Anda di halaman 1dari 11

117

LAMPIRAN B
Uraian Perhitungan Aktual

A. Perhitungan Aktual
Perhitungan Data 2 Tanggal : 20 Agustus 2019
Diketahui :
Shell = Ammonia Gas
Tabel Spesifikasi Alat pada Shell

ID 1.500 mm 59,05 in
L 7.198 mm 23,61 ft
N 1 pass -
B 899,75 mm 35,42 in
(Toyo Engineering Corporation, 1976)

Data Operasi Aktual


 Tin = 49,3 ⁰C = 121 ⁰F
 Tout = 35,5 ⁰C = 96 ⁰F
 T1 – T2 = 13,8 ⁰C = 25 ⁰F
 Tavg = 42,4 ⁰C = 108,3 ⁰F
 W = 12.267 kg/hr = 27.044,110 lb/hr
 ƛ = 468 Btu/lb …………………………………..(fig.12, Kern)
Tube = Cooling Water
Tabel Spesifikasi Alat pada Tube
ID 21,18 mm 0.0695 ft
OD 25,40 mm 1 in
L 7.200 mm 23,6160 ft
Nt 1.744 -
BWG 14 -
PT 32 mm 1,2598 in
N 1 pass -
a’t 0,546 in2 -
C” 6,60 mm 0,2598 in
(Toyo Engineering Corporation, 1976)

Data Operasi Aktual


 tin = 31,2 ⁰C = 88,16 ⁰F
 tout = 34,5 ⁰C = 94,1 ⁰F
118

 t2 – t1 = 3,3 ⁰C = 5,94 ⁰F
 tavg = 32,85 ⁰C = 91,13 ⁰F
 w = 1.495.000 kg/hr = 3.295.911,385 lb/hr
1. Menghitung Neraca Panas (Heat Balance)
a. Pada Shell
Diketahui:
W = 12.267 kg/hr = 27.044,11 lb/hr
ƛ = 468 Btu/lb ………………………………………..…(fig.12,
Kern)
Karena terjadi perubahan fase, maka digunakan kalor laten dengan
menggunakan persamaan :
Q1 = W x ƛ ……..……………….…………………….…..(Kern, 1983)
= 27.044,11 lb/hr x 468 Btu/lb
= 12.656.643,64 Btu/hr
b. Pada Tube
Diketahui :
w = 1.495.000 kg/hr = 3.295.911,385 lb/hr
t1 = 31,2 ⁰C = 88,16 ⁰F
t2 = 34,5 ⁰C = 94,1 ⁰F
cp = 0,99 Btu/lb ⁰F ……………………………………….(fig.2,
Kern)
Maka,
Q2 = w cp (t2 – t1) ……..……………….…………...(Kern, 1983)
= 3.295.911,385 lb/hr x 0,99 Btu/lb ⁰F x (94,1 – 88,16 ) ⁰F
= 19.381.936,49 Btu/hr
2. Menghitung LMTD dan ∆t
Hot Fluid Cold Fluid
Differences
(°F) (°F)
T₁ 120,74 Higher Temp. t₂ 94,1 26,6
T₂ 95,9 Lower Temp. t₁ 88,2 7,7
24,84 Differences 6 19
(T1 – T2) (t2 – t1)
119

∆ t 2−∆ t 1 ( 26,6−7,7 ) ° F
LMTD = = = 15,29 °F …… (Kern, 1983)
ln ¿ ¿ ¿ ln(¿ 26,6 /7,7)¿

T −T 2
R =1 = 4 ……….……………….…………...(Kern, 1983)
t 2−t 1

t −t
S =2 1 = 0,18 ……………..………..…….......( Kern, 1983)
T 1−t 1

Berdasarkan data desain Ammonia Condenser 4U-EA-404-D yang


merupakan HE dengan 1 Shell Pass, 1 Tube Pass, maka didapatkan :
Faktor koreksi (Ft) = 0,87 ..……………………………….(fig.18, Kern)
CMTD (∆t) = LMTD x Ft ………….……………… (Kern,
1983)
= 15,29 ˚F x 0,87
= 13,3 ˚F
3. Menghitung Temperatur Rata-Rata

Tav = T 1 +T 2 = 121˚ F+ 96˚ F = 108 ˚F ………(Kern,


2
1983) 2

tav = t 1 +t 2 = 88,16 ˚ F +94,1 ˚ F = 91,13 ˚F …......(Kern, 1983)


2 2
4. Menghitung Luas Penampang (Flow Area)
a. Flow Area pada Shell Side
''
= ID × C × B
as ( Kern, 1983)
……………………………………………..…..............
144 × P T
Dimana,
ID = 59,05 in
B = 35,42 in
PT = 1,2598 in
C” = 0,2598 in
Maka :
''
as = ID × C × B
144 × P T

=
59,05∈×0,2598∈×35,42∈ ¿ ¿
2
144∈¿
× 1,2598∈¿ ¿¿
ft 2
120

,
= 2,9962 ft2

b. Flow Area pada Tube Side


'
at=N t ×a t ………………………………………………………….……... ( Kern, 1983)
144 ×n
Dimana,
Nt = 1.744
n =1
a’t = 0,546 in2
Maka,
N t × a' t
at =
144 ∈¿ 2
×n ¿
ft 2

= 0,546∈¿2
1.744 × ¿
144∈¿2
×1 ¿
ft 2
= 6,6126 ft2
5. Menghitung Kecepatan Massa (Mass Velocity)
a. Kecepatan massa pada shell side
Diketahui :
Ws = 27.044,11 lb/hr
as = 2,9962 ft2
Maka :
Ws
Gs = ……………………………………………………………... (Kern, 1983)
as

27.044,11  lb/hr  
= = 9.026,1102 lb/hr ft2
2,9962   ft² 
Ws 27.044,11 lb/hr
Loading, G” = =
L Nt 2 /3
23,616 ft x 1.744 2/3
= 12,0682 lb/hr lin ft
b. Kecepatan Massa pada Tube Side
Diketahui :
Wt = 3.295.911,385 lb/hr
at = 6,6126 ft2
121

Maka :
Wt
Gt = ……………………………….…………………………….. (Kern, 1983)
at

= 3.295.911,385  lb/hr  
6,61267  ft² 

= 498.423,9417 lb/hr ft2

6. Menghitung Re (Reynold Number)


a. Pada Shell Side (Res)
Diketahui :
Tav = 108,32 °F
µ = 0,011 cP = 0,0266 lb/hr ft …..………………….(fig.15,
Kern)
Gs = 9.026,1102 lb/hr ft2
PT = 0,1049 ft
OD = 0,0833 ft
( π . OD2 )
De =
[
4 Pt 2−
4 ]
π . OD  
(3,14 x (0,0833 ft )2)
= [
4 (0,1049 ft ) −2
4 ]
3,14 x 0,0833  ft  

= 0,0851 ft
Maka :
d ×G s
Res =e ……………………………………………………..... (Kern, 1983)
μ
0,0851 ft × 9.026,1102 lb / hr . ft ²
=
0,0266 lb /ft . hr

= 28.867,71
b. Pada Tube Side (Ret)
Diketahui :
tav = 91,13 °F
µ = 0,81 cP = 1,9602 lb/ft hr
D = 0,0694 ft
122

Gt = 498.423,94 lb/hr ft2


Maka :
Ret =D t ×G t …………………………………………….………...( Kern, 1983)
μ
0,0694 ft × 498.423,94 lb / hr . ft ²
= 1,9602lb / ft . hr
= 17.667,38

7. Menentukan Nilai Faktor Perpindahan Panas


a. Pada Shell Side
Diketahui :
Res = 27.693,62
Maka :
JH = 103 …………………………………………(fig.28, Kern)
b. Pada Tube Side
Diketahui :
Ret = 17.667.38
L = 23,616 ft
D = 0,06948 ft
L/D = 339,88
Maka :
JH = 56 …………………………………………..(fig.24, Kern)

8. Menghitung Koefisien Perpindahan Panas (Prandtl Number)


a. Pada Shell Side
Diketahui :
Tav = 108,32 °F
c = 0,53 Btu/lb.°F ………………………………..……....(fig.3,
Kern)
k = 0,01532 Btu/hr ft2(.°F/ft) ……..…………………...(table 5,
Kern)
μ = 0,02662 lb/hr ft ………………………………….…(fig.15, Kern)
Maka : 1
0,53 Btu /lb . ° F x 0,02662lb/ ft . hr
(c μ/k ) 1/ 3
= ( 0,0152 Btu /(hr )(ft 2 )(° F / ft) ) 3
(Kern, 1983)
……….
123

= 0,9728
b. Pada Tube Side
Diketahui :
tav = 91,13 °F
c = 0,99 Btu/lb.°F…………………………….....………(fig.3,
Kern)
kc = 0,3591 Btu/hr ft2(.°F/ft) ……………………..……(table 4, Kern)
μc = 1,9602 lb/ hr ft ………………………………….…(fig.14, Kern)
Maka : 1
0,99 Btu /lb . ° F x 1,9602lb/ ft . hr
(c μ/k ) 1/ 3
= ( 0,3591 Btu /(hr )(ft 2 )(° F / ft ) ) 3
…………. (Kern, 1983)

= 1,7548
9. Menghitung Koefisien Perpindahan Panas (ho dan hi)
a. Pada Shell Side
Diketahui :
G” = 12,0682 lb/hr lin ft
Kf = 0,01532 Btu/hr ft2 (°F/ft) …………………………(table 5, Kern)
Sf = 0,61 …………………………………………..……(table 6,
Kern)
µf = 0,011 cP…………………………………………….(fig.14, Kern)
Maka :
ho = 301 Btu/(hr)(ft2)(°F) ……………………(fig. 12.9, Kern)
b. Pada Tube Side
Diketahui :
jH = 56
k = 0,3591 Btu/hr ft2 (°F/ft) …..........................(table 4, Kern)
D = 0,0694 ft
k/D = 5,1682 Btu/(hr)(ft2)(°F)
(c μ/k )1/ 3 = 1,7548
( μ/ μ w)0,14 = ø t =1
Maka :
1/ 3
k c .μ
jH .
D ( )
.
k
Φt
124

hi = ……………………………….…… ( Kern, 1983)

= 56 x 5,1682 Btu/(hr)(ft2)(°F) x 1,7548 x 1


= 507,89 Btu/(hr)(ft2)(°F)
10. Menentukan Nilai hio
Diketahui :
hi = 507,89 Btu/(hr)(ft2)(°F)
ID = 59,05 in
OD tube = 1 in
Maka :
hio = hi × ID ………………………………………………………….………..( Kern, 1983)
OD
= 507,89 Btu /(hr )(ft 2)(° F )× 59,05∈ ¿ ¿
1∈¿¿
2
= 29.993,46 Btu/(hr)(ft )(°F)
11. Menentukan Clean Overall Coeficient (Uc)
Diketahui :
hio = 29.993,46 Btu/(hr)(ft2)(°F)
ho = 301 Btu/(hr)(ft2)(°F)
Maka :
hio   × ho
Uc =
hio  + ho

29.993,46   Btu/(hr)(ft 2 )(°F)   ×301   Btu/(hr)(ft 2)(°F)   


= 29.993,46   Btu/(hr)(ft 2)(°F)  +301  Btu/(hr)(ft 2 )(°F)   

