Anda di halaman 1dari 10

LAPORAN PERAWATAN TRAFO

Customer : UNIVERSITAS MUHAMMADIYAH GRESIK

Alamat : GRESIK

Data Transformator I

1. Lokasi : UNMUH GRESIK (Gedung Baru) 5. Tegangan : 20000V / 400V


2. Merk : Trafindo 6. Tahun : 2016
3. Daya : 630kVA 7. Volume Oli : 395 Kg
4. No Seri : 163300450 8. Berat Total :

Data Pengecekan Fisik Trafo

No Point Pengecekan Sebelum Sesudah Keterangan

1 Bushing + Isolator Primer Packing Rembes Baik Ganti Packing


2 Bushing + Isolator Sekunder Packing Rembes Baik Ganti Packing
3 Packing Bak Trafo Baik Baik
4 Packing DGPT Baik Baik
5 Indikator Level Oli Baik Baik
6 Indikator Temperatur Baik Baik

Data Pengetesan Minyak Trafo

No Point Pengetesan Standart Hasil

1 Warna Menurut Kartu Maks No. 5 2


Warna Menurut Min HC (Hampir
2 HC
Callophane Cukup)
Rata –
Tegangan Tembus 1 2 3 4 5 6 rata
4 Min 30kV / 2.5mm (kV)
Sebelum
33,7 32,3 39,2 31,2 39,2 33,5 34,8
Rata –
Tegangan Tembus 1 2 3 4 5 6 rata
5 Min 30kV / 2.5mm (kV)
Sesudah
60,7 60,6 61,0 60,9 61,0 61,0 60,8
1. Oli Trafo setelah di purifikasi tegangan tembusnya diatas standart
6 Keterangan
jadi trafo layak untuk di energize.
Data Pengetesan Tahanan Isolasi Trafo

Trafo Nilai Uji HV – G HV – G HV – LV


(V) (GΩ) (GΩ) (GΩ)

Trafo Gedung Baru 5000 7,8 GΩ 1,49 GΩ 1,06

Keterangan : Nilai Tahanan Isolasi Trafo sudah bagus, trafo layak untuk di
energize
Data Transformator II

1. Lokasi : UNMUH GRESIK (Gedung Lama) 5. Tegangan : 20000V / 400V


2. Merk : Trafindo 6. Tahun : 2016
3. Daya : 315kVA 7. Volume Oli :
4. No Seri : 130024 8. Berat Total :

Data Pengecekan Fisik Trafo

No Point Pengecekan Sebelum Sesudah Keterangan

1 Bushing + Isolator Primer Baik Baik


2 Bushing + Isolator Sekunder Baik Baik
3 Packing Bak Trafo Baik Baik
4 Packing DGPT NA NA
5 Indikator Level Oli Baik Baik
6 Indikator Temperatur Baik Baik

Data Pengetesan Minyak Trafo

No Point Pengetesan Standart Hasil

1 Warna Menurut Kartu Maks No. 5 2


Warna Menurut Min HC (Hampir
2 HC
Callophane Cukup)
Rata –
Tegangan Tembus 1 2 3 4 5 6 rata
4 Min 30kV / 2.5mm (kV)
Sebelum
31,8 41,3 40,8 41,2 41,2 41,3 39,6
Rata –
Tegangan Tembus 1 2 3 4 5 6 rata
5 Min 30kV / 2.5mm (kV)
Sesudah
60,9 60,8 60,8 60,8 60,8 60,8 60,8
1. Oli Trafo setelah di purifikasi tegangan tembusnya diatas standart
6 Keterangan
jadi trafo layak untuk di energize.
Data Pengetesan Tahanan Isolasi Trafo

Trafo Nilai Uji HV – G HV – G HV – LV


(V) (GΩ) (GΩ) (GΩ)

Trafo Gedung Baru 5000 9,41 GΩ 9,57 GΩ 11

Keterangan : Nilai Tahanan Isolasi Trafo sudah bagus, trafo layak untuk di
energize
LAPORAN PERAWATAN KUBIKEL & LVMDP

