GANGGUAN EXTERNAL

CONTACT DAN LINK VIDEO


Bisa juga presentasi ini ditoton di : https://www.youtube.com/watch?v=6L-zcpjRRKA&t=318s
• EMAIL : adiputra_cv@yahoo.com
• Website : www.adiputra.co.id
• Facebook : Tekep Isolator
• Pemasangan tekep isolator lurus (A3CS):https://www.youtube.com/watch?v=IVK5aSmeQpE
• Pemasangan tekep isolator lurus polimer (A3CS): https://www.youtube.com/watch?v=aJOds09z3yc&t=58s
• Pemasangan tekep isolator lurus anti melorot (jika A3CS putus tidak melorot, tapi dapat mengakibatkan isolator
tumpu bengkok seperti menggunakan tie)/gardu 1 konsumen : https://www.youtube.com/watch?v=HCh2LE6ejRQ
• Pemasangan tekep isolator belokan (A3CS) : https://www.youtube.com/watch?v=yZEbmJ9WHqM
• Pemasangan tekep isolator lurus+extensi untuk mengantisipasi gangguan binatang dan pohon (A3C):
https://www.youtube.com/watch?v=exUyVLJlpm8&t=8s
• Pemasangan tekep isolator strain clamp+extention untuk mengantisipasi gangguan binatang dan pohon serta loss
contact (A3C): https://www.youtube.com/watch?v=Yy9NZiQszgo
• Pemasangan tekep isolator strain clamp untuk mengantisipasi gangguan binatang dan pohon serta loss contact
(A3CS)https://www.youtube.com/watch?v=VWifniuO9mk
• Pemasangan tekep isolator gardu untuk mengantisipasi gangguan binatang dan pohon serta loss contact :
https://www.youtube.com/watch?v=v-R7hWoAb1w
• Pemasangan tekep isolator jamperan dengan CCO untuk mengantisipasi gangguan binatang dan pohon serta loss
contact : https://www.youtube.com/watch?v=LJKHpHmTocg
• Pemasangan tekep isolator connector dg LLC untuk mengantisipasi gangguan binatang dan pohon serta loss contact
: https://www.youtube.com/watch?v=RshJcM8UjIc
• Pemasangan tekep isolator TREEGUARD untuk mengantisipasi gangguan binatang dan pohon (A3C):
https://www.youtube.com/watch?v=3HXmv5nP_pw
PROBLEMATIKA GANGGUAN TRAFO
POHON
MENYENTUH
A3CS

ISOLASI
TAMBAHAN
TETAPI DIIKAT
DENGAN
LOGAM
PENYEMPURNAAN JTM BELUM TUNTAS
PENYEMPURNAAN JTM BELUM TUNTAS
Penambahan EPI
LLC TERBUKA Mengurangi
Air masuk ke dalam isolasi creepage distance
kabel jamper dari LLC ke
FCO
Terjadi lost-contact di kabel
schoon incoming FCO
Terjadi lost-contact di kabel
schoon arrester dan trafo,
krn schoon tanpa heatsring

JADI SEMAKIN SEMPURNA


DIPASANG TEKEP ISOLATOR:
YSL-150-AP (UJUNG)
YS-CONNECTOR-70-240-AP
YS-STRAINCLAMP-70-240-AP
YS-FCO-70-240-AP
YS-BUS-SEC-70-240-AP
YS-BUS-ARR-70-240-AP
Cover Cover
arrester TERBUKA
Cover arrester
terbuka, terbuka,
berlubang
karena karena
karena terbakar,
miring, TERANGKAT,
mungkin
sehingga sehingga
diakibatkan oleh
bagian yang bagian yang
partial discharge,
bertegangan bertegangan
atau lost contact
jadi terbuka jadi terbuka
Perlu diteliti lebih
dan korosi dan korosi
lanjut
PROBLEMATIKA SUTM
ADA COVER
TAPI
TERBUKA

