN REAKTOR
PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

BUSBAR - B

L/R

P
Q
V
I

72
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
TSS
40 P1Z1 *) Distance zone 1 A 1
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
TSD 5 CSO Check synchronizing override I 1
12 LI Line isolator switch closed/opened I 2
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder

73
SPLN S5.001: 2008

TB-29: Bay penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker

BAY PENGHANTAR PARALEL TB-29


DENGAN 1 REAKTOR PADA
KONFIGURASI 1½ BREAKER
BUSBAR - A

BUSBAR - B

P
Q
Q V
I
L/R

74
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR Circuit breaker trip A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
TSS
40 P1Z1 *) Distance zone 1 A 1
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
3 CB Circuit breaker closed/opened I 1
TSD 12 LI Line isolator switch closed/opened I 2
13 LR Local remote I 1
RCD*) 2 CB Circuit breaker closed/opened 1

KETERANGAN:
*)
= Khusus untuk OHL Feeder

75
SPLN S5.001: 2008

TB-30: Bay penghantar paralel dengan 2 reaktor seri pada konfigurasi 1½


breaker

TB-30
BAY PENGHANTAR PARALEL DENGAN 2
REAKTOR SERI PADA KONFIGURASI 1 ½
BREAKER
BUSBAR- A

BUSBAR- B

P
Q Q
V
I
Q

76
SPLN S5.001: 2008

Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor seri Pada Konfigurasi 1½
Breaker

Data No Kode Fungsi Tipe Jmh


2 I Arus 1
3 P Daya aktif 1
TM
6 Q Daya reaktif 1
7 V Tegangan 1
23 AR *) Circuit breaker auto reclose I 1
24 ARO *) Auto reclose on/off I 1
26 BF Bay fault DC A 1
30 CSP Check synchronizing in progress I 1
36 P1CD Current differential A 1
37 P1DEF Directional earth fault A 1
40 P1Z1 *) Distance zone 1 A 1
TSS
41 P1Z2 *) Distance zone 2 A 1
42 P1Z3 *) Distance zone 3 A 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
45 P3DTT*) Direct transfer trip A 1
61 TTR Teleprotection trip receive I 1
62 TTT Teleprotection trip transmit I 1
TSD 12 LI Line isolator switch closed/opened I 2

KETERANGAN:
*)
= Khusus untuk OHL Feeder

77
SPLN S5.001: 2008

TB-31: Bay kopel pada konfigurasi double busbar

TB-31
BAY KOPEL
PADA KONFIGURASI DOUBLE BUSBAR

L/R

BUSBAR - A

BUSBAR - B

Teleinformasi Data Untuk Bay Kopel Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh


TM 1 I Arus 1
26 BF Bay fault DC A 1
27 BRF Breaker fault A 1
28 CBTR CB trip A 1
TSS
30 CSP Check synchronizing in progress I 1
43 P2GFR Ground fault relay A 1
44 P2OCR Over current relay A 1
1 BI Bus isolator switch I 2
3 CB Circuit breaker closed/opened I 1
TSD
5 CSO Check synchronizing override I 1
13 LR Local remote I 1
1 BI Bus isolator switch 2
RCD
2 CB Circuit breaker closed/opened 1

78
SPLN S5.001: 2008

TB-32: Bus section

TB-32
BUS SECTION

Tipe-1

L/R

Tipe-2
L/R

Teleinformasi Data Untuk Bus Section

Jumlah
Data No Kode Fungsi Tipe
Tipe-1 Tipe-2
26 BF Bay fault DC A 1 1
27 BRF Breaker fault A 1
TSS
28 CBTR CB trip A 1
30 CSP Check synchronizing in progress I 1
1 BI Bus isolator switch I 2 1
3 CB Circuit breaker closed/opened I 1
TSD
5 CSO Check synchronizing override I 1
13 LR Local remote I 1 1
1 BI Bus isolator switch 2 1
RCD
2 CB Circuit breaker closed/opened 1

79
SPLN S5.001: 2008

TB-33: Bay diameter pada konfigurasi 1½ breaker

TB-33
BAY DIAMETER
PADA KONFIGURASI 1½ BREAKER

BUSBAR - A

L/R

L/R

L/R

BUSBAR - B

Teleinformasi Data Untuk Diameter

Data No Kode Fungsi Tipe Jmh


27 BRF Breaker fault A 3
TSS 28 CBTR CB trip A 3
30 CSP Check synchronizing in progress I 3
1 BI Bus isolator switch I 6
3 CB Circuit breaker closed/opened I 3
TSD
5 CSO Check synchronizing override I 3
13 LR Local remote I 3
1 BI Bus isolator switch 6
RCD
2 CB Circuit breaker closed/opened 3

80
SPLN S5.001: 2008

TB-34: Bus bar

TB-34
BUS BAR

BUSBAR - A
V

Teleinformasi Data Untuk Bus Bar

Data No Kode Fungsi Tipe Jumlah


TM 7 V Tegangan 1
26 BF Bay fault DC A 1
34 OVR Over voltage relay operate A 1
TSS 35 P1BP Busbar protection A 1
64 UVR Under voltage relay A 1
67 VS Voltage status A 1

81
SPLN S5.001: 2008

LAMPIRAN C – DAFTAR TELEINFORMASI (DISTRIBUSI)

C-1: Telesignal

Single (S) Suggested


or Double Alarm (A) or
No Kode Fungsi Implementasi
(D) Event/Indication
Indication (I)
Feeder
1 ARU Auto Recloser Use/Unuse D I
PBO
Feeder
2 BI Bus Isolator Switch Closed/Opened Incoming D I
Generator
3 CAM Capacitor Auto/Manual Capacitor D I
Bus Coupler
Bus Section
Feeder
4 CB Circuit Breaker Closed/Opened Incoming D I
Capacitor
Generator
PBO
5 DCBC Dummy Breaker Closed/Opened RTU D I

6 GUC Generator Unit Run/Stop Generator D I


Feeder
7 LBS Load Break Switch D I
Key Point
Bus Coupler
Bus Section
8 LR Local Remote Feeder D I
Incoming
Keypoint
Feeder
9 RACK Circuit Breaker Rackin/Rackout D I
Incoming
Feeder
10 RR Recloser Reset D I
PBO

