SOAL 1

Kolom built-up simetri tunggal

1. Hitung properti geometri penmapang profil-I simetri tunggal


No b t A yi A*yi Io A(yi-yt)^2
1 350 19 6650 9.5 63175 200054.17 59936308.2839
2 8 250 2000 144 288000 10416667 3130508.01154
3 200 16 3200 277 886400 68266.667 95289886.2362
total 285 11850 1237575 10684988 158356703

yt = 104.4 mm
yb =
Ix = 159594277.5316 mm4
Iy = 78562750 mm4
rx = 116.1 mm
ry = 81.4 mm
d' = 267.5 mm
j = 1118936.666667 mm4
a = 0.864
yo = -134.7 mm
Cw = 659621915749 mm6
Ix + I y = 238157028

2. Menentukan Klasifikasi Penampang


sayap atas = 9.211 << 15 (tidak langsing)
sayap bawah = 6.25 << 15 (tidak langsing)
badan = 31.250 << 42 (tidak langsing)

3. Tegangan kritis tekuk-lentur (AISC-E3)


KL/rx = 51.7 << 133.2 (tekuk inelastis)
Fe = 737.7 Mpa
Fy / Fe = 0.339
Fcr = 0.868 Fy Mpa

4. tekuk lentur-puntir profil sumbu simetri tunggal (AISC-E4)


KL/ry = 73.7 << 133
Fey = 363.1 Mpa
ro 2
= 38252.3
Fez = 270 MPa
H = 0.525
Fe = 182.6 MPa
Fy / Fe = 1.37 << 2.25 (tekuk inelastis)
Fcr = 0.56 Fy Mpa

5. kuat tekan nominal kolom


Fcr tekuk lentur-puntir << Fcr tekuk lentur maka tekuk yang terjadi adalah lentur-puntir
Pn = 1670.3 kN
0Pn = 1503.3 kN

6. Berdasarkan hitungan analisa struktur yang telah dibuat dapat diketahui bahwa:
Pmax = 626.4 kN
ket
Fy = 250 Mpa
E = 200000
Kc = 0.72
KL = 6000
phi = 3.14
G = 77200
xo = 0
L = 6000 mm
K = 1
SOAL 2
KOLOM SIKU GANDA

Kolom Ac : profil siku L 90 x 90 x 9


t r1 r2 A q Cx=Cy Ix=Iy Imax Imin
mm mm mm cm2 kg/m cm cm4 cm4 cm4
9 11 5.5 15.5 12.2 2.07 116 184 47.8

Kolom AB : Profil WF 250 x 125 x 7 x 11


Dimension (mm) A q Ix Iy
H B t1 t2 r cm2 kg/m cm4 cm4
250 175 7 11 16 56.24 44.1 6120 984

Tinjau batang AB, profil WF 250 x 125 x 6 x 9 dengan KL = 3,5 m

1. Hitung properti geometri penampang profil-H


A= 5624 m2
Ix = 61,200,000 mm4
rx = 104 mm
Iy = 9,840,000 mm4
ry = 41.8 mm
J= 182609 mm4
Cw = 140517660000 mm6
Ix+Iy = 71,040,000 mm4

2. Menentukan klasifikasi penampang berdasarkan tabel 5.1


sayap = 8.0 < 15.8 (tidak langsing)
badan = 32.6 < 42 (tidak langsing)

klasifikasi profil I adalah penampang tidak langsing,


ditinjau tekuk-lentur (AISC -E3) dan tekuk puntir (AISC-E4)

3. Tegangan kritis tekuk lentur


KL/rmin = 83.7 < 133 (tekuk inelastis)
Fe = 281.3 Mpa
Fy / Fe = 0.89
Fcr = 0.7 Fy
4. Tegangan kritis tekuk-puntir (AISC-E4)
Fe = 516.8
Kolom jepit-jepit maka dapat di anggap KzL = KL sehi
Fy / Fe = 0.484 < 2.25 (tekuk inelastik)
Fcr = 0.82 Fy

5. Kuat tekan nominal kolom profil H


Fcr tekuk puntir > Fcr tekuk lentur, maka tekuk yang terjadi adalah tekuk lentur. Kuat tekan nominalnya adalah

Pn = 969.2 kN
Pmax(AB) = 1454.09 kN

Tinjau struktur keseluruhan


Dari tinjauan kuat batang AB dan AC maka sistem dite
tercapai terlebih dahulu.
Pu max = Pmax(AC)= 365.7936 kN
keterangan
rx=ry rmax rmin Sx=Sy E= 200000 Mpa
cm cm cm cm 3 Fy = 250 MPa
2.74 3.45 11.76 18 KL = 3500 mm
phi = 3.14
G= 77200
rx ry Sx Sy
cm cm cm3 cm3
10.4 4.18 502 113

Tinjau batang AC profil 2L90x90x9 dengan KL = 3,5 m

1. profil siku L90x90x9


t r1 r2 A q Cx=Cy Ix=Iy Imax Imin
mm mm mm cm2 kg/m cm cm4 cm4 cm4
9 11 5.5 15.5 12.2 2.07 116 184 47.8