COVER
BAWAH
LEPAS
TIDAK SESUAI
SPLN
D5.006.2013
PROBLEMATIKAN SUTM
PEMANFAATAN TREE GUARD UNTUK MENGAMANKAN JTM DARI GEDUNG, KURANG BAIK
UNTUK JARINGAN, KARENA BERAT SEHINGGA ANDONGAN PENGHANTAR MENJADI BESAR.
DAN TIDAK SELURUH PENGHANTAR TERLINDUNGI. SEBAIKNYA MENGGUNAKAN TEKEP
ISOLATOR EXTENTION YANG LEBIH RINGAN, MURAH, DAN DAPAT MENGISOLASI DALAM 1
GAWANG.
PEMASANGAN ARRESTER PEMASANGAN ARRESTER
SEPERTI INI TIDAK SESUAI SESUAI SPLN D5.006 : 2013,
STANDAR KONSTRUKSI SPLN SEMAKIN DEKAT ARRESTER
D5.006 : 2013, HAL INI AKAN DENGAN KOMPONEN
MENURUNKAN KINERJA YANG DILINDUNGI SEMAKIN
ARRESTER BAIK, JADI SEMAKIN
SEMPURNA DIPASANG
TEKEP ISOLATOR BUSHING,
SEHINGGA AMAN DARI
GANGGUAN BIANATANG
A3CS TIDAK DIKUPAS
PADA POSISI KLEM
PISTOL/STRAIN CLAMP,
SEHINGGA MENIMBULKAN
DISCHARGE AKIBAT
TERJADINYA KAPASITANSI
ANTARA PENGHANTAR
DENGAN KLEM PISTOL
YANG TERBUAT DARI
ALUMINIUM
PERLAKUAN TERHADAP ISOLATOR YANG
TIDAK BERSAHABAT, SEHINGGA ISOLATOR
KOTOR, CACAT DAN PECAH
PENGGUNAAN COVER
DENGAN MODEL PENGIKAT
PENGGUNAAN COVER BEGEL INI SERING KALI TIDAK
MEREK TERTENTU DG DISAIN
SESUAI UKURANNYA
YANG TIDAK KOKOH,
SEHINGGA
DENGAN ISOLATOR,
KANCINGANNYA TERBUKA SEHINGGA
PEMASANGANNYA
LONGGAR DAN RAWAN
LEPAS.
UKURAN BEGEL TIDAK
SESUAI DENGAN
DIAMETER LEHER
ISOLATOR, SEHINGGA
HANYA BISA DIPASANG
1 BAUT, HAL INI SANGAT
RAWAN PENGHANTAR
LEPAS DARI ISOLATOR
TUMPU
DIAMETER LINGKAR DIAMETER LINGKAR
PLP/PREFORMED TIE PLP/PREFORMED TIE TIDAK
TIDAK SESUAI SESUAI DENGAN DIAMETER
DENGAN DIAMETER LEHER ISOLATOR TUMPU,
LEHER ISOLATOR SEHINGGA IKATAN
TUMPU, SEHINGGA LONGGAR
IKATAN LONGGAR

DISAIN PLP
TIDAK COCOK
UNTUK
KONSTRUKSI
TM2 DENGAN
TIANG
KECIL/BESI,
DAN
OVERLENGTH
STOOT,
SEHINGGA
IKATANNYA
LEPAS
PLP LEPAS DR ISOLATOR TUMPU
PLP LEPAS
 PENGGUNAAN ALUMINIUM BENDING WIRE/PLP/PREFORMED TIE
MENIMBULKAN KERUSAKAN PADA ISOLATOR DAN TRAVERSE,
KARENA TERJADINYA PEMUAIAN PENGHANTAR YANG TIDAK
SERAGAM ANTARA GAWANG SATU DENGAN GAWANG YANG
LAINNYA. SEBAIKNYA GUNAKAN TEKEP ISOLATOR, SEHINGGA
PENGHANTAR BEBAS BERGERAK, KE KANAN DAN KE KIRI PADA SAAT
TERJADI PEMUAIAN PADA SIANG HARI DAN PENGKERUTAN PADA
MALAM HARI. DENGAN DEMIKIAN ISOLATOR TUMPU TIDAK
MENGALAMI BEBAN TARIK, HANYA MENAHAN BEBAN TUMPU
SIPENJOL LEPAS
DAMPAK YANG DITIMBULKAN SEBELUM
PENGGUNAAN TEKEP ISOLATOR THD A3CS
Hasil Inspeksi P.Tangeb di Tibubeneng Partial Discharger (Loss Kontak)
Foto kiriman dari Ryn Mengwi tgl.: 10 Juni 2012
Hasil Inspeksi P.Tangeb di Tibubeneng Partial Discharger (Loss Kontak)
Foto kiriman dari Ryn Mengwi tgl.: 10 Juni 2012
Hasil Inspeksi JTM di Br Gumicik Ketewel tgl.: 21 Agustus 2019
Pukul : 05.30 WITA
UPAYA YG TELAH DILAKUKAN
UPAYA YG TELAH DILAKUKAN
UPAYA YG TELAH DILAKUKAN

DISCHARD MERUSAK KABEL PASCA


PEMASANGAN PREFORMAERD TIE
A3CS tidak dikupas
Konstruksi tak pad klem pistol
sesuai SPLN
D5.006.2013

PAREPARE-SULSEL
DAMPAK RUGI ENERGI
DAMPAK RUGI ENERGI
DAMPAK YANG DITIMBULKAN TANPA TEKEP ISOLATOR
KEKHUSUSAN A3CS
 BERISOLASI BANCI JENIS POLYETHYLENE
 PENGHANTAR TANPA FASELIN

 ACESSORIES MENYENTUH ISOLASI MESTI SEJENIS/BERBAHAN


BAKU PLASTIK, AGAR ISOLASI TIDAK CACAT.
 TIDAK BOLEH ADA BAGIAN PENGHANTAR YANG TERBUKA, DPT
MENGAKIBATKAN KOROSI, FLASH OVER, MEMUTUSKAN
PENGHANTAR.
 BAGIAN LUAR PENGHANTAR YANG BERSENTUHAN DENGAN
ISOLATOR HARUS SELALU BERSIH, UNTUK MENCEGAH
TERJADINYA KAPASITANSI, ANTARA PENGHANTAR DENGAN
PARTIKEL KOTORAN.

A3C PERLU DILINDUNGI DARI GANGGUAN


TEMPORER/POHON/BINATANG/BURUNG
1. TEKEP ISOLATOR UNTUK MENCEGAH PENGOTORAN PD
ISOLATOR TUMPU DG MENGGANTI ALUMINIUM BENDING
WIRE PD A3CS.

• ISOLATOR TUMPU TANPA


TEKEP

 PENAMPUNG
DEBU
CAPASITANSI PADA SAAT A3CS BERDEBU

PAPAN
ISOLASI DIELEKTRIK
PARTIKEL KOTORAN/DEBU PAPAN
C=εO x A
d

POTONGAN A3CS CAPASITOR


COVER TERIMINAL: ARRESTER, BUSING TRAFO & FCO
PELINDUNG GANGGUAN BINATANG
&COROSI

TEKEP
ISOLATOR BINATANG
BUSING MATI
TRAFO KESETRUM
BUSHING
DAN
Tekep
Tekep MENYEBAB
isolator
isolator KAN
FCO
FCO PENGAMAN
TRIP

TEKEP
ISOLASTOR
ARRESTER
TAMENG BINATANG
LOKASI : LOKASI : LOKASI : LOKASI :
JIMBARAN PADANG PONTIANAK MATARAM
BALI SUMBAR KALBAR NTB
TEKEP GARDU @PLN BALI SELATAN 2022
PENGARUH JARAK ARRESTER THD KEMAMPUAN
ARRESTER MENANGGULANGI TEG. PELEPASAN PETIR
20 KV  TEG KRJA ARRESTER 87 KV
JARAK +/- TKT PERLINDUNGAN (TP) = 87 X 1,1 = 95,7 KV
1,2 MTR TID = 125 KV > 95,7 KV
Ut= 125/1,3 = 96,15 kV
v = 300 m/micro scd

JARAK +/-
0,25 MTR

JARAK : 1,2 MTR du/dt = 1.143 KV/micro scd

SESUAI SPLN D5.006.2013:


JARAK : 0,25 MTR du/dt =5.490 KV/micro scd
MENINGKAT 381% (ARRESTER SEDEKAT MUNGKIN)
PENGARUH JARAK ARRESTER THD KEMAMPUAN
ARRESTER MENANGGULANGI TEG. PELEPASAN PETIR
20 KV  TEG KRJA ARRESTER 87 KV
Gardu TKT PERLINDUNGAN (TP) = 87 X 1,1 = 95,7 KV
PizzaHut TID = 125 KV > 95,7 KV
Ut= 125/1,3 = 96,15 kV
Banyuwangi v = 300 m/micro scd

JARAK +/-
2,75 MTR

JARAK +/-
0,25 MTR

JARAK : 2,75 MTR du/dt = 500 KV/micro scd

SESUAI SPLN D5.006.2013:


JARAK : 0,25 MTR du/dt =5.490 KV/micro scd
MENINGKAT 998% (ARRESTER SEDEKAT MUNGKIN)
REKOMENDASI
PEMASANGAN TEKEP ISOLATOR PADA RECLOSER
DAN JOINTING
Tekep isolator sebuah solusi

• Jaringan Lurus, belokan, ekstensi (penyambung tekep/pelindung SUTR dari pohon/


treeguard/binatang), tekep isolator: strainclamp (cocok u/ isolator keramik, kaca
maupun polymer), LLC + CCO, Fuse Cut Out, arrester, dan bushing trafo
• Ukuran : 70, 150 dan 240 mm2
• Hasil uji tegangan tembus di atas 24 KV (phasa-Netral), Polivinil cloride dg umur 10 th
lebih, tali nylon kekuatan tarik 150 daN
TEG TEMBUS (WITNESS SUCOFINDO)
(SPLN 1/1995 : 24 KV)
• YSL-70-AP : 32,3 KV • YS-CONNECTOR-70-240AP :
• YSL-150-AP : 42,7 KV 73,2 KV
• YSL-240-AP : 34,4 KV
• YS-STRAINCLAMP-70-240AP :
• YSB-70-AP : 32,3KV 73,2 KV
• YSB-150-AP : 31,3 KV
• YSB-240-AP : 40,1 KV • YS-CO-70-240AP : 52,3 KV
• YS-CO-AP : 38,01 KV
• YS-EXT-150 AP : 30,4 KV • YS-BUS-ARR--70-240AP : 60,7 KV
• YS-BUS-SEC-7-240AP : 71,58 KV
Trial and Observation

Qty
Lenght
No Name of Feeder (set) Method
(kms)
1 Kedonganan 68 100 APD
2 Wibrata 82 100 Insulator
Ties/PLP
3 Nusa Indah 63 100 Insulator Covers

The trial of the three methods is done at 20 KV distribution


network within approximately 1 km from the coast and observed
for six months.
Result of the observaton after six month

Percentage Of Number of Installing


No Method Noise feeder Time
PD Flash
outage (minute)
1 APD 7,3 5,3 2,2 3 18
2 Insulator Ties/PLP 8,1 1,3 0 8 30
3 Insulator Covers 0 0 0 0 20
PD : Partial Discharge is measuring by ultrasonic PD > 45 db
Flash : Flash emited by PD and observed visually
Noise : Noise emited by PD and observed manually
Number of trip : number of feeder outage with indicator earth fault and fault
current related to the location of the material that installed
TESTIMONI
oleh : Ondy Juanudin
Mantan Asmenjar Area
Majalaya, Jabar

Implementasi Tekep Isolator


mampu menekan gangguan
penyulang sbb :

Th. 2012 = 573 Kali/th


Th. 2013 = 407 Kali/th
Th. 2014 = 300 Kali/th
Th. 2015 = 244 Kali/th
TEKEP ISOLATOR SANGAT
BERMANFAAT
PERSIAPAN PEMASANGAN (YSL, YSB, YS-EXT)
• perhatikan dan terapkan JSA
• Pastikan penghantar sudah di stringing
• Pastikan konstruksi sdh benar (1. tidak ada pohon
menyentuh jaringan. 2. fungsi pinpost dan linepost
sebagai penumpu tidak digantung dan ditarik)
• Pastikan isolator sudah bersih dan tidak rusak (retak,
cacat, tembus, bengkok dsb)
• Gunakan perlengkapan K3
• Gunakan sarung tangan agar lemak/minyak tidak
menodai isolator.
• Alat kerja (Lap silikon, gunting seng, obeng -, tang
kombinasi dan tan potong)
• Siapkan tekep isolator lurus/belokan/extention sesuai
konstruksi
LANGKAH PEMASANGAN
TEKEP ISOLATOR LURUS

1 2 PERUBAHAN
PERTAMA:
MENEBALKAN TUTUP
& MENGANTI WARNA
PERUBAHAN KEDUA: DARI ABU-ABU JADI
MERUBAH HITAM
KONSTRUKSI DARI 1
PENGIKAT, MENJADI 2
PENGIKAT PANJANG

3 5

4
LANGKAH PEMASANGAN
TEKEP ISOLATOR BELOKAN

1 2 3
POTONG DI SINI, JIKA
TRAVERSE TANPA ADAPTOR

ADAP

4
TOR

5 6
LANGKAH PEMASANGAN TEKEP ISOLATOR EXTETION

1 2
4
3
5 6
TREEGUARD (TEKEP ISOLATOR EXTENTION)
EKOR ULAR MENYENTUH TRAVERSE
BADANNYA MELILIT KLEM
PISTOL/PENGHNATAR

EKOR MONYET
MENYENTUH
TRAVERSE
LANGKAH PEMASANGAN TEKEP ISOLATOR TARIK/ HANG
Atur posisi kabel agar
pas dengan cover

1 Pastikan
A3CS
dikupas
pada
strainclamp
2
Pada bagian ini terdapat 2 garis. Jika penghantar A3CS 75mm2 tidak perlu dipotong.
Potong pd grs ke 1 untuk A3CS 150 mm2, potong pada garis ke 2 untuk A3CS 240 mm2

Kencangkan Kencangkan
kancingan

5
kancingan

3 4
LANGKAH PEMASANGAN TEKEP ISOLATOR LLC
Atur posisi kabel agar
pas dengan cover

1
3
2 Kencangkan kancingan

Pada bagian ini


terdapat 2 garis.
Jika penghantar 4
A3CS 75mm2 tidak
perlu dipotong.
Potong pd grs ke 1
untuk A3CS 150
mm2, potong pada
5
garis ke 2 untuk
A3CS 240 mm2
Tekep Isolator Connector CCO
FINISHING

•PASTIKAN POSISI TEKEP ISOLATOR


TERPASANG DENGAN BAIK
•PASTIKAN TARIKAN SABUK PENGIKAT SUDAH
KUAT
•PASTIKAN SABUK YANG BERLEBIHAN
DIPOTONG.
•PASTIKAN TIDAK ADA GAP/JARAK ANTARA
PENGHANTAR DENGAN ISOLATOR
•BEBASKAN JARINGAN DARI JUMPER
PENGAMAN
LOKASI PANTAI LEBIH GIANYAR
NORMAL
ABNORMAL

TEKEP
TEBAKAR
& LEPAS

SEMESTINYA MENGGUNAKAN
TEKEP ISOLATOR BELOKAN,
SEDANGKAN YANG DIGUNAKAN
ADALAH TEKEP ISOLATOR LURUS
KONSTRUKSI YANG SALAH
TEKEP ISOLATOR LURUS DIPASANG JARINGAN
BERBELOK/NGENIK
KEGAGALAN TEKEP ISOLATOR
JIKA SAAT MASANG TIDAK BERSIH INILAH DAMPAKNYA
MATERIAL TEKEP GARDU YG DISIAPKAN DISET
UNTUK GARDU (Pengambilan, Arrester, cut out,
trafo) ISOLASI
LLC/CCO HEATSHRING

SCHOON
Tekep isolator : Material Pendukung :
3 bh YS-BUS-ARR-AP 3 bh LLC/CCO
3 bh YS-CO-AP (atas 15 bh Kabel schoon 70 mm2
&bawah) 15 bh Isolasi Heatsring
7 bh YS-BUS-SEC-AP 9 ptg Kabel A3CS 70 mm2
LANGKAH PEMASANGAN TEKEP ISOLATOR GARDU
untuk pelindung dr gangguan binatang&corosi
KESALAHAN PEMASANGAN TEKEP BUSHING
1. TIDAK
MENGGUNAKAN
HEATSHRING/ISOLASI
CIUT PANAS, SHG AIR
MASUK DAN
BERDAMPAK KOROSI
2. KOMPRESION DES
SEPATU KABEL
KURANG KUAT
3. BAUT TERMINAL
BUSHITNG KURANG
KERAS
KESALAHAN
KONSTRUKSI