11 TC Tap Changer Raise/Lower Incoming 20 kV D I

12 TCC Tap Changer Auto/Manual Incoming 20 kV D I


Feeder
13 AR Circuit Breaker Auto Reclose S A
PBO
Bus Coupler
Bus Section
14 BRF Breaker Fault Feeder S A
Capacitor
Generator
Bus Coupler
Bus Section
15 CBTR CB Trip Feeder S A
Capacitor
PBO
16 COM Communication Faulty Comm. Device S A
Gardu Induk
17 DOOR Door Activated Gardu Tengah S A
Gardu Hubung
18 FPO Fire Protection Operated Gardu Induk S A

19 FRA Fire Alarm Gardu Induk S A

82
SPLN S5.001: 2008

Single (S) Suggested


or Double Alarm (A) or
No Kode Fungsi Implementasi
(D) Event/Indication
Indication (I)
20 FRSF Fire Alarm System Failure Gardu Induk S A

21 GTT Generator Transformer Trip Gen Transf S A


Keypoint
22 EFI Earth Fault Indicator Gardu Hubung S A
Gardu Tengah
23 P1DEF Directional Earth Fault Feeder S A
Bus Coupler
Bus Section
24 P2GFR Ground Fault Relay Feeder S A
Capacitor
PBO
Bus Coupler
Bus Section
25 P2OCR Over Current Relay Feeder S A
Capacitor
PBO
Bus Coupler
Bus Section
26 PTF Protection Faulty Feeder S A
Capacitor
PBO
RTU
27 RTUA Remote Station Alarm S A
IED

28 TCH Tap Changer High Limit Incoming 20 kV S A

29 TCL Tap Changer Low Limit Incoming 20 kV S A

30 TPIF Tap Position Indication Failure Incoming 20 kV S A

Incoming 20 kV
31 UFR Under Frequency Relay Operate S A
Capacitor
32 UT Unit Trip Generator S A

33 VACF VAC Failure Power Supply S A

34 VDCF VDC Failure Power Supply S A

83
SPLN S5.001: 2008

C-2: Telemeasurement

No Kode Fungsi Implementasi

1 AMF Ampere Fault (Per Phase) Feeder

2 F Frekuensi Busbar

Feeder
3 I Arus
Incoming 20 kV
Generator
Keypoint
PBO
Feeder
4 P Daya Aktif Incoming 20 kV
Generator

5 PF Power Factor Incoming 20 kV

Incoming 20 kV
6 Q Daya Reaktif Capacitor
Generator
Busbar
Generator
7 V Tegangan
Keypoint
PBO
Feeder
Incoming 20 kV
8 CCB Counter Of Circuit Breaker Capacitor
Generator
PBO

84
SPLN S5.001: 2008

C-3: Tap changer position

No Kode Fungsi Implementasi

1 TPI Tap Position Indication Incoming 20 kV

C-4: Remote control digital

No Kode Fungsi Implementasi

Feeder
1 ARU Auto Recloser use/unuse
PBO

2 CAM Capasitor Auto/Manual Capacitor

Bus Coupler
Bus Section
Feeder
3 CB Circuit Breaker Closed/Opened
Incoming 20 kV
Capacitor
PBO

4 DCBC Dummy Circuit Breaker Closed/Opened RTU

Keypoint
5 LBS Load Break Switch Close/Open Gardu Tengah
Gardu Hubung
Feeder
6 RR Recloser Reset
PBO

7 TC Tap Changer Raise/Lower Incoming 20 kV

8 TCC Tap Changer Auto/Manual Incoming 20 kV

85
SPLN S5.001: 2008

LAMPIRAN D - BIDANG DISTRIBUSI (TELEINFORMASI PADA


BERBAGAI KONFIGURASI JARINGAN DISTRIBUSI)

DA-01: Konfigurasi umum pada double busbar

DA- 01

KONFIGURASI UMUM PADA DOUBLE BUSBAR

CAPASITOR GENERATOR

P
Q
V

Q P
Q KOPEL
I

L/ R L/ R L/ R

V(R)
BUSBA-RA V(S)
V(T)

BUSBA-RB
V(R)
V(S)
V(T)

I
P L/ R L/ R

IP
Q
PF

FEEDER INCOMING 20 KV

86
SPLN S5.001: 2008

Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar


Group
Data No Kode Fungsi Tipe Jmh
Bay
2 F Frekuensi 1
Busbar TM
7 V Tegangan 6
1 AMF Ampere Fault 1
3 I Arus 1
TM
4 P Daya Aktif 1
8 CCB Counter Of Circuit Breaker 1
13 AR Circuit Breaker Auto Reclose A 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS 24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
Feeder
26 PTF Protection Faulty A 1
31 UFR Under Frequency Relay Operate A 1
1 ARU Auto Reclose Use/Unuse I 1
2 BI Bus Isolator Switch Closed/Opened I 2
TSD 4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
10 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
3 CB Circuit Breaker Closed/Opened 1
RCD
6 RR Recloser Reset 1
3 I Arus 1
4 P Daya Aktif 1
TM 5 PF Power Factor 1
6 Q Daya Reaktif 1
8 CCB Counter Of Circuit Breaker 1
28 TCH Tap Changer High Limit A 1
TSS 29 TCL Tap Changer Low Limit A 1
Incoming 30 TPIF Tap Position Indication Failure A 1
20 kV 2 BI Bus Isolator Switch Closed/Opened I 2
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
11 TC Tap Changer Raise/Lower I 1
12 TCC Tap Changer Auto/Manual I 1
3 CB Circuit Breaker Closed/Opened 1
7 TC Tap Changer Raise/Lower 1
RCD
8 TCC Tap Changer Auto/Manual 1
Capasitor 6 Q Daya Reaktif 1
TM
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
26 PTF Protection Faulty A 1
TSD 2 BI Bus Isolator Switch Closed/Opened I 2
3 CAM Capacitor Auto/Manual I 1

87
SPLN S5.001: 2008

Group
Data No Kode Fungsi Tipe Jmh
Bay
4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
2 CAM Capacitor Auto/Manual I 1
RCD
3 CB Circuit Breaker Closed/Opened 1
3 I Arus 1
4 P Daya aktif 2
TM 6 Q Daya reaktif 2
7 V Tegangan 1
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker fault A 1
Generator TSS 15 CBTR Circuit breaker trip A 1
32 UT Unit trip A 1
2 BI Bus isolator switch I 2
4 CB Circuit breaker closed/opened I 2
TSD
6 GUC Generator unit run/stop I 1
8 LR Local remote I 1
RCD 3 CB Circuit breaker closed/opened 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
Kopel
26 PTF Protection Faulty A 1
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
9 RACK Circuit Breaker Rackin/Rackout I 1
RCD 3 CB Circuit Breaker Closed/Opened 1

88
SPLN S5.001: 2008

DA-02: Konfigurasi umum pada single busbar

DA - 02

KONFIGURASI UMUM PADA SINGLE BUSBAR

CAPASITOR GENERATOR

P
Q
V

P
Q Q
I

L/ R L/R

V (R)
BUSBAR
- A V (S)
V (T)

I
P
L/ R L/R

I
P
Q
PF

FEEDER INCOMING 20 KV

89
SPLN S5.001: 2008

Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar


Group
Data No Kode Fungsi Tipe Jmh
Bay
2 F Frekuensi 1
Busbar TM
7 V Tegangan 3
1 AMF Ampere Fault 1
3 I Arus 1
TM
4 P Daya Aktif 1
8 CCB Counter Of Circuit Breaker 1
13 AR Circuit Breaker Auto Reclose A 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS 24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
Feeder
26 PTF Protection Faulty A 1
31 UFR Under Frequency Relay Operate A 1
1 ARU Auto Reclose Use/Unuse I 1
2 BI Bus Isolator Switch Closed/Opened I 1
TSD 4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
10 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
3 CB Circuit Breaker Closed/Opened 1
RCD
6 RR Recloser Reset 1
3 I Arus 1
4 P Daya Aktif 1
TM 5 PF Power Factor 1
6 Q Daya Reaktif 1
8 CCB Counter Of Circuit Breaker 1
28 TCH Tap Changer High Limit A 1
TSS 29 TCL Tap Changer Low Limit A 1
Incoming 30 TPIF Tap Position Indication Failure A 1
20 kV 2 BI Bus Isolator Switch Closed/Opened I 1
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
11 TC Tap Changer Raise/Lower I 1
12 TCC Tap Changer Auto/Manual I 1
3 CB Circuit Breaker Closed/Opened 1
7 TC Tap Changer Raise/Lower 1
RCD
8 TCC Tap Changer Auto/Manual 1
Capasitor 6 Q Daya Reaktif 1
TM
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
26 PTF Protection Faulty A 1
TSD 2 BI Bus Isolator Switch Closed/Opened I 1
3 CAM Capacitor Auto/Manual I 1

90
SPLN S5.001: 2008

Group
Data No Kode Fungsi Tipe Jmh
Bay
4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
2 CAM Capacitor Auto/Manual I 1
RCD
3 CB Circuit Breaker Closed/Opened 1
3 I Arus 1
4 P Daya aktif 2
TM 6 Q Daya reaktif 2
7 V Tegangan 1
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker fault A 1
Generator TSS 15 CBTR Circuit breaker trip A 1
32 UT Unit trip A 1
2 BI Bus isolator switch I 1
4 CB Circuit breaker closed/opened I 2
TSD
6 GUC Generator unit run/stop I 1
8 LR Local remote I 1
RCD 3 CB Circuit breaker closed/opened 1

91
SPLN S5.001: 2008

DB-01: Trafo 150/20 kV dan 70/20 kV tipe 1

DB - 01
TRAFO 150/20 KV DAN 70/20 KV
TYPE 1

RCC
I
L/R DCC
P
Q
PF

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 1


Group Bay Data No Kode Fungsi Tipe Jmh
3 I Arus 1
4 P Daya Aktif 1
TM 5 PF Power Factor 1
6 Q Daya Reaktif 1
8 CCB Counter Of Circuit Breaker 1
28 TCH Tap Changer High Limit A 1
TSS 29 TCL Tap Changer Low Limit A 1
Incoming 30 TPIF Tap Position Indication Failure A 1
20 kV 2 BI Bus Isolator Switch Closed/Opened I 2
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
11 TC Tap Changer Raise/Lower I 1
12 TCC Tap Changer Auto/Manual I 1
3 CB Circuit Breaker Closed/Opened 1
7 TC Tap Changer Raise/Lower 1
RCD
8 TCC Tap Changer Auto/Manual 1
Busbar TM 7 V Tegangan 6

92
SPLN S5.001: 2008

DB-02: Trafo 150/20 kV dan 70/20 kV tipe 2

DB -02
TRAFO 150/20 KV DAN 70/20 KV
TYPE 2

RCC
DCC
I
P
Q
PF

L/R

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 2


Group Bay Data No Kode Fungsi Tipe Jmh
3 I Arus 1
4 P Daya Aktif 1
TM 5 PF Power Factor 1
6 Q Daya Reaktif 1
8 CCB Counter Of Circuit Breaker 1
28 TCH Tap Changer High Limit A 1
TSS 29 TCL Tap Changer Low Limit A 1
30 TPIF Tap Position Indication Failure A 1
Incoming
2 BI Bus Isolator Switch Closed/Opened I 2
20 kV
4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
TSD
9 RACK Circuit Breaker Rackin/Rackout I 1
11 TC Tap Changer Raise/Lower I 1
12 TCC Tap Changer Auto/Manual I 1
3 CB Circuit Breaker Closed/Opened 1
7 TC Tap Changer Raise/Lower 1
RCD
8 TCC Tap Changer Auto/Manual 1
Busbar TM 7 V Tegangan 6

93
SPLN S5.001: 2008

DB-03: Trafo 150/20 kV dan 70/20 kV tipe 3

DB - 03
TRAFO 150/20 KV DAN 70/20 KV
TYPE 3

RCC
I L/R
DCC
P
Q
PF

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 3


Group Bay Data No Kode Fungsi Tipe Jmh

3 I Arus 1
4 P Daya Aktif 1
TM 5 PF Power Factor 1
6 Q Daya Reaktif 1
8 CCB Counter Of Circuit Breaker 1
28 TCH Tap Changer High Limit A 1
TSS 29 TCL Tap Changer Low Limit A 1
Incoming 30 TPIF Tap Position Indication Failure A 1
20 kV 2 BI Bus Isolator Switch Closed/Opened I 1
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
11 TC Tap Changer Raise/Lower I 1
12 TCC Tap Changer Auto/Manual I 1
3 CB Circuit Breaker Closed/Opened 1
7 TC Tap Changer Raise/Lower 1
RCD
8 TCC Tap Changer Auto/Manual 1
Busbar TM 7 V Tegangan 3

