PERHITUNGAN UTILITAS

Perhitungan Parkir Perhitungan Air Bersih

Luas Total = 10.500 m2 Luas Total = 10.500 m2


= 10.500 m2 40 m2
60 m2 = 262 SRP
= 175 SRP
Mobil = 175 SRP Motor = 262 SRP
KEBUTUHAN AIR BERSIH HOTEL Luas tanah: 10.500 m2
KDB : 70%
Perhitungan Tangki Pemadam Kebakaran 1
* kebutuhan air hotel : 250 liter/orang/hari
KEBUTUHAN MAKSIMUM AIR BERSIH PER HARI (Qd) Luas Bangunan lantai dasar :
- Kebutuhan Harian (Q) = n x kebutuhan rata-rata perhari 0.7 x 10.500 m2 = 7.350 m2
VR = Volume tangki air minum (m3/hari)
Q= 138500 liter
Qa = Jumlah kebutuhan per hari (m3 /hari)
Q= 138,5 m3 Luas Hotel Total :
Q. = Kapasitas pipa dinas (m3/jam)
- Keb. Max (Qd) = Kebutuhan Harian x 120% 7.350 m2 x 12 = 88.200 m2
T = Rata-rata pemakaian air per hari Gam/hari)
VF = Cadangan air untuk pemadam kebakaran Qd = 166,2 m3 Building Population Hotel :
2 KEBUTUHAN RATA-RATA PER HARI (Qh) T= 10 jam - Jumlah Kamar : 205 unit
VOLUME TANGKI BAWAH UNTUK PEMADAM KEBAKARAN (Vf) Qh = Qd / T - Jumlah Tamu : 410 orang
Qh = 16,62 m3/jam - Jumlah Karyawan : 144 orang
3 KEBUTUHAN AIR PADA JAM PUNCAK (Qh max) C1 = 2
- Total : 554 orang
Vf = 0,25 x Vr Qh max = Qhm = C1 x Qh
Qhm = 33,24 m3/jam
Qhm = 0,554 m3/menit
4 KEBUTUHAN AIR PADA MENIT PUNCAK (Qm max)
Vf = 13,85 m3 Qm max = Qmm = C2 x (Qh/60) C2 = 4
Qmm = 1,108 m3/menit
5 KAPASITAS PIPA DINAS (Qs)
Qs = 2/3 x Qh (dalam m3/jam)
Vr total = Vr + Vf Qs = 11,08 m3/jam
6 VOLUME TANGKI BAWAH (Vr) T= 10 jam
Vr = Qd – (Qs x T)
Vr = 55,4 m3
Vr total = 69,25 m3 7 VOLUME TANGKI ATAS (Ve) Tp= 60 dan Tpu = 20
Ve = (Qm max – Qh max) Tp – (Qh maks x Tpu)
Ve = 22,16 m3

NAMA : ALVIAN BINTANG PRADANA NIM : 5200911295


PERHITUNGAN UTILITAS
Perhitungan Septictank Perhitungan Air Hujan
Jumlah Pemakai Kloset = 554 orang
Standar kebutuhan air per orang untuk closet per hari = 25 liter/ orang
Lama Pembusukan = 3 hari pembusukan

VOLUME/ KAPASITAS SEPTIC TANK


1 Volume Septictank
Volume = 554 org x 25 ltr x 3 hari
= 41550 liter
= 41,55 m3
Asumsi Tinggi Septictank
Tinggi =3 m
T. Permukaan Air = 2/3 x 3m = 2 m
T. Ruang Udara = 3m – 2m = 1 m Diameter Luasan Atap Volume Curah hujan sepanjang tahun
(Inci) (M2) (Liter/Menit) in Kota Surakarta dengan
2 Luas Alas Septictank rata-rata curah hujan 300
Luas = Volume : T. Permukaan Air 3 s.d.-180 255 milimeter.
= 41,55 m3 x 2m 4 385 547
Luas = 20,775 m2 Luas atap Hotel
5 698 990 Luasan atapnya adalah :
3 Panjang dan Lebar Septictank
L = 32 x 32 + 16 x 16
Panjang = 10 m 6 1135 1610 L = 1.024 + 256
Lebar = 2,0775 m L = 1280 cm²
8 2445 3470

Septictank Luas Atap = 1.280 m²


Curah Hujan rata-rata di Surakarta = 300 mm/m²/jam =5 ltr/mnt.
Jadi 1.280 m² x 5 liter/menit = 6400 liter/menit.
Luas atap 1.280 m² menggunakan diameter 6” dengan kapasitas +/- 1.610 liter/menit.
Curah hujan: 6400 liter/menit, maka air hujan akan mengalir ke bawah dalam waktu (memakai pipa 6”)
= 6.400 : 1.610 = 3,97 atau 4 menit.
Untuk mempercepat pembuangan air diperlukan pipa 6” sebanyak 4 buah yang tersebar letaknya sehingga air di atas atap
pada saat tertentu akan terbuang keluar dalam waktu 1 menit.

Luas Atap = 12000 m2


Curah hujan : = 6400 liter/menit

Perhitungan = 6400
= 1610
=4 menit dg pipa ukuran 6" (1 buah)
=1 menit dg pipa ukuran 6" (4 buah)

NAMA : ALVIAN BINTANG PRADANA NIM : 5200911295


PERHITUNGAN UTILITAS
Perhitungan Air Untuk Fire Protection Perhitungan Jumlah Titik Lampu
Luas Bangunan Total = 88200 m2
Tinggi bangunan = 12 lantai
Luas per Lantai Bangunan = 7350 m2

1. Jumlah Pillar Hydrant = Luas per Lantai Bangunan


1000 m2/ titik
Jumlah Pilar Hydrant = 7350 m2
= 1000 m2/titik
= 7,35 ~ 7 Pilar
Vol. Air utk Pillar Hydrant = Jumlah hydrant x 1000 liter per menit x 30 menit
Vol. Air utk Pillar Hydrant =7 pilar x 1000 liter/menit x 30 menit
= 210000 liter
= 210 m3 1. Standar Room = 6 x 4 m2 2. Deluxe Room = 6 x 8 m2 3. Suite Room = 8 x 9 m2
Penerangan = 300 lux Penerangan = 300 lux Penerangan = 300 lux
- Air untuk Pillar Hydrant minimal 1000 liter/menit selama 30 menit
Dipasang lampu = LED 15 watt Dipasang lampu = LED 15 watt Dipasang lampu = LED 15 watt
- Radius jangkauan 30 meter per pilar (pemasangan tiap jarak 50-60 meter)
E = 300 lux E = 300 lux E = 300 lux
Luas per Lantai Bangunan
2. Jumlah Hydrant Box = A = 24 m2 A = 48 m2 A = 72 m2
600 m2/ titik Ø = 1500 lumen Ø = 1500 lumen Ø = 1500 lumen
Jumlah Hydrant Box/ lt. = 7350 m2 LLF = 0,7 LLF = 0,7 LLF = 0,7
= 600 m2/titik CU = 0,6 CU = 0,6 CU = 0,6
= 12,25 ~ 12 titik/ lantai n =1 buah/titik n =1 buah/titik n =1 buah/titik
Volume Air utk Hydrant Box = Jumlah hydrant x 400 liter per menit x 30 menit 7200 14400 21600
n= n= n=
Vol Air utk Hydrant Box = 12 titik x 400 liter/menit x 30 menit 630 630 630
= 144000 liter n = 11 buah/titik n = 23 buah/titik n = 34 buah/titik
= 144 m3
- Air utk Hydrant Box minimal 400 liter/menit selama 30 menit
- Radius jangkauan 20 meter per HB (pemasangan tiap jarak 35-38 meter) 4. Lobby = 159 m2 5. Gym (Amenities) = 6 x 8 m2
Penerangan = 300 lux Penerangan = 300 lux
Luas per Lantai Bangunan Dipasang lampu = LED 15 watt Dipasang lampu = LED 15 watt
3. Jumlah Spinkler =
10 s.d. 20 m2/ titik
E = 300 lux E = 300 lux
Jumlah Sprinkler/ lt. = 7350 m2
A = 24 m2 A = 45 m2
= 15 m2/titik Ø = 1500 lumen Ø = 1500 lumen
= 490 ~ 490 titik/ lantai LLF = 0,7 LLF = 0,7
Volume Air Sprinkler = Jumlah titik Sprinkler x 18 liter per menit x 30 menit CU = 0,6 CU = 0,6
Vol Air utk Sprinkler = 490 titik x 18 liter/menit x 30 menit n =1 buah/titik n =1 buah/titik
= 264600 liter 47700 13500
= 264,6 m3 n= n=
630 630
- Air utk tiap titik Sprinkler minimal 18 liter/menit selama 30 menit n = 76 buah/titik n = 21 buah/titik
- Radius jangkauan 3-4 meter per Sprinkler

