Anda di halaman 1dari 96

MATERIAL DAN PENGUJIAN

FIBER-REINFORCED POLYMER
(FRP)

Han Ay Lie

web: https://hanaylie.id/
mail: hanaylie@live.undip.ac.id
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

ACI 440.2R Pasal


4.2 – 4.6
SIFAT FISIK, MEKANIS,
SIFAT UMUM FUNGSI WAKTU,
KEAWETAN, KUALIFIKASI

ACI 440.2R Pasal 4.1 RESIN

MATERIAL/BAHAN PENYUSUN SERAT


LAPISAN
PELINDUNG

SHEET/WRAP

PLATE
BENTUK
ROD

STRING

2
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

ACI 440.2R Pasal 3.2 WET LAYUP

PRAIMPREGNASI
SISTEM FRP
PRECURED

NSM
ACI 440.2R Pasal 14.3

3
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

ACI 440.3R Bab 2


FRP ROD/BATANG

PENGUJIAN
UJI CABUT
ACI 440.3R Bab 3
UJI TARIK
FRP LAMINASI
SPESIMEN PIPIH
UJI TARIK
SAMBUNGAN
LEWATAN

4
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SIFAT FISIK, MEKANIS,


SIFAT UMUM FUNGSI WAKTU,
KEAWETAN, KUALIFIKASI

RESIN

MATERIAL/BAHAN PENYUSUN SERAT


LAPISAN
PELINDUNG

SHEET/WRAP MASSA JENIS


PLATE
BENTUK
ROD

STRING

KOEFISIEN EKSPANSI
SIFAT FISIK
THERMAL

PENGARUH SUHU
TINGGI

5
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

MASSA JENIS

Material FRP memiliki masa jenis 1,2 - 2,1 gram/cm3


(4 – 6 kali lebih rendah dari baja).

Massa Jenis Material FRP


KARBON ARAMID
BAJA GELAS (GFRP)
(CFRP) (AFRP)
(gram/cm3) (gram/cm3)
(gram/cm3) (gram/cm3)

7,9 1,2 - 2,1 1,5 - 1,6 1,2 - 1,5

(Sumber : Tabel 4.2.1 RSNI3 8971:2021)

6
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

KOEFISIEN EKSPANSI THERMAL


Material FRP memiliki koefisien ekspansi thermal yang
berbeda dalam arah memanjang dan melintang
Tergantung dari :
• Jenis serat
• Resin
• Fraksi volume serat
Koefisien Pemuaian, x10-6/°C
Arah
Beton Baja GFRP CFRP AFRP
Longitudinal, αL 7 s/d 11 11,7 6 s/d 10 -1 s/d 0 -6 s/d -2
Transversal, αT 7 s/d 11 11,7 19 s/d 23 22 s/d 50 60 s/d 80

(Sumber : Tabel 4.2.2 RSNI3 8971:2021)

7
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

PENGARUH SUHU TINGGI


Tg = Suhu transisi, 60 Tg 82 °C, tergantung dari jenis resin

Ada beberapa kondisi :


• T Tg, sifat mekanis polimer berkurang dan akan mulai
kehilangan kemampuan untuk mentransfer tegangan dari beton
ke serat.
• T > Tg, modulus elastisitas polimer berkurang secara signifikan
(struktur molekul berubah).
• T >>> Tg, kekuatan tarik GFRP dan CFRP menurun hingga
20% (Kumahara et al., 1993).
8
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SIFAT FISIK, MEKANIS,


SIFAT UMUM FUNGSI WAKTU,
KEAWETAN, KUALIFIKASI

RESIN

MATERIAL/BAHAN PENYUSUN SERAT


LAPISAN
PELINDUNG

SHEET/WRAP

PLATE
BENTUK
ROD

STRING

PERILAKU TARIK

SIFAT MEKANIS

PERILAKU TEKAN

9
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

PERILAKU TARIK dan MODULUS ELASTIS


Material FRP tidak mengalamin perilaku plastis (leleh)
sebelum runtuh akibat tegangan Tarik
Faktor yang mempengaruhi kuat tarik material FRP :
• Jenis serat
• Orientasi serat
• Jumlah serat
• Metode produksi serat

10
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Kuat tarik FRP diperoleh dari manufaktur dari pengujian


berdasarkan ASTM D3039/D3039M, D7205/D7205M
atau D7565/ D7565M.
• Kekuatan tarik rata-rata material FRP :