= 298,01 Btu/(hr)(ft2)(°F)
12. Menghitung Design Overall Coeficient (Ud)
Diketahui :
a” = 0,2618 ft2/lin ft …………………...........................(table 10,
Kern)
Nt = 1.744
L = 23,616 ft
Q = 12.748.034,08 Btu/hr
CMTD = 13,3 ° F
Maka :
125

A = a” x Nt x L ……………………………………………………….………..( Kern, 1983)


= 0,2618 ft2/lin ft x 1.744 x 23,616 ft
= 10.782,57 ft2

Q
Ud = ………………………………………………….……….. ( Kern, 1983)
A x CMTD

12.656.643,64 Btu /hr


=
10.782,57 ft 2 x 13,3° F

= 88,2343 Btu/(hr)(ft2)(°F)
13. Fouling Factor (Rd)
Diketahui :
Uc = 298,01 Btu/(hr)(ft2)(°F)
Ud = 88,23 Btu/(hr)(ft2)(°F)
Maka :
U c −U D
Rd = ……………………………………………………….……….. ( Kern, 1983)
Uc× UD

298,01 Btu/( hr)( ft 2)(° F)−88,23 Btu /(hr )(ft 2)(° F)


=
298,01 Btu /(hr)(ft 2)(° F)x 88,23 Btu /(hr )(ft 2)(° F )

= 0,007977 hr ft2 °F / Btu


14. Menghitung Pressure Drop
a. Pada Shell side
1. Menentukan f factor
Res = 28.867,71
f = 0,0023 ft2/in2…………………………………....(Fig.29, Kern)
s = 0,61 ………………..……….....………………..(table.6, Kern)
Ds = 4,92 ft

2. Menghitung No. of Crosses


Diketahui :
L = 283,38 ft
B = 35,42 in
Maka :
126

N + 1 = 12L/B ……………….………………………..(Kern, 1983)


= 12 x 283,38 ft/35,42 in
= 96

3. Menghitung Pressure Drop di Shell


Diketahui :
f = 0,0023 ft2/in2
Gs = 9.026.11 lb/hr.ft²
Ds = 4,92 ft
De = 0,08514 ft
s = 0,61
Øs = 1
Maka :
f G 2s D s ( N +1)
ΔPs = 10 ……..……………….………..(Kern, 1983)
5,22 x 10 De s ∅s
0,0023 ft 2 /¿2 x( 9.026,11lb/hr . ft ²)2 x 4,92 ft x 96
=
5,22 x 10 10 x 0,08514 ft x 0,61 x 1

= 0,0326 Psi

b. Pada Tube side


1. Menentukan f factor
Ret = 17.667,38
f = 0,00026 ft2/in2…………….……………………...(Fig.26, Kern)
s =1 ………………………………...……..…..…(Table.6, Kern)
Dt = 0,06948 ft

2. Menghitung ΔPt
Diketahui :
f = 0,00026 ft2/in2
Gt = 498.423,94 lb/hr.ft²
Dt = 0,06948 ft
L = 23,62 ft
n = 1 pass
127

Øs = 1
Maka:
f G 2t ln
ΔPt = ……….………………………..(Kern, 1983)
5,22 x 10 10 D t s ∅ s
0,00026 ft 2 /¿2 x( 498.423,94 lb /hr . ft ²)2 x 23,62 x 1
=
5,22 x 1010 x 0,06948 ft x 0,61 x 1

= 0,4206 Psi
3. Menghitung ΔPr
Diketahui :
n = 1 pass
s =1
Gt = 498.424,94 lb/hr.ft²
V2 = 1 psi …………………………………………..(Fig.27, Kern)
2g'

Maka :
4n V2
ΔPr = x ……………………………...…………..(Kern, 1983)
s 2g'

= 4 (1)
x1 psi
1
= 4 psi
4. Menghitung ΔPT
ΔPT = ΔPt + ΔPr ………………………………………...(Kern, 1983)
= 0,4206 Psi + 4 Psi
= 4,4206 Psi