SPACE CREAREANCE
KURANG DARI 20 CM

SOLUSI : ATUR JARAK


ARRESTER ATAU
POTONG TOPI TEKEP
ISOLATOR SETELAH
DIPASANG
REFRENSI PENGGUNAAN
TEKEP ISOLATOR
LURUS
• PLN DIST BALI : 75.947 SET
EKSTENSI
• PLN DIST JATIM : 83.653 SET • PLN DIST JATIM : 23.000 SET
• PLN DIST JABAR : 358.548 SET • PLN DIST JABAR : 157.035 SET
• PLN DIST JATENG : 53.177 SET
• PLN WIL SULSELBAR : 8.800 SET
• PLN WIL SULSELBAR : 14.150 SET
• PLN WIL SUMATRA : 77.696 SET • PLN AREA AMBON : 9.846 SET
• PLN AREA AMBON : 19.878 SET • PLN DIST JATENG : 13.000 SET
• PLN WIL NTB : 1.000 SET
TOTAL : 213.193 SET
• PLN WIL PAPUA : 9.228 SET
• PLN KALBAR : 1.298 SET
TOTAL : 696.775 SET TEKEP ISOLATOR CONNECTOR
BELOKAN
PLN WIL KALBAR : 114 SET
PLN DIST BALI : 1.643 SET
• PLN DIST JATIM : 25.520 SET TEKEP ISOLATOR STRAIN CLAMP
• PLN DIST JABAR : 121.122 SET PLN WIL KALBAR : 870 SET
• PLN DIST JATENG : 65.707 SET
PLN WIL PAPUA : 50 SET
• PLN WIL SULSELBAR : 5.835 SET
• PLN WIL PAPUA : 5.878 SET
• PLN WIL NTB : 200 SET TEKEP ISOLATOR GARDU
• PLN WIL SUMATRA : 15.942 SET
• PLN WIL KALBAR : 288 SET
PLN WIL SUMATRA : 2.155 SET
TOTAL : 242.135 SET PLN WIL KALBAR : 18 SET
KUALITAS KARYA ANAK BANGSA
7 ALASAN PILIH TEKEP ISOLATOR
1. TERLENGKAP (ONE STOP SHOPING)
2. MURAH
3. BERKUALITAS
4. PRODUKSI DALAM NEGERI
5. MENYELAMATKAN DEVISA NEGARA
6. RAMAH LINGKUNGAN KARENA DAPAT DIDAUR
ULANG
7. TELAH TERBUKTI KINERJANYA
TEKEP ISOLATOR LURUS (Type : YSL-……AP)
3 SET
TEKEP ISOLATOR BELOKAN (Type : YSB-……AP)
3 SET
TEKEP BELOKAN (Type : YSB-…….AP)
6 SET
Tekep Isolator Belokan (Type : YSB-…….-AP) 1 set/isolator tumpu
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP) 1 set/isolator tarik
Tekep Isolator Belokan (YSB-…….AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP)
Tekep Isolator Bushing Trafo/Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP)
Tekep Isolator Bushing Trafo/Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP)
Tekep Isolator Belokan (YSB-……AP)
Tekep Isolator Bushing Trafo Primer&sekunder (YS-Bus-Sec-AP)
Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP)
Tekep Isolator Lurus (YSL-……AP)
Tekep Isolator LLC (YS-Connector-70-240AP)
Tekep Isolator FCO (YS-CO-70-240AP)
Tekep Isolator Bushing Trafo/Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP)
Tekep Isolator Belokan (YSB-……AP)
Tekep Isolator Lurus (YSL-……AP)
Tekep Isolator LLC (YS-Connector-70-240AP)
Tekep Isolator FCO (YS-CO-70-240AP)

YS-CO-AP
Tekep Isolator Bushing Trafo/Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP)
Tekep Isolator Belokan (YSB-……AP)
Tekep Isolator LLC (YS-Connector-70-240AP)
Tekep Isolator FCO (YS-CO-70-240AP)
Tekep Isolator Bushing Trafo/Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP) Tekep
Tekep Isolator Belokan (YSB-……AP)
Tekep Isolator LLC (YS-Connector-70-240AP) YSL-…..AP
Tekep Isolator FCO (YS-CO-70-240AP)

Tekep
YSB-…AP

YS-
CONNECTOR-
AP
YS-BUS-SEC-
YS-CO-AP
YS-BUS-ARR-AP
Tekep Isolator Bushing Trafo/Arrester (YS-Bus-ARR-AP)
Tekep Isolator straincalamp (YS-Strinclamp-70-240 AP) Tekep
Tekep Isolator Belokan (YSB-……AP)
Tekep Isolator LLC (YS-Connector-70-240AP) YSB-…..AP
Tekep Isolator FCO (YS-CO-70-240AP)

YS-
CONNECTOR-
AP
YS-BUS-SEC-
YS-CO-AP
YS-BUS-ARR-AP AP