94
SPLN S5.001: 2008

DB-04: Generator pada konfigurasi double busbar

DB-04

GENERATOR PADA KONFIGURASI DOUBLE BUSBAR

P
Q
V

P
Q
I

L/R

BUSBAR - A

BUSBAR - B

Teleinformasi Data Untuk Generator Pada Konfigurasi Double Busbar


Data No Kode Fungsi Tipe Jmh
3 I Arus 1
4 P Daya aktif 2
TM 6 Q Daya reaktif 2
7 V Tegangan 1
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker fault A 1
TSS 15 CBTR Circuit breaker trip A 1
32 UT Unit trip A 1
2 BI Bus isolator switch I 2
4 CB Circuit breaker closed/opened I 2
TSD
6 GUC Generator unit run/stop I 1
8 LR Local remote I 1
RCD 3 CB Circuit breaker closed/opened 1

95
SPLN S5.001: 2008

DB-05: Generator pada konfigurasi single busbar

DB-05

GENERATOR PADA KONFIGURASI SINGLE BUSBAR

P
Q
V

P
Q
I

L/R

BUSBAR

Teleinformasi Data Untuk Generator Pada Konfigurasi Single Busbar


Data No Kode Fungsi Tipe Jmh
3 I Arus 1
4 P Daya aktif 2
TM 6 Q Daya reaktif 2
7 V Tegangan 1
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker fault A 1
TSS 15 CBTR Circuit breaker trip A 1
32 UT Unit trip A 1
2 BI Bus isolator switch I 2
4 CB Circuit breaker closed/opened I 2
TSD
6 GUC Generator unit run/stop I 1
8 LR Local remote I 1
RCD CB Circuit breaker closed/opened 1

96
SPLN S5.001: 2008

DB-06: Feeder 20 kV tipe 1

DB - 06
FEEDER 20 KV
TYPE 1

I L/R
P

Teleinformasi Data Untuk Feeder 20 kV Tipe 1


Group Bay Data No Kode Fungsi Tipe Jmh
1 AMF Ampere Fault 1
3 I Arus 1
TM
4 P Daya Aktif 1
8 CCB Counter Of Circuit Breaker 1
13 AR Circuit Breaker Auto Reclose A 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS 24 P2GFR Ground Fault Relay A 1
Feeder 25 P2OCR Over Current Relay A 1
20 kV 26 PTF Protection Faulty A 1
31 UFR Under Frequency Relay Operate A 1
1 ARU Auto Reclose Use/Unuse I 1
2 BI Bus Isolator Switch Closed/Opened I 2
TSD 4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
10 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
3 CB Circuit Breaker Closed/Opened 1
RCD
6 RR Recloser Reset 1

97
SPLN S5.001: 2008

DB-07: Feeder 20 kV tipe 2

DB - 07
FEEDER 20 KV
TYPE 2

L/R

I
P

Teleinformasi Data Untuk Feeder 20 kV Tipe 2


Group Bay Data No Kode Fungsi Tipe Jmh
1 AMF Ampere Fault 1
3 I Arus 1
TM
4 P Daya Aktif 1
8 CCB Counter Of Circuit Breaker 1
13 AR Circuit Breaker Auto Reclose A 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS 24 P2GFR Ground Fault Relay A 1
Feeder 25 P2OCR Over Current Relay A 1
20 kV 26 PTF Protection Faulty A 1
31 UFR Under Frequency Relay Operate A 1
1 ARU Auto Reclose Use/Unuse I 1
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
9 RACK Circuit Breaker Rackin/Rackout I 1
10 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
3 CB Circuit Breaker Closed/Opened 1
RCD
6 RR Recloser Reset 1

98
SPLN S5.001: 2008

DB-08: Feeder 20 kV tipe 3

DB - 08
FEEDER 20 KV
TYPE 3

I L/R
P

Teleinformasi Data Untuk Feeder 20 kV Tipe 3

Group Bay Data No Kode Fungsi Tipe Jmh


1 AMF Ampere Fault 1
3 I Arus 1
TM
4 P Daya Aktif 1
8 CCB Counter Of Circuit Breaker 1
13 AR Circuit Breaker Auto Reclose A 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS 24 P2GFR Ground Fault Relay A 1
Feeder 25 P2OCR Over Current Relay A 1
20 kV 26 PTF Protection Faulty A 1
31 UFR Under Frequency Relay Operate A 1
1 ARU Auto Reclose Use/Unuse I 1
2 BI Bus Isolator Switch Closed/Opened I 1
TSD 4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
10 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
3 CB Circuit Breaker Closed/Opened 1
RCD
6 RR Recloser Reset 1

99
SPLN S5.001: 2008

DB-09: Bus Section 20 kV tipe 1

DB - 09
BUS SECTION 20 KV
TYPE 1

L/R

Teleinformasi Data Untuk Bus Section 20 kV Tipe 1


Group Bay Data No Kode Fungsi Tipe Jmh
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
Bus
25 P2OCR Over Current Relay A 1
Section
20 kV 26 PTF Protection Faulty A 1
2 BI Bus Isolator Switch Closed/Opened I 2
TSD 4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
RCD 3 CB Circuit Breaker Closed/Opened 1

100
SPLN S5.001: 2008

DB-10: Bus section 20 kV tipe 2

DB -10
BUS SECTION 20 KV
TYPE 2

L/R

Teleinformasi Data Untuk Bus Section 20 kV Tipe 2

Group Bay Data No Kode Fungsi Tipe Jmh


14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
Bus
25 P2OCR Over Current Relay A 1
Section
20 kV 26 PTF Protection Faulty A 1
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
9 RACK Circuit Breaker Rackin/Rackout I 1
RCD 3 CB Circuit Breaker Closed/Opened 1

101
SPLN S5.001: 2008

DB-11: Kopel

DB -11
KOPEL

L/R

Teleinformasi Data Untuk Kopel

Group Bay Data No Kode Fungsi Tipe Jmh


14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
Kopel
26 PTF Protection Faulty A 1
4 CB Circuit Breaker Closed/Opened I 1
TSD 8 LR Local Remote I 1
9 RACK Circuit Breaker Rackin/Rackout I 1
RCD 3 CB Circuit Breaker Closed/Opened 1