2. profil siku ganda dianggap sebagai satu kesatuan


Ag = 2A = 3100 mm
2

Igx = 2Ix = 2320000 mm


4

Igy = 2Iy + 2A(20,7 + 10/2)2 = 4367519 mm


4
pelat = 10 mm
rgx = (Igx / Ag)1/2 = 27.4 mm
rgy = (Igy / Ag)1/2 = 37.5 mm
karena, KLx = KLy maka KLmin = KL/rmin = 127.9 < 133 (tekuk lentur)

3. Tegangan kritis tekuk-lentur (AISC-E3)


KL/rmin= 127.9396 < 133 (tekuk inelastik)
Fe = 120.4702 Mpa
Fy / Fe = 2.075
Fcr = 0.420 Fy

4. kuat tekan nominal kolom profil gabungan adalah


Pn = 325.1 kN
Pmax(AC)= 365.8 kN < Pmax(AB) = 1454.09 kN
minalnya adalah

an AC maka sistem ditentukan oleh kuat batang AC yang kapasitasnya akan


rx=ry rmax rmin Sx=Sy
cm cm cm cm3
2.74 3.45 11.76 18

(tekuk lentur)
SOAL 3

PENGARUH PEMILIHAN PROFIL DAN BRACING


Kapasitas dukung sistem struktur pada soal 2 ditentukan oleh persyaratan stabilitas
Dengan tegangan kritis Fcr batang AC adalah 0,7Fy dan batang AB adalah 0,82Fy

Perencanaan pemasangan bracing(pertambatan)


1. batang AB dengan profil WF 250 x 175 x 7 x 11
Dimension (mm) A q Ix Iy
H B t1 t2 r cm2 kg/m cm4 cm4
250 175 7 11 16 56.24 44.1 6120 984

A= 5624 mm2
Ix = 61200000 mm4
Iy = 9840000 mm4
rx = 104 mm
ry = 41.8 mm
KLx/rx = 33.7
KLy/ry = 41.8
Klymin = (KLx/rx ) x ry = 1406.7 mm

2. Batang AC dengan profil 2Lx90x90x9


t r1 r2 A q Cx=Cy Ix=Iy Imax Imin
mm mm mm cm2 kg/m cm cm4 cm4 cm4
9 11 5.5 15.5 12.2 2.07 116 184 47.8

Ag = 2A = 3100 mm2
Igx = 2Ix = 2320000 mm4
Igy = 2Iy + 2A(20,7 + 10/2)2 = 4367519 mm
4
pelat = 10 mm
rgx = (Igx / Ag) =
1/2
27.4 mm
rgy = (Igy / Ag)1/2 = 37.5 mm
karena, KLx = KLy maka KLmin = KL/rmin = 27.4 < 133 (tekuk lentur)
KLy / ry = 93.2
KLx / rx = 127.9
Klrmin = (KLy / ry)*rx = 2550.9 mm

Tinjau batang AC , profil 2L90x90x9


1. profil siku L 90 x 90 x 9
t r1 r2 A q Cx=Cy Ix=Iy Imax Imin
mm mm mm cm2 kg/m cm cm4 cm4 cm4
9 11 5.5 15.5 12.2 2.07 116 184 47.8

2. Profil siku ganda dianggap sebagai satu kesatuan


Ag = 2A = 3100 mm2
Igx = 2Ix = 2320000 mm4
Igy = 2Iy + 2A(20,7 + 10/2)2 = 4367519 mm
4
pelat = 10 mm
rgx = (Igx / Ag) 1/2
= 27.4 mm (rmin)
rgy = (Igy / Ag) 37.5 mm
1/2
=
arah sumbu y-y tidak di pengaruhi bracing maka KL= 3500.0 mm
KLy / ry = 93.2
arah sumbu x-x di perpendek oleh bracing maka KL = 1750 mm
KLx / rx = 64.0

3. sumbu x-x : tekuk-lentur (AISC E3)


KLx / rx = 64.0 << 133 (tekuk inelastik)
Fe = 481.9
Fy / Fe = 0.519
Fcr = 0.805 Fy = 201.20348

4. sumbu y-y : profil gabungan dan tekuk lentur-torsi (AISC-E4)


3/4( KLy / rgy ) = 69.9 >> 32.0

5. cek pengaruh kekakuan profil gabungan akibat sambungan pelat kopel.


untuk a / ri < 40
(KL/r)m = 93.2

6. Tegangan kritis tekuk-puntir (AISC-E4)


(KL/r)m = 98.6 << 133 (tekuk inelastis)
Fe = 202.9 Mpa
Fy / Fe = 1.232
Fcr = 0.597 Fy
Fcry = Fcr = 0.597 Fy = 149.3 Mpa
Ix+Iy / Ag = 2157.3
r 0
2
= 2419.7
83106 mm
4
J =
Fcrz = 855.3 MPa
H = 0.892
Fcr = 146.02
7. Kuat tekan nominal
Fcr tekuk lentur puntir << Fcr tekuk lentur , maka tekuk yang terjadi adalah tekuk lentur puntir