: kuat tarik ultimit berdasarkan manufaktur (MPa)
• Regangan ultimate material FRP :


: regangan runtuh ultimit (mm/mm)
11
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Untuk menentukan kuat tarik ultimit jumlah benda


uji specimen minimum 20

• Modulus elastisitas E harus dihitung berdasarkan


ASTM D3039/D3039M, D7205/D7205M, atau
D7565/D7565M

12
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

PERILAKU TEKAN

• Sistem FRP terlekat eksternal tidak boleh digunakan


sebagai perkuatan tekan karena jumlah data hasil
penelitian tidak memadai untuk dapat digunakan
sebagai validasi kehandalan system
• Modulus elastisitas tekan FRP biasanya lebih kecil dari
modulus elastisitas tarik (Ehsani, 1993).

13
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Pola kegagalan FRP akibat gaya tekan arah longitudinal


serat :
• Runtuh tarik transversal
• Patah mikro pada serat
• Runtuh geser
Faktor yang mempengaruhi kegagalan FRP akibat gaya
tekan longitudinal :
• Jenis serat
• Fraksi volume serat
• Jenis resin

14
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SIFAT FISIK, MEKANIS,


SIFAT UMUM FUNGSI WAKTU,
KEAWETAN, KUALIFIKASI

RESIN

MATERIAL/BAHAN PENYUSUN SERAT


LAPISAN
PELINDUNG

SHEET/WRAP

PLATE
BENTUK
ROD

STRING

RUNTUH RANGKAK
PERILAKU
BERDASAR
FUNGSI WAKTU
FATIK

15
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

RUNTUH RANGKAK
• Runtuh Rangkak : FRP yang mengalami beban tetap,
tiba-tiba gagal setelah periode waktu daya tahannya.
• Secara umum, serat karbon paling tidak rentan
terhadap runtuh rangkak, serat aramid tergolong
cukup rentan, dan serat gelas paling rentan
• Dari pengujian runtuh rangkak FRP, diperoleh
hubungan linier antara kekuatan runtuh rangkak dan
logaritma waktu untuk semua tingkat beban.

16
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Rasio tegangan yang menyebabkan runtuh rangkak


setelah 500.000 jam (sekitar 50 tahun) dengan
kekuatan ultimit jangka pendek dari kekuatan GFRP,
AFRP, dan CFRP adalah sekitar 0,3; 0,5; dan 0,9
(Yamaguchi et al., 1997; Malvar, 1998)
• Rekomendasi batas tegangan tetap untuk menghindari
runtuh rangkak dijelaskan dalam Pasal 9 hingga 15.
• Selama tegangan tetap FRP < batas tegangan runtuh
rangkak, maka FRP aman untuk beban tidak tetap.

17
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

FATIK

• Kondisi pengujian yang menaikkan suhu dan kadar


kelembaban material FRP menurunkan perilaku
fatik lingkungan.
• CFRP paling tidak rentan terhadap kegagalan fatik.

18
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

KEAWETAN
• Faktor yang menyebabkan menurunnya sifat mekanik
FRP sebagai fungsi waktu:
• Suhu tinggi
• Kelembapan
• Paparan kimia
• Lingkungan dan lama paparan
• Jenis dan formulasi resin
• Metode pengeringan resin
• Jenis serat
19
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

KUALIFIKASI SISTEM FRP


Sistem FRP harus memenuhi syarat terhadap :

• Data uji laboratorium independen terhadap material


kandungan FRP dan lamina yang terbentuk
• Data uji struktur yang ditinjau dari jenis
penggunaanya
• Data keawetan yang mewakili lingkungan
penggunaannya

20
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Data uji yang disediakan oleh produsen sistem


FRP harus memenuhi semua persyaratan desain
mekanik dan fisik, termasuk kekuatan tarik,
keawetan, keawetan terhadap rangkak, lekatan
substrat, dan Tg.
• Sistem komposit FRP yang belum sepenuhnya
diuji sebaiknya tidak digunakan.