NAMA : ALVIAN BINTANG PRADANA NIM : 5200911295


PERHITUNGAN UTILITAS
Perhitungan AC

Standar Room 6 x 4 x 3

L W H I E LxWxHxIxE Kebutuhan Jml AC PK

19,68 13,12 9,84 10 16 406.513 6.775 BTU 1 ¾

Deluxe Room 6 x 8 x 3

L W H I E LxWxHxIxE Kebutuhan Jml AC PK


(L x W x H x I x E) / 60 = kebutuhan BTU
L = Panjang Ruang (dalam feet) 19,68 26,24 9,84 10 17 863.839 14.397 BTU 2 ¾
W = Lebar Ruang (dalam feet)
I = Nilai 10 jika ruang berinsulasi (berada di lantai bawah,
atau berhimpit dengan ruang lain
Nilai 18 jika ruang tidak berinsulasi (di lantai atas). Suite Room 8 x 9 x 3
H = Tinggi Ruang (dalam feet)
E = Nilai 16 jika dinding terpanjang menghadap utara, L W H I E LxWxHxIxE Kebutuhan Jml AC PK
nilai 17 jika menghadap timur,
Nilai 18 jika menghadap selatan, dan nilai 20 jika
menghadap barat.
26,24 29,52 9,84 10 18 1.371.980 22.866 BTU 1 2½
1 Meter = 3,28 feet
BTU = British Thermal Unit
Lobby 16 x 13 x 3

Perhitungan Zero Run Off L W H I E LxWxHxIxE Kebutuhan Jml AC PK

Luas Atap = 1280 m2 = 128000 dm2


Curah hujan tahunan di Kota Surakarta = 2320 mm/tahun 52,48 42,64 9,84 18 18 7.134.296 118.905 BTU 5 2½
Koefiesien run off atap = 0,9

• Volume air hujan yang jatuh di area tersebut


Musholla 7 x 15 x 3
= 128000 dm2 x 23,2 dm x 0,9
= 2.672.640 liter/ tahun
L W H I E LxWxHxIxE Kebutuhan Jml AC PK
• Asumsi hanya 90% dari total air yang dapat di panen
= 2.672.640 liter/ tahun x 0,9
= 2.405.376 liter/ tahun 22,96 49,2 9,84 18 18 3.601.448 60.024 BTU 3 2½

NAMA : ALVIAN BINTANG PRADANA NIM : 5200911295


PERHITUNGAN UTILITAS
Perhitungan Lift
1. BUILDING POPULATION (SP) 2. pHC (Prosentase yang dihandel) 3. HANDLING CAPACITY (HC)
Jumlah kamar = 205 pHC = 10 - 12 % LIFT Hotel
Building population hotel = 410 orang HC = Jumlah total populasi x Phc
Jumlah Karyawan = 144 orang HC = 66,48
Jumlah Total Populasi = 554 orang

4. SPESIFIKASI LIFT 5. RT (ROUND TRIP) 6. CAR PASSENGER CAPACITY (P)


LIFT Hotel Lantai Hotel = 12 Lantai Hotel
HC = Jumlah total populasi x Phc Min Car Speed = 700 Fpm
HC = 66,48
RT Hotel
Round Trip =130 Seconds

7. KAPASITAS YANG AKAN DIANGKUT DALAM 1X 8. JUMLAH LIFT 9. INTERVAL


PENGANGKUTAN (h) LIFT Hotel I = RT / N
N = Hc I = 130 / 2
Hotel h = 300 x 23 h I = 65
130
h = 46 N = 1,445217391
N = 2 lift

NAMA : ALVIAN BINTANG PRADANA NIM : 5200911295