Pn = 452.6 kN
Pmax(AC) = 509.2 kN
keterangan
KL = 3.5 m 3500
E = 200000
rx ry Sx Sy Fy = 250 Mpa
cm cm cm 3
cm 3

10.4 4.18 502 113

rx=ry rmax rmin Sx=Sy b b


cm cm cm cm3 mm mm
2.74 3.45 11.76 18 90 90

(tekuk lentur)
rx=ry rmax rmin Sx=Sy b b
cm cm cm cm3 mm mm
2.74 3.45 11.76 18 90 90

keterangan
a = 875 mm
G = 77200 Mpa
phi = 3.14
x0 = 0
y0 = 16.2
mm
SOAL 4
Kolom built-up - elemen langsing

1. Hitung properti geometri penmapang profil-I simetri tunggal


No b t A yi A*yi Io A(yi-yt)^2
1 450 9 4050 4.5 18225 27337.5 46217244.898
2 6 200 1200 109 130800 4000000 6488.96
3 350 12 4200 215 903000 50400 45143378.042
total 221 9450 1052025 4077737.5 91367111.905

yt = 111.3 mm
yb =
Ix = 92419137 mm4
Iy = 111222350 mm4
rx = 98.9 mm
ry = 108.5 mm
d' = 210.5 mm
j = 326106 mm4
a = 0.614
yo = -24.0 mm
Cw = 1167425373885 mm6
Ix + I y = 203641487 mm4

2. Menentukan Klasifikasi Penampang


sayap atas = 25 << 15 (langsing)
sayap bawah = 14.6 << 15 (tidak langsing)
badan = 33.3 << 42 (tidak langsing)

3. untuk elemen pelat sayap kolom built-up


15 < 25 < 28
maka,
Qs = 0.72
Qa = 1
Q = 0.72

4. tegangan kritis tekuk lentur (AISC-E3)


KL/rx = 60.7 << 156.5 (tekuk inelastis)
Fe = 535.7 Mpa
QFy / Fe = 0.338
Fcr = 0.63 Fy Mpa

5. tekuk torsi-lentur profil sumbu simetri tunggal (AISC-E4)


KL/ry = 55.3 << 133
Fey = 644.7 Mpa
ro 2 = 22126.6
Fez = 426 MPa
H = 0.97
Fe = 407.9 MPa
QFy / Fe = 0.44 << 2.25 (tekuk inelastis)
Fcr = 0.60 Fy Mpa

6. kuat tekan nominal


Fcr tekuk torsi-lentur << Fcr tekuk lentur maka tekuk yang terjadi adalah torsi-lentur

Pn = 1421.7 kN
0Pn = 1279.6 kN ± 122% dari kolom tidak langsing
ket
Fy = 250
E = 200000
Kc = 0.7
KL = 6000
K = 1
L = 6000 mm
phi = 3.14
G = 77200
xo = 0
=
SOAL 5
Kantilever

Kantilever WF 500x200x10x16
Bentang = 7,5 m

1. pemodelan struktur dan beban serta gaya gaya internal


qu = 5 kN/m
Pu = 20 kN Pu = 20 kN Pu = 10 kN

Notasi
d x bf
1.5 2.5 3.5 600 x 200

10
27.5 Segmen 1
87.5

200 65.625
325.625
Segmen 2

Segmen 3
Notasi d x bf x t w x t f Berat Zx ᵩMp ᵩMr BF LP
kg/m mm kg/m cm3 kNm kNm kN m
103 H600x200x11x17 103 2.863 618 375 56.1 2.1
92 H596x199x10x15 92.4 2.535 548 332 52.3 2.1

Mu = 325.625
ᵩMn = ᵩMp = 618
R1 = Mu/ᵩMn = 0.527
Vu = 87.5
ᵩVn = 950

Mu = 200
ᵩMn = 595.56
R2 = 0.336 < 1

Mu = 65.625
ᵩMn = 539.46
R3 = 0.122 < 1
Lr Ix ᵩVn
m cm4 kN
6.5 75600 950
6.2 66600 858

ket
Cb = 1
SOAL 6

Balok I gilas: UB 1020x 304x26x46


Bentang = 15m
Fy = 240 Mpa

Pu

4m 2m 2m 4m
Notasi d x bf x t w x t f Berat Zx ᵩMp ᵩMr BF
d x bf kg/m mm kg/m cm3 kNm kNm kN
200x200 50 H200x200x8x12 49.9 513 111 70 5

ᵩMp = ᵩZx x Fy = 110.808


Karena Lp 2.6 < Lb 4< Lr
ᵩMn = 113.15 > ᵩMp
jadi Mu = ᵩMn = ᵩMp = 110.808
Karena Mmax = 1/4 PL sedangkan Mmax = Mu
maka P=Pu dimana Pu = 4Mu/L
Pu = 29.5488
Karena Vu =ᵩVn = 230 > Pu
LP Lr Ix ᵩVn
m m cm4 kN ket
2.6 10.9 4720 230 Fy = 240
Cb = 1.09
L = 15
=
10.9 , maka: