HASIL PENGUJIAN ( μA )
ARUS BOCOR
NO BAY MERK / TYPE ARRESTER TANGGAL UJI PHASA Leakage Corrective
(Ref.Pabrikan / μA)
Current ( IR Value ( IR corr Total Current
[TH] ) ) ( Itotal )
1 2 3 4 5 6 7 8 9
BAY TRAFO 1 60 MVA SIEMENS / 3EP2 150-2PH31-2CA1 16 APRIL 2018 91 R 4 6 605
1 BAY TRAFO 1 60 MVA SIEMENS / 3EP2 150-2PH31-2CA1 16 APRIL 2018 91 S 4 7 598
BAY TRAFO 1 60 MVA SIEMENS / 3EP2 150-3PH42-2CA1 16 APRIL 2018 91 T 5 10 566
Pht 150 KV GANDA MEKAR 1 TRIDELTA / SB150/20.4-1 16 APRIL 2018 150 R 9 15 921
2 Pht 150 KV GANDA MEKAR 1 TRIDELTA / SB150/20.4-1 16 APRIL 2018 150 S 7 12 983
Pht 150 KV GANDA MEKAR 1 TRIDELTA / SB150/20.4-1 16 APRIL 2018 150 T 11 18 900
PHT 150 KV GANDA MEKAR 2 TRIDELTA / SB150/20.4-1 16 APRIL 2018 150 R 12 20 890
3 PHT 150 KV GANDA MEKAR 2 TRIDELTA / SB150/20.4-1 16 APRIL 2018 150 S 9 14 948
KETERANG TEGANGAN
% SUHU ( ⁰C )
AN UJI ( KV )
10 = (8/5)*100 11 12 13
6.59340659340659 Good 150 32
7.69230769230769 Good 150 33
10.989010989011 Good 150 33
10 Good 150 34
8 Good 150 34
12 Good 150 33
4 BAY 150 kV PWKTA MITSUBISHI/SV-CA 01 FEBRUARI 2021 100 S 170 34 77 834 77 Weakened 148 31
MITSUBISHI/SV-CA 01 FEBRUARI 2021 100 T 170 52 118 838 118 DAMAGE 148 31
5 BAY 150 kV CKPAY EMP/MCA 2-27 01 FEBRUARI 2021 130 S 170 14 32 526 24.6153846154 Good 149 31
EMP/MCA 2-27 01 FEBRUARI 2021 130 T 170 11 25 369 19.2307692308 Good 149 31
HAL 1/2
ABB/XLIM P144/H17 01 FEBRUARI 2021 167 R 170 27 61 877 36.5269461078 Good 148 31
6 BAY 150 kV PDLRU#1 ABB/XLIM P144/H17 01 FEBRUARI 2021 167 S 170 22 50 858 29.9401197605 Good 148 31
ABB/XLIM P144/H17 01 FEBRUARI 2021 167 T 170 28 64 807 38.3233532934 Good 148 31
ABB/XLIM P144/H17 01 FEBRUARI 2021 167 R 170 47 109 792 65.2694610778 Weakened 148 31
7 BAY 150 kV PDLRU#2 ABB/XLIM P144/H17 01 FEBRUARI 2021 167 S 170 20 46 729 27.5449101796 Good 148 31
ABB/XLIM P144/H17 01 FEBRUARI 2021 167 T 170 28 63 923 37.7245508982 Good 148 31
8 BAY TRAFO#5 150/20 kV SIEMENS/3EL2 144 01 FEBRUARI 2021 130 S 170 16 37 676 28.4615384615 Good 149 31
sisi 150 Kv
SIEMENS/3E P2 150 01 FEBRUARI 2021 130 R 170 22 51 435 39.2307692308 Good 149 31
BAY IBT#3 150/70 kV SIEMENS/3E P2 150 01 FEBRUARI 2021 130 S 170 14 31 391 23.8461538462 Good 149 31
9
sisi 150 kV
SIEMENS/3E P2 150 01 FEBRUARI 2021 130 T 170 18 42 401 32.3076923077 Good 149 31
C-PROBE
ASEA/XBC75 01 FEBRUARI 2021 130 R 72 149 31
BAD SIGNAL
BAY IBT#3 150/70 kV sisi 70
10 C-PROBE
kV ASEA/XBC75 01 FEBRUARI 2021 130 S 72 149 31
BAD SIGNAL
C-PROBE
ASEA/XBC75 01 FEBRUARI 2021 130 T 72 149 31
SIEMENS/3EL1-060- BAD SIGNAL
01 FEBRUARI 2021 130 R 60 25 45 436 34.6153846154 Good 70 31
1PK21-4XA1
SIEMENS/3EL1-060-
11 BAY 70 kV PWKTA#1 01 FEBRUARI 2021 130 S 60 18 33 432 25.3846153846 Good 70 31
1PK21-4XA1
SIEMENS/3EL1-060-
01 FEBRUARI 2021 130 T 60 19 34 439 26.1538461538 Good 70 31
1PK21-4XA1
COOPER/VAR1 STAR 01 FEBRUARI 2021 130 R 72 46 43 924 33.0769230769 Good 71 31
12 BAY 70 kV PWKTA#2 COOPER/VAR1 STAR 01 FEBRUARI 2021 130 S 72 34 28 923 21.5384615385 Good 71 31
REKAPITULASI
HASIL PENGUKURAN ARUS BOCOR PADA LIGHTNING ARRESTER
ALAT UJI : DOBLE LCM 500
GITET CIRATA
ARUS BOCOR HASIL PENGUJIAN ( μA ) Sys.
MERK / SUHU
NO BAY TYPE ARRESTER TANGGAL UJI (Ref.Pabrikan PHASA Leakage Current Corrective Value Total Current ( % KETERANGAN Volt (°C)
/ μA) ( IR [TH] ) ( IR corr ) Itotal ) (kV)
13 =
1 2 3 4 5 6 10 11 12 (11/5)*100 14 8 9
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 R 225 426 1554 202.85714 DAMAGE 483 31
1 BAY 500 kV PHT CBATU#1 ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 S 79 86 1255 40.952381 Good 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 T 117 221 1343 105.2381 DAMAGE 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 R 124 234 1262 111.42857 DAMAGE 483 31
2 BAY 500 kV PHT CBATU#2 ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 S 90 169 1189 80.47619 Monitor 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 R 124 280 1317 133.33333 DAMAGE 483 31
3 BAY 500 kV PHT SGLNG#1 ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 S 85 158 1200 75.238095 Weakened 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 R 287 524 1582 249.52381 DAMAGE 483 31
4 BAY 500 kV PHT SGLNG#2 ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 S 229 427 1620 203.33333 DAMAGE 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 T 110 204 1708 97.142857 Monitor 483 31
HAL 1/3
ABB/
EXLIM T444-BV 550M 01 FEBRUARI 2021 210 R 75 137 1721 65.238095 Weakened 483 31
6 BAY 500 kV MTR#2 ABB/ 01 FEBRUARI 2021 210 S 20 37 1542 17.619048 Good 483 31
EXLIM T444-BV 550M
ABB/
EXLIM T444-BV 550M 01 FEBRUARI 2021 210 T 42 76 1655 36.190476 Good 483 31
ABB/
EXLIM T444-BV 550M 01 FEBRUARI 2021 210 R 61 112 1606 53.333333 Weakened 483 31
ABB/
7 BAY 500 kV MTR#3 01 FEBRUARI 2021 210 S 19 34 1473 16.190476 Good 483 31
EXLIM T444-BV 550M
ABB/
01 FEBRUARI 2021 210 T 65 93 1720 44.285714 Good 483 31
EXLIM T444-BV 550M
ABB/
01 FEBRUARI 2021 210 R 85 138 1661 65.714286 Weakened 483 31
EXLIM T444-BV 550M
8 BAY 500 kV MTR#4 ABB/ 01 FEBRUARI 2021 210 S 32 58 1560 27.619048 Good 483 31
EXLIM T444-BV 550M
ABB/ 01 FEBRUARI 2021 210 T 2 4 142 1.9047619 Good 483 31
EXLIM T444-BV 550M
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 R 371 578 2762 275.2381 DAMAGE 483 31