21
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SIFAT FISIK, MEKANIS,


SIFAT UMUM FUNGSI WAKTU,
KEAWETAN, KUALIFIKASI

RESIN

MATERIAL/BAHAN PENYUSUN SERAT


LAPISAN
PELINDUNG

SHEET/WRAP

PLATE
BENTUK
ROD

STRING

RESIN

PENYUSUN SERAT
LAPISAN
PELINDUNG

22
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

PRIMER

BAHAN: PUTTY
• EPOKSI FILLERS
• VINIL RESIN
ESTER SATU-
• POLYESTER RANTS

ADHESIF

23
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SYARAT RESIN UNTUK SISTEM FRP

a) Sesuai dengan zat perekat ke substrat beton


b) Sesuai dengan zat perekat ke sistem
komposit FRP
c) Sesuai dengan zat perekat pada serat
penguat
d) Tahan terhadap dampak lingkungan

24
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SYARAT RESIN UNTUK SISTEM FRP


a) Sesuai dengan zat perekat ke substrat beton
b) Sesuai dengan zat perekat ke sistem komposit FRP
c) Sesuai dengan zat perekat pada serat penguat
d) Tahan terhadap dampak lingkungan
e) Kemampuan mengisi
f) Kelecakan
g) Umur pakai konsisten untuk penggunaannya
h) Pengembangan sifat mekanik yang sesuai untuk
komposit FRP
25
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

JENIS POLIMERIK RESIN


Primer
• Penetrasi permukaan beton.
• Meningkatkan lekatan adhesif untuk resin jenuh
atau adhesif.
Pengisi dempul (putty)
• Mengisi rongga kecil di substrat.
• Memperhalus permukaan tempat sistem FRP
dilekatkan.
• Mencegah terbentuknya gelembung selama proses
pengeringan resin jenuh.
26
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

JENIS POLIMERIK RESIN


Resin jenuh
• Untuk penyerapan serat, memperbaiki dan
mentransfer beban antar serat.
• Perekat untuk sistem penghamparan basah dan
menyediakan lintasan beban geser antara substrat
beton yang di primer dengan sistem FRP.
Perekat
• Merekatkan prarawat laminasi FRP dan near-
surface mounted (NSM) ke substrat beton.
• Mengikat beberapa lapisan laminasi FRP.
27
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SERAT

• Macam-macam serat: gelas, aramid, dan karbon


• Dapat memberikan kekuatan dan kekakuan pada
sistem FRP.
• Detail sifat-sifat serat dijelaskan dalam
Lampiran A pada RSNI3 8971:2021
• Detail jenis serat diberikan dalam ACI 440R

28
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

LAPISAN PELINDUNG

• Berfungsi untuk melindungi lekatan perkuatan


FRP dari berbagai potensi kerusakan pengaruh
lingkungan dan mekanis.

• Pelapis biasanya dipasang di permukaan luar


sistem FRP setelah proses pelekatan atau
pengeringan resin jenuh.

29
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

JENIS LAPISAN PELINDUNG


a) Lapisan polimer umumnya berupa epoksi atau poliuretan.
b) Lapisan akrilik berupa sistem akrilik biasa atau sistem
akrilik berbasis semen.
c) Sistem semen yang memerlukan pengkasaran permukaan
FRP dan dapat dipasang dengan cara yang sama yang
dapat diterapkan pada permukaan beton.
d) Pelapis tahan api (intumescent) berbasis polimer yang
digunakan untuk perlindungan terhadap kebakaran pasif,
kontrol penyebaran api, dan pembentukan asap sesuai
kode/syarat yang ada.
30
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Sistem perlindungan juga dibutuhkan untuk


melindungi sistem FRP yang telah terpasang pada
permukaan beton, karena:
a) Perlindungan terhadap cahaya ultraviolet.
b) Antisipasi kebakaran.
c) Vandalisme.
d) Impak, abrasi, dan keausan.
e) Estetika.
f) Daya tahan terhadap bahan kimia.
g) Perendaman dalam air yang dapat diminum.

31
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SIFAT FISIK, MEKANIS,


SIFAT UMUM FUNGSI WAKTU,
KEAWETAN, KUALIFIKASI

RESIN

MATERIAL/BAHAN PENYUSUN SERAT


LAPISAN
PELINDUNG
SHEET/WRAP
SHEET/WRAP

PLATE
BENTUK
ROD

STRING

PLATE
BENTUK
FRP
ROD

STRING
32
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Sheet/Wrap

(PT Sika Indonesia)

33
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

String

(PT Sika Indonesia)

34
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Plate

(PT Sika Indonesia)

35
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Rod

(PT Sika Indonesia)


36
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

SHEET/WRAP
Wrap (SikaWrap®-231 C) adalah kain serat karbon
tenun searah dengan kekuatan tinggi, dirancang untuk
pemasangan menggunakan proses aplikasi kering atau
basah.

Wrap digunakan sebagai penguatan pada struktural:


• Beton bertulang
• Pasangan bata
• Elemen atau struktur bata dan kayu

37
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Wrap juga digunakan untuk meningkatkan kapasitas


beban lentur dan geser, seperti:

• Peningkatan kinerja seismik dari pasangan


dinding bata
• Mengganti tulangan baja yang hilang
• Meningkatkan kekuatan dan daktilitas kolom
• Meningkatkan kapasitas beban elemen struktural

38
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Memungkinkan perubahan guna bangunan


maupun perbaikan
• Memperbaiki desain strutur dan/atau cacat
konstruksi
• Meningkatkan ketahanan terhadap pergerakan
gempa
• Meningkatkan masa pakai dan daya tahan
peningkatan struktur agar sesuai dengan standar
saat ini

39
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Kekuatan tarik serat kering : 4900 MPa


Modulus elastisitas tarik serat kering : 230.000 Mpa
Regangan putus serat kering : 1,7%
Kepadatan serat kering : 1,80 gr/cm3
Kepadatan area : 235 gr/m3
Ketebalan serat kering : 0,129 mm
Lebar produk : 500 mm

(Sumber: Brosur Produk PT Sika Indonesia)

40
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

PLATE
Plate (Sika® CarboDur® S) adalah laminasi serat karbon yang
diperkuat serat karbon (CFRP) yang dirancang untuk
memperkuat struktur polimer beton, kayu, pasangan bata,
baja dan serat.

Pelat Sika® CarboDur® direkatkan ke struktur sebagai


tulangan yang direkatkan secara eksternal menggunakan
perekat berbasis resin epoksi Sikadur®-30.

41
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Kekuatan tarik laminasi : 3100 MPa


Modulus elastisitas laminasi : 165000 Mpa
Regangan putus laminasi akibat tarik : 1,8%
Kepadatan : 1,6 gr/cm3

Luas
Tipe Sika®
Lebar (mm) Tebal (mm) Penampang
CarboDur® S
(mm2)
512 50 1,2 60
812 80 1,2 96
1012 100 1,2 120
(Sumber: Brosur Produk PT Sika Indonesia)

42
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

ROD
Rod (Sika® CarboDur® BC rods) adalah laminasi serat karbon
yang diperkuat serat karbon (CFRP) dengan penampang
melingkar, dirancang untuk memperkuat beton, kayu dan
batu.

Batang Sika® CarboDur® BC diikat ke dalam slot sebagai


tulangan yang dipasang di dekat permukaan menggunakan
perekat berbasis resin epoksi Sikadur®-330 atau Sikadur®-30
untuk suhu aplikasi normal.

43
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Plate dan Rod memiliki kegunaan yang sama yaitu


untuk meningkatkan atau memperbaiki kinerja dan
ketahanan struktur untuk:

• Peningkatan kapasitas beban


• Mencegah kehancuran elemen struktur
• Peningkatan masa layan dan daya tahan
• Perubahan sistem struktural
• Ketahanan terhadap berbagai kemungkinan
• Memperbaiki cacat desain atau konstruksi

44
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Kekuatan tarik laminasi : 3100 MPa


Modulus elastisitas tarik laminasi : 148000 MPa
Regangan putus laminasi akibat tarik : > 1,7%
Kepadatan : 1,6 gr/cm3

Tipe Sika® Diameter Luas Penampang


CarboDur® BC (mm) (mm2)
BC8 8 60
BC10 10 96
(Sumber: Brosur Produk PT Sika Indonesia)

45
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

STRING
String (SikaWrap® FX-50 C) adalah string serat karbon
searah, terbungkus dalam amplop plastik, yang digunakan
sebagai penguatan yang dipasang di dekat permukaan dan
sebagai konektor serat untuk penjangkaran kain SikaWrap®
String digunakan untuk:
• Mengikat kain karbon dan serat kaca SikaWrap® pada
beton atau pasangan bata
• Menghubungkan serat karbon atau serat kaca SikaWrap®
melalui struktur beton atau pasangan bata
• Penguatan flexible near surface mounted (NSM)
46
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Kekuatan tarik serat kering : 4000 MPa