102
SPLN S5.001: 2008

DB-12: Capacitor bay

DB -12
CAPACITOR BAY

L/R
Q

Teleinformasi Data Untuk Capasitor Bay

Group Bay Data No Kode Fungsi Tipe Jmh


6 Q Daya Reaktif 1
TM
8 CCB Counter Of Circuit Breaker 1
14 BRF Breaker Fault A 1
15 CBTR CB Trip A 1
23 P1DEF Directional Earth Fault A 1
TSS
24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
Capasitor
26 PTF Protection Faulty A 1
2 BI Bus Isolator Switch Closed/Opened I 2
3 CAM Capacitor Auto/Manual I 1
TSD
4 CB Circuit Breaker Closed/Opened I 1
8 LR Local Remote I 1
2 CAM Capacitor Auto/Manual I 1
RCD
3 CB Circuit Breaker Closed/Opened 1

103
SPLN S5.001: 2008

DB-13: SUTM radial dengan keypoint dan PBO

DB -13
SUTM RADIAL
DENGAN KEYPOINT DAN PBO

KP
I

I I PBO

L/R I
V (R) V
V (S)
V (T)

Teleinformasi Data Untuk SUTM radial dengan keypoint dan PBO

Group Bay Data No Kode Fungsi Tipe Jmh


3 I Arus 3
TM
7 V Tegangan 3
Keypoint TSS 22 EFI Earth Fault Indicator A 3
7 LBS Load Break Switch Closed/Opened I 1
TSD
8 LR Local Remote I 1
RCD 5 LBS Load Break Switch Closed/Opened 1
3 I Arus 3
TM 7 V Tegangan 3
8 CCB Counter Of Circuit Breaker 1
13 AR Circuit Breaker Auto Reclose A 1
15 CBTR CB Trip A 1
TSS 24 P2GFR Ground Fault Relay A 1
25 P2OCR Over Current Relay A 1
26 PTF Protection Faulty A 1
1 ARU Auto Recloser Use/Unuse I 1
PBO TSD 4 CB Circuit Breaker Closed/Opened I 1
10 RR Recloser Reset I 1
1 ARU Auto Recloser Use/Unuse 1
3 CB Circuit Breaker Closed/Opened 1
RCD
6 RR Recloser Reset

104
SPLN S5.001: 2008

DB-14: SUTM radial dengan keypoint tanpa PBO

DB -14
SUTM RADIAL
DENGAN KEYPOINT TANPA PBO

KP

I I

L/R
V (R)
V (S)
V (T)

Teleinformasi Data Untuk SUTM radial dengan keypoint tanpa PBO

Group Bay Data No Kode Fungsi Tipe Jmh


3 I Arus 3
TM
7 V Tegangan 3
Keypoint TSS 22 EFI Earth Fault Indicator A 3
7 LBS Load Break Switch Closed/Opened I 1
TSD
8 LR Local Remote I 1
RCD 5 LBS Load Break Switch Closed/Opened 1

105
SPLN S5.001: 2008

DB-15: SUTM loop dengan beberapa keypoint

DB -15
SUTM LOOP
DENGAN BEBERAPA KP

L/R

I
V

I
L/R
V

L/R

I
V

Teleinformasi Data Untuk SUTM loop dengan beberapa keypoint

Group Bay Data No Kode Fungsi Tipe Jmh


3 I Arus 3
TM
7 V Tegangan 3
Keypoint TSS 22 EFI Earth Fault Indicator A 3
7 LBS Load Break Switch Closed/Opened I 3
TSD
8 LR Local Remote I 3
RCD 5 LBS Load Break Switch Closed/Opened 3

106
SPLN S5.001: 2008

DB-16: Spindle 20 kV

DB -16
SPINDLE 20 kV

20 kV
GI
Busbar

GD

GT L/R L/R L/R L/R L/R L/R

GD

GH L/R

Teleinformasi Data Untuk Spindle 20 kV

Group Bay Data No Kode Fungsi Tipe Jmh


17 DOOR Door Activated A 1
TSS
22 EFI Earth Fault Indicator A 6
Gardu
Tengah (GT) 7 LBS Load Break Switch Closed/Opened I 6
TSD
8 LR Local Remote I 6
RCD 5 LBS Load Break Switch Closed/Opened 6
17 DOOR Door Activated A 1
TSS
22 EFI Earth Fault Indicator A 7
Gardu 7 LBS Load Break Switch Closed/Opened I 7
Hubung TSD
8 LR Local Remote I 1
(GH)
RCD 5 LBS Load Break Switch Closed/Opened 7

107
SPLN S5.001: 2008

LAMPIRAN
LAMPIRAN EE ––STRUKTUR
STRUKTURINFORMASI
INFORMASI

Struktur
Struktur informasi
informasi terdiri dari 112
terdiri dari 112 karakter
karakteryang
yangdapat
dapatdikelompokkan
dikelompokkan menjadi
menjadi sembilan
sembilan
bagian,
bagian,yaitu:
yaitu:

AA BB C DD EE FF GG H H I I

Bagian
BagianA:A:Nomor
Nomor ID,
ID, terdiri dari
dari 66 digit
digit(sebagai
(sebagaiprimary
primarykey)
key)
Bagian
Bagian B:B: Time
Time stamp, sebanyak karakter
stamp, sebanyak karakter 2323 karakter
karakter
Bagian
Bagian C:C: Nama
Nama GI/GH/GT/KP, sebanyak 20
GI/GH/GT/KP, sebanyak 20 karakter
karakter
Bagian D: Level tegangan, sebanyak
Bagian D: Level tegangan, sebanyak 5 karakter 5 karakter
Bagian
BagianE:E:Nama
Nama baybay / feeder, sebanyak20
feeder, sebanyak 20karakter
karakter
Bagian
BagianF:F:Kode
Kode nama
nama peralatan ataunama
peralatan atau namaalarm
alarmatau
ataunama
nama elemen,
elemen, sebanyak
sebanyak 5 5
karakter
karakter
Bagian
BagianG:G:Status
Status peralatan atau status
peralatan atau statusalarm,
alarm,sebanyak
sebanyak1515 karakter
karakter
Bagian
BagianH:H:Nama
Nama user
user yang melakukan
melakukanaksi aksi(seperti
(sepertiremote
remotecontrol,
control, dan
dan sebagainya),
sebagainya),
sebanyak
sebanyak10 10 karakter
karakter
Bagian
Bagian I:I: Prioritas
Prioritas alarm, sebanyak 88 karakter
alarm, sebanyak karakter
Struktur
Strukturdidi atas
atas ditentukan dalam field
ditentukan dalam fieldyang
yangberbeda.
berbeda.
Contohnya
Contohnyadapatdapat dilihat pada tabel
dilihat pada tabel1. 1.