BAY IBT#1 500/150 kV
9 sisi 500 kV ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 S 96 175 1207 83.333333 Monitor 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 T 104 193 1281 91.904762 Monitor 483 31
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 R 104 190 1168 90.47619 Monitor 483 31
BAY IBT#2 500/150 kV
10 ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 S 91 167 1284 79.52381 Weakened 483 31
sisi 500 kV
ALSTHOM/PSB444Z 01 FEBRUARI 2021 210 T 98 179 1175 85.238095 Monitor 483 31
OHIO BRASS/ 01 FEBRUARI 2021 210 R 94 158 1240 75.238095 Weakened 483 31
BAY 500 kV MTR#1 OHIO BRASS/ 01 FEBRUARI 2021 210 S 61 114 1219 54.285714 Weakened 483 31
12
sisi PH
OHIO BRASS/ 01 FEBRUARI 2021 210 T 84 142 1272 67.619048 Weakened 483 31
SIEMENS/
3P6-444-3PF43-2XA1-Z 01 FEBRUARI 2021 210 R 54 101 1315 48.095238 Good 483 31
ABB/
EXLIM T444-BV 550M 01 FEBRUARI 2021 210 R 75 138 1550 65.714286 Weakened 483 31
SIEMENS/3EL1 072-
02 FEBRUARI 2021 130 R 60 20 24 433 18.46153846 Good 67 30
1PK21-4XA1-Z
SIEMENS/3EL1 072-
1PK21-4XA1-Z 02 FEBRUARI 2021 130 T 60 13 15 400 11.53846154 Good 67 30
SIEMENS/3EL1 072-
1PK21-4XA1-Z 02 FEBRUARI 2021 130 R 72 16 34 461 26.15384615 Good 67 30
SIEMENS/3EL1 072-
02 FEBRUARI 2021 130 T 72 9 19 465 14.61538462 Good 67 30
1PK21-4XA1-Z
REKAPITULASI
HASIL PENGUKURAN ARUS BOCOR PADA LIGHTNING ARRESTER
ALAT UJI : DOBLE LCM 500
GI INDORAMA
ARUS HASIL PENGUJIAN ( μA )
Sys.
NO BAY MERK / TANGGAL UJI BOCOR PHASA Leakage Current ( Corrective Value Total Current % KETERANGAN Volt SUHU
TYPE ARRESTER (Ref.Pabrika (°C)
IR [TH] ) ( IR corr ) ( Itotal ) (kV)
n / μA)
13 =
1 2 3 4 5 6 10 11 12 14 8 9
(11/5)*100
SIEMENS/
21 APRIL 2022 130 R 30 58 376 44.615385 Good 69 32
3EL1-060-1PK21-4XA1
SIEMENS/
2 BAY 70 kV PWKTA#2 21 APRIL 2022 130 S 17 33 400 25.384615 Good 69 32
3EL1-060-1PK21-4XA1
SIEMENS/
3EL1-060-1PK21-4XA1 21 APRIL 2022 130 T 21 41 410 31.538462 Good 69 32
SIEMENS/
3EL1-060-1PK21-4XA1 21 APRIL 2022 150 R 21 22 541 14.666667 Good 69 33
5 BAY 70 kV KONSUMEN#1 EMP/IMB 75 21 APRIL 2022 130 S 54 100 318 76.923077 Weakened 69 30
REKAPITULASI
HASIL PENGUKURAN ARUS BOCOR PADA LIGHTNING ARRESTER
ALAT UJI : DOBLE LCM 500
GI INDACI & GI CIGANEA
HASIL PENGUJIAN ( μA )
ARUS Sys.
NO BAY MERK / TANGGAL UJI BOCOR PHASA Leakage Current ( Corrective Value Total Current % KETERANGAN Volt SUHU
TYPE ARRESTER (Ref.Pabrika (°C)
IR [TH] ) ( IR corr ) ( Itotal ) (kV)
n / μA)
13 =
1 2 3 4 5 6 10 11 12 14 8 9
(11/5)*100
SIEMENS/3EL1 21 APRIL 2022 130 R 27 25 399 19.230769 Good 69 30
BAY 70 kV IDRMA
1 GI INDCI SIEMENS/3EL1 21 APRIL 2022 130 S 19 19 402 14.615385 Good 69 30
( MISAN )