Modulus elastisitas tarik serat kering : 240000 Mpa
Regangan putus serat kering akibat tarik : ≥ 1,6%
Kepadatan serat kering : 1,82 gr/cm3
Luas penampang : ≥ 28 mm2

(Sumber: Brosur Produk PT Sika Indonesia)

47
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

ACI 440.2R Pasal 3.2 WET LAYUP

PRAIMPREGNASI
SISTEM FRP
PRECURED

NSM
ACI 440.2R Pasal 14.3

48
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

WET LAY-UP/PENGHAMPARAN BASAH


dan
PRA-IMPREGNASI/PREPEG
Wet-lay up
Lembaran serat kering sarah atau multi-arah yang
diimpregnasi dengan resin jenuh di lapangan (sheet,
string)
Prepreg
Serat atau lembaran serat searah atau multi-arah
dikeringkan dengan resin jenuh saat proses
manufaktur (rod, plate)
49
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Sheet
Pelapisan epoxy pada permukaan beton
50
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Peletakan sheet FRP


51
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Impregnasi lapangan
52
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Finalisasi permukaan
53
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

String
Impreknasi di
lapangan

54
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Pultrusi

55
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Penempatan
string

56
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Finalisasi

57
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

ACI 440.3R Bab 2


FRP ROD/BATANG

PENGUJIAN
UJI CABUT
ACI 440.3R Bab 3
UJI TARIK
FRP LAMINASI
SPESIMEN PIPIH
UJI TARIK
SAMBUNGAN
LEWATAN

58
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

METODE UJI BATANG FRP

1. Uji sifat penampang FRP


2. Uji sifat tarik longitudinal batang FRP
3. Uji kekuatan lekat batang FRP dengan pengujian cabut
4. Uji kekuatan geser melintang batang FRP
5. Uji kekuatan bengkok FRP dan sengkang di lokasi
bengkok
6. Uji ketahanan alkali batang FRP

59
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

7. Uji penentuan fatik tarik batang FRP


8. Uji keruntuhan rangkak batang FRP
9. Uji relaksasi jangka panjang batang FRP
10. Uji kinerja angkur tulangan FRP
11. Uji sifat tarik batang tulangan FRP yang
dibengkokkan
12. Uji menentukan efek jari-jari sudut pada kekuatan
tarik batang FRP

60
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

1. Uji Sifat Penampang FRP


Metode uji ini telah digantikan oleh ASTM D7205 /
D7205M, Tensile Properties of Fiber Reinforced
Polymer Matrix Composite Bars.

2. Uji Sifat Tarik Longitudinal Batang FRP


Metode uji ini telah digantikan oleh ASTM D7205 /
D7205M, Tensile Properties of Reinforced Polymer
Matrix Composite Bars.

61
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

3. Uji Kekuatan Lekat Batang FRP dengan


Pengujian Cabut
Menentukan kekuatan lekat batang FRP yang digunakan
sebagai tulangan atau tendon prategang dalam beton.
Metode uji lekatan untuk penulangan FRP dalam
beton: (a)

(a) Spesimen Cabut

62
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Set Up Pengujian Lekatan dengan Metode Cabut

(Sumber: Gambar B.3.4.2 RSNI3 8972:2021)


63
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

(b)

(b) Spesimen Ujung-balok;

(c) Spesimen Balok Sederhana; (c)

64
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

(d) Spesimen ujung balok dengan sendi;


(e) Spesimen lewatan;
(f) Spesimen balok kantilever (tanpa tonjolan untuk
dudukan beban/dogbones);
(g) Spesimen balok kantilever (dengan tonjolan untuk
dudukan beban/dogbones)
(d) (e)

Penyebab Retak

(f) (g)

(Sumber: Gambar B.3.1a


RSNI3 8972:2021)

65
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Metode untuk spesimen uji casting


Spesimen Uji Lekatan Vertikal
PVC atau material
Tulangan FRP lain yang cocok untuk
mencegah ikatan

db
200mm
100mm

100mm 5db

200mm 200mm

Arah
pengecoran

(Sumber: Gambar B.3.1b RSNI3 8972:2021)

66
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Stirrups Ø8-100
Size in mm FRP rod Ø8 Unbonded FRP FRP rod Ø8
Bonded FRP Reinforcement 4D13 Stirrups
Ø8-100
Tensile pull-off bar
D25 Steel bar
D25
150

Steel bar
4D13

120 250 20 30 100 120 190 150

67
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Spesimen Uji Lekatan Horizontal

(Sumber: Gambar B.3.1c RSNI3 8972:2021)

68
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

4. Uji Kekuatan Geser Melintang Batang FRP

Metode uji ini telah digantikan oleh ASTM D7617 /


D7617M, Standard Test Method for Transverse Shear
Strength of Fiber Reinforced Polymer Matrix
Composite Bars.

69
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

5. Uji Kekuatan Bengkok FRP dan Sengkang di


Lokasi Bengkok

Menentukan kekuatan bagian bengkok yang disediakan


sebagai angkur dengan variabel utama adalah ukuran,
radius bengkok, atau jenis sengkang FRP.

Metode uji ini mengukur kapasitas beban ultimit dari


sengkang FRP tunggal yang dikenai gaya tarik pada arah
bagian yang lurus.

70
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Konfigurasi Spesimen
Dimensi masing-masing blok beton yang digunakan untuk
pengangkuran sengkang FRP dapat bervariasi sesuai
dengan dimensi sengkang yang digunakan. Panjang bebas
sengkang di antara kedua balok tidak boleh kurang dari 200
mm.

(Sumber: Gambar B.5.5.1


RSNI3 8972:2021)

71
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Set Up Pengujian

(Sumber: Gambar B.5.7.1 RSNI3 8972:2021)


72
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

6. Uji Ketahanan Alkali Batang FRP

Menentukan data ketahanan terhadap alkali (alkali


resistance) untuk spesifikasi material, penelitian dan
pengembangan, jaminan mutu, dan desain dan analisis
struktural.
Metode uji ini mengukur perubahan massa dan kapasitas
tarik batang FRP setelah perendaman dalam larutan alkali
tanpa tegangan (Prosedur A), kapasitas tarik batang FRP
setelah perendaman dalam larutan alkali dan kapasitas
tarik batang FRP yang tertanam dalam beton yang
lembab dengan kondisi beban tetap (Prosedur B dan C).
73
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Tiga prosedur yang dilakukan pada suhu 60°C, masing-


masing pada kondisi beban yang berbeda.

• Prosedur A — Spesimen FRP direndam dalam larutan


alkali tanpa beban tarik. Parameter kontrol tes adalah
nilai pH dan suhu larutan alkali dan waktu perendaman.
Sampel untuk Prosedur A harus direndam dalam larutan
alkali pada 60 ± 3°C selama 1, 2, 3, 4, dan 6 bulan,
kecuali ditentukan lebih lama dari waktu tersebut.
Setelah waktu yang ditentukan, sampel harus
dikeluarkan dari larutan alkali, dicuci secara
menyeluruh dalam air deionisasi, dikeringkan,
ditimbang, dan diuji tarik sampai gagal.
74
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Prosedur B – Spesimen FRP direndam dalam larutan


alkali dengan beban tarik tetap. Parameter uji adalah
tingkat beban tetap, nilai pH, dan suhu larutan dan
perendaman alkali waktu.

Sampel untuk Prosedur B harus dipasang pada


perangkat penahan di kedua ujungnya sesuai dengan
ASTM D7205 / D7205M. Bagian uji spesimen harus
direndam dalam larutan alkali di dalam wadah
penyimpanan larutan alkali dan memiliki suhu konstan
60 ± 3°C.

75
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Prosedur C – Spesimen FRP, dikelilingi oleh beton


lembap, dikenakan beban tarik tetap. Parameter uji
adalah tingkat beban berkelanjutan, nilai pH, dan suhu
beton dan waktu tertanam.

Sampel untuk Prosedur C harus disiapkan dengan


menanamkan bagian uji spesimen dalam beton lembap.
Dimensi khas silinder beton ditunjukkan pada Gambar
B.6.6.3. Dimensi spesimen sebesar 150 mm dapat
ditambahkan jika digunakan batang berdiameter lebih
besar.

76
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Dimensi Silinder Beton

(Sumber: Gambar B.6.6.3 RSNI3 8972:2021)

77
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

7. Uji Penentuan Fatik Tarik batang FRP


Bertujuan untuk menentukan jumlah siklus beban
berulang yang diperlukan untuk gagal pada batang FRP.