Tabel1.1.Struktur
Tabel Strukturinformasi
informasi

AA B
B CC DD EE FF GG H H I I
RCC
RCCCawang
Cawang
110007
110007 02/03/2007
02/03/2007 11:10:05.320
11:10:05.320 Cawang
Cawang 150 Gandul-1
150 Gandul-1BI1BI1 Close
Close Class-3
Class-3
110009
110009 05/03/2007
05/03/2007 07:00:55.115
07:00:55.115 Gandul
Gandul 150 Cawang-1
150 Cawang-1AROARO Appear
Appear Class-2
Class-2
RCC
RCCWaru
Waru
140104
140104 11/04/2007
11/04/2007 17:44:21.220
17:44:21.220 Rungkut
Rungkut 150 Waru-1
150 Waru-1 LTLT Disappear
Disappear Class-1
Class-1
140085
140085 12/04/2007
12/04/2007 20:11:51.312
20:11:51.312 Waru
Waru 150 Bangil-1
150 Bangil-1 CBCB Invalid
Invalid Class-4
Class-4
DCC
DCCPasuruan
Pasuruan
430011
430011 25/04/2007
25/04/2007 00:30:35.000
00:30:35.000 GondangWetan
Gondang Wetan 2020 Bromo CBCB Open
Bromo Open Adi AdiClass-1
Class-1
430012
430012 19/11/2007
19/11/2007 10:00:05.520
10:00:05.520 GondangWetan
Gondang Wetan 2020 Semeru CBTR
Semeru CBTR Appear
Appear Class-1
Class-1

A.
A.Nomor
NomorID
ID

Nomor
Nomor ID
ID (bagian
(bagian A) terdiri
terdiri dari
dari dua
dua bagian.
bagian. Bagian
BagianA1A1terdiri
terdiridari
dari3 3 digit
digit yang
yang
menyatakan kode
menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan
Bagian A2 terdiri dari 3 digit merupakan nomor RTU nomor RTU
bersangkutan.
bersangkutan. Nomor
Nomor ID dinyatakan
dinyatakandengan
dengansusunan
susunansebagai
sebagai berikut
berikut

A1
A1 A2
A2

Bagian
BagianA1:
A1:Kode
Kode area
area
Bagian
BagianA2:
A2:Nomor
Nomor RTU
RTU

108
SPLN S5.001: 2008

Kode area
Kode area yang terdiri dari 3 karakter adalah sebagai berikut:
NCC : 900

IRCC : x00
IRCC Jawa-Bali : 100
IRCC Sumatera : 200
IRCC Kalimantan : 300
IRCC Sulawesi : 400
IRCC di Indonesia Timur : 500

RCC di Jawa-Bali : 1xx


RCC Cawang : 110
RCC Cigereleng : 120
RCC Ungaran : 130
RCC Waru : 140
RCC di Sumatera : 2xx
RCC Medan : 210
RCC Padang : 220
RCC Palembang : 230
RCC di Kalimantan : 3xx
RCC Banjarbaru : 310
RCC Balikpapan : 320
RCC di Sulawesi : 4xx
RCC Makassar : 410
RCC Manado : 420
RCC di Indonesia Timur : 5xx

IDCC : x00
IDCC Jawa-Bali : 100, 200, 300, 400
IDCC Sumatera : 500, 600
IDCC Kalimantan : 700
IDCC Sulawesi : 800
IDCC di Indonesia Timur : 900

DCC di Jakarta : 0xx – 1xx


DCC daerah Jawa bagian Barat : 2xx
DCC daerah Jawa bagian Tengah : 3xx
DCC daerah Jawa bagian Timur dan Bali : 4xx
DCC daerah Sumatera : 5xx – 6xx
DCC daerah Kalimantan : 7xx
DCC daerah Sulawesi : 8xx
DCC daerah Indonesia Timur : 9xx
Nomor RTU
Nomor RTU terdiri dari 3 digit (001 – 999)

109
SPLN S5.001: 2008

B. Time stamp

Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri
dari
23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan
(2 karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6
karakter atau sampai dengan orde milidetik). Contohnya:

25/04/2007 00:30:35.000
19/11/2007 10:00:05.520

C. Nama GI/GH/GT

Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20


karakter). Contohnya adalah sebagai berikut:

Cawang
Gandul
Gondang Wetan
Rungkut
Waru
Cawang : menyatakan GI Cawang (dikontrol oleh RCC
Cawang). Gandul : menyatakan GI Gandul (dikontrol oleh RCC
Cawang). Waru : menyatakan GI Waru (dikontrol oleh RCC Waru).
Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru).
Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh
DCC Pasuruan).

D. Level Tegangan

Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada tabel 2.

Tabel 2. Level tegangan

Tegangan Level Tegangan


500 kV 500
275 kV 275
150 kV 150
70 kV 70
66 kV 66
30 kV 30
25 kV 25
23.5 kV 23
20 kV 20
16.75 kV 16.75
16.5 kV 16.5
13 kV 13
11 kV 11
6 kV 6

110
SPLN S5.001: 2008

E. Nama Bay / Feeder

Nama Bay/Feeder terdiri dari 20 karakter. Contohnya dapat dilihat pada tabel 3.

