ABSTRACT
Halokarbon refrigerant or R22 used in refrigeration systems later revealed potentially
damaging the ozone layer, as replacement could be used a hydrocarbon refrigerant, one of
which is environmentally friendly HCR22 refrigerant. In this study conducted experimental
study of vapor compression refrigeration machine that compares the performance of the
engine in transient conditions using hydrocarbon refrigerant substitutes for R22 (HCR22)
and the refrigerant halokarbon (R22). The results showed that the use of hydrocarbon
refrigerant HCR22 (10.6 oC temperature achieved at the time 10 minutes) lower
temperature achieved faster than using the R22 (19.8 oC temperature achieved at the time
10 minutes). This result is comparable with the resulting COP, COP with HCR22 (3.104
after 50 minutes) is greater than the R22 COP (2.123 after 50 minutes). Compressor power
used by HCR22 (0.846 kW after 65 minutes) is smaller than the R22 (0.953 kW after 65
minutes). Can be concluded that the use of hydrocarbon refrigerant to produce cooling low
temperature more rapid with a more efficient electrical consumption of compressors .
Keywords : transient, refrigeration, halocarbon, hydrocarbon
1. PENDAHULUAN “Gambar (2)” dapat membantu dalam menentukan
parameter-parameter tersebut.
Mesin refrigerasi atau disebut juga mesin pendingin
adalah mesin yang dapat menimbulkan efek
refrigerasi, sedangkan refrigeran adalah zat yang Qk
digunakan sebagai fluida kerja untuk menimbulkan
2
efek refrigerasi tersebut. Efek refrigerasi atau efek 3
pendinginan adalah suatu efek penyerapan panas dari
Kondensor
suatu zat atau produk sehingga temperaturnya berada Wkom
di bawah temperatur lingkungan. Katup Kompresor
ekspansi
Secara umum bidang refrigerasi mencakup kisaran Evaporator
75
Jurnal Teknik Mesin Vol. 6, No.2,Desember 2009 ISSN 1829-8958
Pada mesin refrigerasi efek pendinginan dan efek refrigeran halokarbon. (Pasek, A.D.,Tandian, N.P.,
pemanasan dapat dihasilkan dan dimanfaatkan secara 2000). Refrigeran hidrokarbon adalah refrigeran yang
bersamaan, agar daya guna mesin menjadi lebih ramah lingkungan, hal ini diperlukan agar
tinggi. Mesin refigerasi dengan fungsi ganda ini kelestarian lingkungan terjaga, karena lapisan ozon di
dikenal dengan mesin refrigerasi hibrida, karena stratosfir berfungsi melindungi bumi dari radiasi
mesin refrigerasi ini beroperasi dengan siklus sinar ultra violet intensitas tinggi yang berbahaya
kompesi uap, maka mesin ini disebut mesin (antara lain dapat menimbulkan kanker kulit, katarak
refrigerasi siklus kompresi uap hibrida. (Amrul, mata, menurunkan immunitas tubuh, dapat
2001) membunuh phytoplankton yang merupakan bagian
dari rantai kehidupan laut) (Pasek, A.D.,Tandian,
Pada sistem kompresi uap, refrigeran menyerap kalor
N.P., Adriansyah W., 2004). Perangkat
dari suatu ruang melalui proses evaporasi dan
pengkondisian udara umumnya menggunakan
membuang kalor ke ruang lain melalui proses
refrigeran halokarbon jenis R22, sebagai alternatif
kondensasi. Refrigeran adalah fluida kerja yang
pengganti maka digunakan refrigeran hidrokarbon
digunakan untuk mentransfer panas di dalam siklus
pengganti R22 (HCR22).
refrigerasi. Sifat-sifat yang dipertimbangkan dalam
memilih refrigeran, adalah: sifat kimia, sifat fisik dan
2. METODOLOGI
sifat termodinamik. Berdasarkan sifat-sifat kimianya
refrigeran yang baik adalah: tidak beracun, tidak Fasilitas pengujian terdiri dari satu unit mesin
bereaksi dengan komponen refrigerasi, dan tidak refrigerasi, seperangkat alat ukur dan beberapa
mudah terbakar, serta tidak berpotensi menimbulkan peralatan pendukung. Mesin refrigerasi beroperasi
pemanasan global (non-GWP(Global Warming pada dua siklus yaitu siklus primer dan siklus
Potential)) dan tidak merusak lapisan ozon (non- sekunder. Siklus primer merupakan siklus refrigeran
ODP (Ozone Depleting Potential) sedangkan siklus sekunder merupakan siklus air
(chiller). Penelitian dilakukan di Laboratorium
Refrigeran hidrokarbon merupakan salah satu
Perawatan dan Perbaikan, Teknik Mesin, Fakultas
refrigeran alternatif pengganti refrigeran halokarbon
Teknik, Universitas Riau.
(CFC). Refrigeran hidrokarbon tidak berpotensi
merusak ozon karena ODP = 0 dan GWP yang kecil.