Kehilangan kekuatan yang terkait dengan kerusakan


fatik dapat ditentukan dengan menghentikan
pembebanan siklik untuk mendapatkan kekuatan tarik
quasi-statik menggunakan ASTM D7205 / D7205M.

8. Uji Keruntuhan Rangkak Batang FRP


Metode uji ini telah digantikan oleh ASTM
D7337/D7337M.
78
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

9. Uji Relaksasi Jangka Panjang Batang FRP


Berfungsi untuk mengevaluasi perilaku relaksasi jangka
panjang batang FRP yang digunakan sebagai tendon
prategang dalam beton dan pasangan dengan suhu dan
regangan yang konstan.
Dokumen referensi:
• ASTM D618-08—Standard Practice for Conditioning
Plastics for Testing
• ASTM D7205/D7205M-06(2011)—Standard Test
Method for Tensile Properties of Fiber Reinforced
Polymer Matrix Composite Bars
• ASTM E4-10—Standard Practices for Force
Verification of Testing Machines
79
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Gunakan mesin uji dengan kapasitas pemuatan yang


melebihi beban relaksasi spesimen uji dan dikalibrasi
sesuai dengan ASTM E4.
• Mesin uji harus mampu memuat pada kecepatan (200 ±
50) MPa/menit dan mempertahankan beban serta
regangan konstan. Fluktuasi regangan tidak lebih dari ±
25×10-6.
• Jika batang FRP tergelincir dari bagian penahan, jarak
slip harus dikompensasi agar tidak mempengaruhi hasil
pengujian.
• Keakuratan pembacaan atau perekaman otomatis beban
harus dalam 0,1 persen dari beban awal.
80
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

10. Uji Kinerja Angkur Tulangan FRP


Menetapkan persyaratan uji untuk kinerja angkur
tulangan FRP yang digunakan sebagai tendon prategang
pratarik pada beton dan pasangan.

Dokumen referensi:
• ASTM D7205 / D7205M-06 (2011) — Standard Test
Method for Tensile Properties of Fiber Reinforced
Polymer Matrix Composite Bars
• ASTM E4-10 — Standard Practices for Force
Verification of Testing Machines

81
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

FRP
Wrap

Epoxy

15
15

coakan

clip
82
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

11. Uji Sifat Tarik Batang Tulangan FRP yang


Dibengkokkan
Menentukan data tarik lentur tulangan FRP yang
dibengkokkan untuk spesifikasi bahan, penelitian dan
pengembangan, jaminan mutu, desain dan analisis struktur.

Dokumen referensi:
• ASTM D618-08 — Standard Practice for Conditioning
Plastics for Testing
• ASTM D7205 / D7205M-06 (2011) — Standard Test
Method for Tensile Properties of Fiber Reinforced Polymer
Matrix Composite Bars
• ASTM E4-10 — Standard Practices for Force Verification
of Testing Machines
83
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Tes Set Up Tipikal Uji Lentur


a. Susunan pengujian, dengan sudut tekuk 180º

(Sumber: Gambar B.11.7.1(a) RSNI3 8972:2021)

84
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

b. Susunan pengujian, dengan sudut tekuk 180º

(Sumber: Gambar B.11.7.1(b) RSNI3 8972:2021)

85
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

12. Uji Menentukan Efek Jari-jari Sudut pada


Kekuatan Tarik Batang FRP
Menentukan efek jari-jari sudut pada sifat tarik
batang FRP, di mana batang mengalami tegangan
tarik.

Pengujian tarik dilakukan dengan perlengkapan uji


khas. Perlengkapan uji terdiri dari tiga komponen:
bagian, bawah, dan sisipan sudut yang dapat ditukar,
yang terbuat dari logam seperti aluminium atau baja.

