Slide Kontroler PID 3 - 2
Slide Kontroler PID 3 - 2
Pengendalian Sistem
Pendahuluan
Urutan cerita :
1. Pemodelan sistem
2. Analisa sistem
3. Pengendalian sistem
Contoh : motor DC
1. Pemodelan mendapatkan transfer function dan
blok sistem motor DC
2. Analisa memberikan inputan sinyal uji pada
motor, menganalisa respon yang dihasilkan
3. Pengendalian mengendalikan motor agar
memberikan hasil yang sesuai
Pendahuluan
Dari analisa respon sistem yang telah kita
lakukan, bagaimana respon sistem (c(t)) yang
kita inginkan?
Sesuai dengan input/r(t) (misal : unit step)
Jika tidak sesuai?
Salah satu caranya dengan menambahkan kontroler
Fungsi kontroler :
Mengendalikan sistem dengan memanipulasi sinyal
error, sehingga respon sistem (output) sama dengan
yang kita inginkan (input)
Kontroler dalam Diagram Blok
Error detector Energy or
(comparator) fuel
Controller
Error Output
Set Point
Signal Signal
+ Controller Actuator
r(t) -
e(t) u(t)
Manipulated
Feedback variable
Signal
Disturbances
Manufacturing
Process
Measured
Measurement variable
Devices Controlled
c(t) variable
Definisi kontroler
Controller
“Otak” dari sistem.
Ia menerima error / e(t) sebagai input
Lalu menghasilkan sinyal kontrol / u(t)
U(t) menyebabkan controlled variable / c(t)
menjadi sama dengan set point / r(t)
Respon Sistem
Analisa respon sistem :
Kestabilan
Respon transient (karakteristik sistem)
Error steady state
Respon yang diinginkan (set point), misal unit
step. Spesifikasi :
Unit step
1
Stabil
Karakteristik respon transient :
Mp : 0 % (sekecil mungkin) t
Tr, tp, ts : 0 (sekecil mungkin)
A Proportional Controller (Kp) will have the effect of reducing the rise time and
will reduce settling time, but never eliminate, the steady-state error.
An Integral Controller (Ki) will have the effect of eliminating the steady-state
error, but it may make the transient response worse.
A Derivative Controller (Kd) will have the effect of increasing the stability of
the system, reducing the overshoot, and improving the transient response.
The Characteristics of P, I, and D controllers
Lastly, please keep in mind that you do not need to implement all three
controllers (proportional, derivative, and integral) into a single system, if
not necessary. For example, if a PI controller gives a good enough
response (like the above example), then you don't need to implement
derivative controller to the system. Keep the controller as simple as
possible.
Kontroler Proporsional (P)
Persamaan matematis :
u(t) = KP . e(t)
Diagram Blok
+ E(s) U(s)
Ki / s
-
Kontroler Integral (I)
Pengaruh pada sistem :
Menghilangkan Error Steady State +
Respon lebih lambat (dibanding P)(Settling -
Time besar)
Perubahan sinyal kontrol sebanding -
Dengan kontroler PI
Kp = 2 , Ki = 1
Dengan kontroler I, Ki = 1
Aplikasi kontroler Integral
• Perhitungan dari contoh tersebut :
• Jika transfer function plant = • Jika transfer function kontroler I =
1
GP ( s )
1 GC ( s )
2s 1 s
1
• Maka transfer function open loop = G ( s)
2s 2 s
• Transfer function error = E ( s) 1 E (s) 2s 2 s
2
R( s) 1 G ( s) H ( s) R( s) 2s s 1
• TF Error steady state = E lim sE ( s ) 2s 2 s 1
ss E ( s) 2
s 0 2s s 1 s
2s 2 s 1
Ess lim s 2 0
s 0 2 s s 1 s