Refrigeran hidrokarbon juga tidak mengalami reaksi
kimia dengan oli pelumas yang digunakan untuk
76
Studi Eksperimental Mesin Refrigerasi Siklus Kompresi Uap Menggunakan Refrigeran Hidrokarbon Substitusi R22 pada Kondisi Transient (Azridjal Aziz)
Komponen siklus primer terdiri dari dua unit refrigerannya (420 gram) lebih kecil dibanding R22
evaporator, dua unit kondensor, satu buah kompresor, (900 gram).
satu buah alat ekspansi dan beberapa komponen
pendukung seperti pompa air listrik, blower. 47
Sedangkan pada siklus sekunder terdapat satu unit 44
41
kabin pendingin, satu unit kabin pengering, sebuah
38
koil pendingin dan pemanas serta satu buah katup 35
T out kondensor C
solenoid. Skema sederhana fasilitas pengujian 32 R22
HCR22
”Gambar (3)”. 29 R22
26 HCR22
Pow er (HCR22)
23 Pow er (R22)
3. HASIL DAN PEMBAHASAN Pow er (R22)
20
Massa Refrigeran R22 dan HCR22 17
14
Pada penambahan massa refrigeran dengan selang 11
penambahan massa setiap 40 gram, “Gambar (4)” 8
5
terlihat bahwa massa refrigeran optimum R22
0 15 30 45 60
sebesar 900 gram pada COP 2,42. Sedangkan massa Waktu (menit)
refrigeran optimum HCR22 sebesar 420 gram pada
COP 2,55. Dengan menggunakan refrigeran HCR 22 Gambar 5. Laju Pendinginan dan Pemanasan
massa refrigeran lebih hemat 57 persen dari massa
refrigeran R22. COP HCR22 sedikit lebih tinggi dari Perubahan COP terhadap Waktu
COP R22 dengan jumlah refrigeran yang sangat Perubahan COP terhadap waktu sebanding dengan
sedikit. laju pendinginan yang dihasilkan, COP dengan
COPHCR22 COP R22 HCR22 (3,104 setelah 50 menit) lebih besar
3.0
Poly. (COPHCR22) Poly. (COP R22) dibanding COP dengan R22 (2,123 setelah 50 menit).
Hal ini berarti bahwa HCR22 menyerap kalor lebih
2.5
banyak daripada R22 sehingga diperoleh COP yang
Performansi
1.5
4.00
1.0 3.50
Pendinginan kWatt
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10 0
10 0
11 0
11 0
40
3.00
30
34
38
42
46
50
54
58
62
66
70
74
78
82
86
90
94
98
2
6
0
1.10
Sedangkan laju pemanasan menggunakan R22 Log. (Wk HCR22)
1.00
setelah 30 menit dicapai temperatur 40,3 oC
sedangkan dengan HCR 22 setelah 30 menit dicapai 0.90
Daya kompresor yang digunakan dengan HCR22 dan Paralel dengan Menggunakan Refrigeran
(0,846 kW setelah 65 menit) lebih kecil Hidrokarbon HCR-12, Tesis, Jurusan Teknik
dibandingkan dengan R22 (0,953 kW setelah 65 Mesin, ITB, Bandung, 2001.
menit). Hal ini terjadi karena massa refrigeran yang
2. Arora, C. P. Refrigeration and Air
digunakan dengan HCR22 lebih sedikit dari R22,
Conditioning. Mc. Graw-Hill International
sehingga kerja kompresor menjadi lebih rendah
Edition. 2001.
dibandingkan menggunakan HCR22. “Gambar (7)”.
3. Aziz, Azridjal. Kaji Eksperimental Pengaruh
4. KESIMPULAN DAN SARAN Perubahan Suhu pada Siklus Sekunder dan
Siklus Primer terhadap Performansi Mesin
Kesimpulan yang dapat diambil dari dari penelitian
Refrigerasi Hibrid dengan Refrigeran
ini adalah :
Hidrokarbon HCR12. Jurnal Saintek Lemlit
1. Laju pendinginan dan pemanasan menggunakan UNP. 2004.
refrigeran hidrokarbon HCR22 lebih cepat
4. Aziz, Azridjal. Penggunaan Hidrokarbon
dicapai dibandingkan menggunakan R22.
sebagai Refrigeran pada Mesin Refrigerasi
2. COP dengan HCR22 (3,104 setelah 50 menit) Siklus Kompresi Uap Hibrida dengan
lebih besar dibanding COP dengan R22 (2,123 Memanfaatkan Panas Buang Perangkat
setelah 50 menit). Pengkondisian Udara. Laporan Penelitian
Lemlit Universitas Riau. Pekanbaru. 2005.
3. Daya kompresor yang digunakan dengan
HCR22 (0,846 kW setelah 65 menit) lebih kecil 5. Moran, M.J., and Saphiro, H.N. Fundamental
dibandingkan dengan R22 (0,953 kW setelah 65 of Engineering Thermodinamycs. 3rd ed. New
menit). York: John Wiley & Sons, Inc. 1995.
4. HCR22 memiliki kapasitas kalor dan kalor laten 6. Pasek, A.D., and Tandian, N.P. Short Course
yang lebih besar dibanding R22, dengan jumlah on the Applications of Hydrocarbon
massa refrigeran yang lebih sedikit (420 gram) Refrigerants. International Conference on Fluid
dibanding R22 (900 gram). and Thermal Energy Conversion 2000. Bandung.
2000.
UCAPAN TERIMA KASIH 7. Pasek, A.D., Tandian, N.P., and Adriansyah
Penulis mengucapkan terima kasih kepada Lembaga W. Training of Trainer Refrigeration Servicing
Penelitian Universitas Riau yang mendanai Sector. Training Manual. Bandung: ITB. 2004.
penelitian ini melalui Dana Penelitian SPP/DPP
8. Reynolds, W., and Perkins, H.. Engineering
Universitas Riau, serta terima kasih kepada Agustiar,
Thermodynamics, 2nd ed. Singapore: McGraw-
Agus Setiadi, dan Rahmat Iman Mainil yang Hill Co. 1997
membantu penulis mewujudkan penelitian ini,
sehingga penelitian ini dapat terlaksana sepenuhnya. 9. UNEP. The Montreal Protocol on Substance
that Deplete Ozone Layer. United Nations
PUSTAKA Environment Programme. 2000.
1. Amrul, Kaji Eksperimental Karakteristik Mesin
Refrigerasi Hibrid Kompresi Uap Susunan Seri
78