86
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Peralatan Pengujian Tarik


• (a) Perakitan peralatan uji; dan (b) Sketsa

(Sumber: Gambar B12.3.1a RSNI3 8972:2021)


87
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Bagian atas peralatan uji (dalam mm)

(Sumber: Gambar B12.3.1b RSNI3 8972:2021)


88
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Bagian bawah peralatan uji:


(a) baji; dan (b) bagian bawah (dalam mm)

(Sumber: Gambar B12.3.1c RSNI3 8972:2021)


89
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Baji dan sudut penyisipan yang dapat diganti:


(a) sudut pemasukan; dan (b) pemegang

(Sumber: Gambar B12.3.1d RSNI3 8972:2021)


90
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Peralatan tarik dibutuhkan dua set (yoke) (dalam mm)

(Sumber: Gambar B12.3.1e RSNI3 8972:2021)


91
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

• Pemasangan benda uji dan pengaturan alat ukur


regangan (dalam mm)

(Sumber: Gambar B12.3.1f RSNI3 8972:2021)


92
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

UJI CABUT
UJI TARIK
FRP LAMINASI
SPESIMEN PIPIH
UJI TARIK
SAMBUNGAN
LEWATAN

93
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

PENGUJIAN FRP LAMINASI

1. Uji Cabut
• Telah digantikan oleh ASTM D7522 / D7522M

2. Uji Tarik Spesimen Pipih


• Telah digantikan oleh ASTM D7565 / D7565M

3. Uji Tarik Sambungan Lewatan


• Telah digantikan oleh ASTM D7616 / D7616M

94
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

Ay Lie Han; Hsuan-Teh Hu; Buntara S. Gan; Fu-Pei Hsiao; Yanuar Haryanto, 2022, “Carbon Fiber-Reinforced Polymer Rod
Embedment Depth Influence on Concrete Strengthening”, Arabian Journal for Science and Engineering
https://doi.org/10.1007/s13369-022-06601-2
Haryanto, Y., Hu, H. T., Han, A. L., Hsiao, F. P., Teng, C. J., Hidayat, B. A., Wariyatno, N.G., 2021, “Negative moment region flexural
strengthening system of RC T-beams with half-embedded NSM FRP rods: a parametric analytical approach”, Journal of the Chinese
Institute of Engineers, Vol. 44(6), Pp. 553-561.
https://doi.org/10.1080/02533839.2021.1936646
Utomo, J., Khusyeni, M. N., Partono, W., Han, A. L., Gan, B. S., 2021, “Experimental Investigation on the Failure Behavior of Carbon
Fiber Reinforced Polymer (CFRP) Strengthened Reinforced Concrete T-beams”, Civil Engineering Dimension, Vol. 23(2), Pp. 115-122.
https://doi.org/10.9744/ced.23.2.115-122
Yanuar Haryanto; Hsuan-Teh Hu; A. L. Han; Fu-Pei Hsiao; Chrang-Jen Teng; Banu A. Hidayat; Laurencius Nugroho, 2021 “Numerical
investigation on RC T-beams strengthened in the negative moment region using NSM FRP rods at various depth of embedment”
Computers and Concrete, 28 (4), pp. 347-360, 2021.
https://doi.org/10.9744/ced.23.2.115-122
Junaedi Utomo; Nauval Rabbani; Sri Tudjono; Ay Lie Han; Sukamta, 2021, “The Influence of External CFRP String Reinforcement on
The Behavior of Flexural RC Elements” JGEET (Journal of Geoscience, Engineering, Environment, and Technology), 6 (3), pp. 141 -
146, 2021, ISSN: 2541-5794.
Sri Tudjono, Han Ay Lie, Buntara Sthently Gan, 2018, “An Integrated System for Enhancing Flexural Members’ Capacity via
Combinations of the Fiber Reinforced Plastic Use, Retrofitting, and Surface Treatment Techniques”, International Journal of
Technology Vol 9(1), pp. 1-15.
http://ijtech.eng.ui.ac.id/article/view/298
Agung Budipriyanto, Ay Lie Han, Hsuan Teh Hu., 2018, “Bond-shear Behavior of FRP Rods as a Function of Attachment
Configuration”, Journal of Advanced Civil & Environmental Engineering, Vol 1(1), pp 9-17.
https://doi.org/10.30659/jacee.1.1.9-17
Han, A.L., Gan, B.S., Budipriyanto, A., 2018, “Shear-bond behavior of fiber reinforced polymer (FRP) rods and sheets”, MATEC Web
of Conferences Vol. 195, pp. 1-7. https://www.matec-
conferences.org/articles/matecconf/abs/2018/54/matecconf_icrmce2018_02001/matecconf_icrmce2018_02001.html
95
Han Ay Lie 2022
MATERIAL DAN PENGUJIAN FIBER-REINFORCED POLYMER (FRP) Diponegoro University

2022

96
Han Ay Lie 2022