Tabel 3. Nama bay atau feeder

Nama Bay / Feeder Kode

Pusat Listrik
Pusat Listrik Tenaga Air PLTA
Pusat Listrik Tenaga Diesel PLTD
Pusat Listrik Tenaga Gas PLTG
Pusat Listrik Tenaga Panas Bumi PLTP
Pusat Listrik Tenaga Nuklir PLTN
Pusat Listrik Tenaga Uap PLTU
Pusat Listrik Gas/Uap (Combine Cycle) PLTGU
Pusat Listrik Tenaga Mikrohidro PLTMH
Pusat Listrik Tenaga Angin/Bayu PLTB

Peralatan di Gardu Induk


Line Bay (Feeder Bay) Format penulisan:
ƒ IRCC/RCC:
Nama GI lawan + ”-” + nomor
penghantar. Contohnya:
o Gandul-1
o Cawang-1
ƒ DCC:
Nama Feeder. Contohnya:
o Bromo
o Semeru
Bay ke Unit Generator UNIT
Busbar BUSBAR
Kopel (Bus Tie) KOPEL
Bus Section BUSSECT
Trafo TRAFOx (X adalah Kode Tegangan
dari primer dan sekunder trafo)
Diameter DAMTR
Shunt Reactor SHTXL
Shunt Capacitor SHTXC
Cadangan SPARE

Nama Bay
Bay 500 kV diameter 1 busbar A 7A1
Bay 500 kV diameter 3 antara busbar A 7AB3
dan B
Bay 500 kV diameter 5 busbar B 7B5
Kode tegangan dari primer dan sekunder trafo dapat dilihat pada tabel 4.

111
SPLN S5.001: 2008

Tabel 4. Kode tegangan dari primer dan sekunder trafo

Tegangan Range Kode


Tegangan Rendah (TR) sampai 1000 V 0
Tegangan Menengah (TM) 1 sampai 10 kV 1
Tegangan Menengah (TM) 10 sampai 30 kV 2
Tegangan Menengah (TM) 30 sampai 60 kV 3
Tegangan Tinggi (TT) 60 sampai 90 kV 4
Tegangan Tinggi (TT) 90 sampai 200 kV 5
Tegangan Tinggi (TT) 200 sampai 400 kV 6
Tegangan Ekstra Tinggi (TET) 400 sampai 600 kV 7
Tegangan Ekstra Tinggi (TET) 600 sampai 1000 kV 8
Tegangan Ekstra Tinggi (TET) 1000 kV ke atas 9

F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen

Kode nama peralatan atau nama alarm atau nama elemen terdiri dari 5
karakter. Contohnya dapat dilihat pada tabel 5.

Tabel 5. Kode nama peralatan/alarm/elemen

Nama Kode
Circuit Breaker CB
Bus Isolator #1 BI1
Bus Isolator #2 BI2
Line Isolator LI
Ground Fault GF
Over Current OC
Line Trip LT
Breaker Fault BRF
Power Supply Faulty PSF
Daya MW P
Daya MVAr Q
Arus I
Load Break Switch LBS
Recloser REC
Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal,
telemeasurement atau remote kontrol seperti ditunjukan pada Lampiran A-D).

G. Status Peralatan atau Status Alarm

Status peralatan atau status alarm terdiri dari 15 karakter, menunjukkan status
dari peralatan atau alarm pada bagian E.
Contohnya adalah sebagai berikut:

Close
Open
Invalid
Appear
Disappe
ar On
Off

112
H. Nama user yang melakukan aksi

Nama user terdiri dari 10 karakter, menunjukkan nama user yang login pada
Off
Off SPLN S5.001: 2008
H. Nama
Offuser yang melakukan aksi
H.
NamaNama userterdiri
user yang melakukan aksi menunjukkan nama user yang login pada
dari 10 karakter,
H. Nama user yang melakukan aksi
saat melakukan aksi tertentu seperti Remote Control, Overall Check, start dan stop
Nama
perangkatuser terdiri
keras, out dari 10 karakter,
of service RTU dan Intermenunjukkan
Center Link,nama user yang login pada
dan sebagainya.
saat melakukan
Nama user terdiri aksidari
tertentu seperti Remote
10 karakter, Control, nama
menunjukkan Overalluser
Check, start
yang dan pada
login stop
Contohnya
perangkat adalah
keras, outsebagai
of berikut:
service RTU dan Inter Center Link, dan sebagainya.
saat melakukan aksi tertentu seperti Remote Control, Overall Check, start dan stop
perangkat
Adi keras,
Contohnya adalah outsebagai
of service RTU dan Inter Center Link, dan sebagainya.
berikut:
Lukman
Contohnya adalah sebagai berikut:
Adi
Jufri
Lukman
Adi
Joko
Jufri
Lukman
Syafnir
Joko
Jufri
Kuncoro
Syafnir
Joko
Kuncoro
Syafnir
I. Prioritas Alarm
Kuncoro
I. Prioritas
Prioritas Alarm
alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class
I. Prioritas Alarm
1 merupakan kelas alarm yang menempati prioritas paling tinggi.
Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class
Contohnya
1 merupakan
Prioritas alarmsebagai
kelas
terdiri berikut:
alarm
dari yang menempati
8 karakter, prioritas kelas
menunjukkan palingalarm
tinggi.yang ditampilkan. Class
1 merupakan
Class-1
Contohnya kelas alarm
sebagai berikut: yang menempati prioritas paling tinggi.
Class-2
Contohnya sebagai berikut:
Class-1
Class-3
Class-2
Class-1
Class-4
Class-3
Class-2
StrukturClass-4
Class-3
Informasi Khusus
Class-4
Struktur
Penamaan Informasi
PemutusKhusus Tenaga Pada Gardu Induk 1 ½ Breaker.
Struktur Informasi Khusus
Struktur
Penamaan informasi
Pemutus khusus
Tenagauntuk
Padapemutus
Gardu Induk tenaga
1 ½ pada gardu induk 1 ½ breaker
Breaker.
dipakai
Penamaan untuk
Pemutustujuan komunikasi
Tenagauntuk verbal
Padapemutus
Gardu Induk diantara operator.
1 ½ pada
Breaker. Kode tersebut hanya
Struktur
ditampilkan di VDU (Video Display Unit), dan dipergunakan diinduk
informasi khusus tenaga gardu 1 ½database.
dalam breaker
dipakai
Struktur untuk
Struktur informasi
informasi tujuan
khususkomunikasi
dinyatakan untuk verbal
pemutus
dengan susunan diantara
tenaga
sebagai operator.
pada garduKode
berikut: induktersebut hanya
1 ½ breaker
ditampilkan
dipakai untuk di VDU
tujuan(Video Displayverbal
komunikasi Unit), diantara
dan dipergunakan di dalam
operator. Kode database.
tersebut hanya
Struktur informasi
ditampilkan di VDUdinyatakan dengan susunan
(Video Display Unit), dansebagai berikut:
dipergunakan di dalam database.
X informasi
Struktur Y dinyatakan dengan
Z susunan sebagai berikut:
BagianX X: kode referensi
Y tegangan
Z
BagianX Y: kode namaY CB Bagian Z Z: nomor diameter
Bagian X: kode referensi tegangan
Contoh Y:
Bagian X: kode nama CB tegangan
referensi Bagian Z: nomor diameter
A
Bagian untuk
Y: kodebreaker
nama yang
CB terhubung
Bagian langsung
Z: nomor ke busbar A
diameter
Contoh
B untuk breaker yang terhubung langsung ke busbar B
A
Contoh
AB untuk breaker
untuk breaker yang
yang terhubung
terhubung ke langsung
breakerkeA busbar A
dan breaker B
B
A untuk breaker yang terhubung langsung ke ke busbar
busbar BA
Contohnya
AB untukdapat dilihat
breaker yangpada gambarke
terhubung 4 breaker
dan gambar
B langsung keAbusbar
dan breaker
B B
5.
AB Untuk tegangan
untuk breaker500 kV
yang diameter
terhubung no.
ke
Contohnya dapat dilihat pada gambar 4 dan gambar 1breaker A dan breaker B
Untuk
5. Untuktegangan
Contohnya dapat150
tegangan kVkV
dilihat
500 diameter
pada no.4
gambar
diameter no.41 dan gambar
5. Untuk
Untuk tegangan
tegangan 150500kVkV diameter
diameter no. 1
no.4
Untuk tegangan 150 kV diameter no.4

Gambar 4. Struktur informasi khusus (bay diameter)

Gambar 4. Struktur informasi khusus (bay diameter)


Gambar 4. Struktur informasi khusus
113 (bay diameter)
SPLN S5.001: 2008

GITET 500 kV SAGULING

Contoh :

UNIT 1 UNIT 2 UNIT 3 UNIT 4


~ ~ ~ ~

BANDUNG SELATAN 2

BUSBAR A

7A1 7A2 7A3

7AB1 7AB2 7AB3 7AB4 7AB5

7B1 7B2 7B3 7B4 7B5

BUSBAR B

CIBINONG 1 CIBINONG 2 CIRATA 1 CIRATA 2 BANDUNG


SELATAN 1

Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker)

114
SPLN S5.001: 2008

LAMPIRAN F – SIMBOL DAN WARNA

Simbol-simbol gambar yang digunakan mengacu pada gambar 6.

SIMBOL GAMBAR

Generator
Trafo Daya Dua Belitan

Circuit Breaker

Circuit Breaker Rack Trafo Daya Tiga Belitan

PBO
Pemutus Balik Otomatis
Cut out fuse

Load Break Switch


I Arus

Isolating Switch
( Disconecting Switch ) V Tegangan

Earthing Switch F Frekuensi

Surge / Lightning Arester PQ Daya aktif

TPI Daya reaktif


Current Transformer
( 3 phases )
RCD Tap Position Indication
Voltage Transformer
RCA Remote Control Digital

Remote Control Analog


Reaktor

TSS Telesignal Single


Kapasitor

TSS Telesignal Double

Capacitor Voltage L/R Local/ Remote


Transformer

LFC(Po, Pr, N) Load Frequency Control


Gardu Distribusi

Gambar 6. Simbol gambar

115
SPLN S5.001: 2008

Tampilan-tampilan status yang digunakan mengacu pada gambar 7.


Tampilan Status

ITEMS SYMBOL REMARK

CB CLOSED Busba'r s color, filled

CB OPENED Busba'r s color, blank


PBO
PBO CLOSED Feeder’s colo,rfilled
PBO
PBO OPENED Feeder’s colo,rblank

LBS CLOSED Feeder’s color


Feeder’s color
LBS OPENED

DS CLOSED Feeder’s colo,rfilled

DS OPENED Feeder’s colo,rblank

ES CLOSED Feeder’s color

ES OPENED Feeder’s color

RACKED IN CB CLOSED Feeder’s colo,rfilled

RACKED IN CB OPENED Feeder’s colo,rblank

RACKED OUT CB CLOSED Feeder’s colo,rfilled

RACKED OUT CB OPENED Feeder’s colo,rblank

GARDU PORTAL TIANG Feeder’s color

GARDU TEMBOK/BESI Feeder’s color

CUT OUT FUSE Feeder’s color

GENERATOR Feeder’s color

TRANSF. 2 WINDINGS Feeder’s color

TRANSF. 3 WINDINGS Feeder’s color

REACTOR Feeder’s color

CAPACITOR Feeder’s color

VOLTAGE STATUS : LIVE

DEAD

Gambar 7. Tampilan status

116
SPLN S5.001: 2008

WARNA TAMPILAN

Tabel 6 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor
dan layar tayang.

Tabel 6. Warna tampilan

URAIAN WARNA

Single line diagram 500 kV Biru


Single line diagram 275 kV Biru-muda
Single line diagram 150 kV Merah
Single line diagram 70 kV Kuning
Single line diagram 30 kV Hijau
Single line diagram 20 kV Coklat
Single line diagram 12 kV Abu-abu
Single line diagram 6 kV Merah muda
Single line diagram 0.4 kV Hijau-muda

All devices Warna Busbar


Invalid device Ungu dan perubahan simbol
Device saat loss connection (RTU out of poll) Oranye
Background color Hitam
Ground color Biru-tua
Kondisi tidak bertegangan Putih
Perubahan status karena gangguan Frame CB warna merah, blinking
Perubahan status karena local dari gardu induk Warna Busbar, blinking + karakter ”L”
Perubahan status karena remote dari dispatcher Warna Busbar, blinking
Telemetering Putih
Invalid telemetering Ungu
Telesignal Alarm Warna kuning, blinking

Keterangan:
x Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merah
pada frame CB mengikuti warna busbar.
x Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna
pada single line diagram level tegangan terdekat.
x Warna jaringan sesuai dengan feeder colouring.
x Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan warna.

117
Pengelola Standardisasi :

PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan


Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,
www.pln-litbang.co.id
Pengelola Standardisasi :

PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan


Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,
www.pln-litbang.co.id