Customer : UNIVERSITAS MUHAMMADIYAH GRESIK

Alamat : GRESIK

A. Data Peralatan

INCOMING (DM1A), TRAFO PROTECTION 500kVA (QM), TRAFO PROTECTION 315kVA (QM)

MERK KUBIKEL SCHNEIDER MERK RELAY SEPAM 40

QM (2 Unit) & DM1-A


TYPE KUBIKEL MERK METER NA
(1 Unit)

MERK LBS SCHNEIDER MERK CT TRAFOINDO

MERK CB SCHNEIDER MERK VT TRAFOINDO

TYPE CB FIX TYPE RATIO CT 15-30/5-5

MEDIA CB + LBS SF-6 RATIO VT 20000/v3 / 100/v3

SUMBER MOTOR
220 VAC CLASS CT 0.5, 5P20
CB

MERK FUSE SCHNEIDER CLASS VT 3P

B. Cleaning

KONDISI
No KOMPONEN KONDISI AWAL
AKHIR

1. Kubikel Berdebu Bersih

2. Load Breaker Switch Berdebu Bersih

Vacuum Circuit
3. Berdebu Bersih
Breaker

4. Main Busbar Berdebu Bersih

5. CT & VT Berdebu Bersih

6. Fuse Berdebu Bersih


7. Isolator Berdebu Bersih

C. Tes Fungsi & Kelayakan Komponen

No KOMPONEN ITEM PENGECEKAN HASIL PENGECEKAN KETERANGAN

OPEN Baik
Load Breaker
1.
Switch CLOSE Baik

OPEN Baik
2. Circuit Breaker Motorized OK
CLOSE Baik

OPEN Baik
3. Earthing Switch
CLOSE Baik

4. Metering FUNGSI PENGUKURAN NA

5. Busbar KELAYAKAN BUSBAR Baik

6. Protection Relay FUNGSI PROTEKSI Baik

7. HRC Fuse KELAYAKAN FUSE Baik

Torsi 28NM
Kekencangan Baut (Main Busbar)
8. KEKENCANGAN BAUT Baik
Contact dan 50NM
(Power Cable)
Heater di
kubikel trafo
9. Heater KELAYAKAN HEATER Baik
500kVA sudah
diganti baru

10. Isolator Devider FUNGSI ISOLATOR Baik


D. Pengujian dan Pengukuran

1. Busbar

a.1. PengukuranTahananIsolasi

Merk : KYORITSU

Type : 3125A

a.2. Hasilukur

Tegangan
Standart R–S S–T R–T R – Gnd S - Gnd T- Gnd
Pengetesan
(MΩ) (GΩ) (GΩ) (GΩ) (GΩ) (GΩ) (GΩ)
(VDC)

5000 >100MΩ 856 825 865 635 555 711

* Kubikel dalam kondisi Baik

2.Kabel HVTrafo 500kVA

a.1. PengukuranTahananIsolasi

Merk : KYORITSU

Type : 3125A

a.2. Hasilukur

Tegangan
Standart R – Gnd S - Gnd T- Gnd
Pengetesan
(MΩ) (GΩ) (GΩ) (GΩ)
(VDC)

5000 >100MΩ 43 126 102

* Kabel HV dalam kondisi Baik


3 .Kabel HVTrafo 315kVA

a.1. PengukuranTahananIsolasi

Merk : KYORITSU

Type : 3125A

a.2. Hasilukur

Tegangan
Standart R – Gnd S - Gnd T- Gnd
Pengetesan
(MΩ) (GΩ) (GΩ) (GΩ)
(VDC)

5000 >100MΩ 214 265 246

* Kabel HV dalam kondisi Baik


Galery Foto Pekerjaan

(Maintenance Trafo 500kVA ) (Maintenance Trafo 500kVA )

(Maintenance Trafo 315kVA) (Maintenance Trafo 315kVA )


(Maintenance Kubikel) (Maintenance Kubikel)

(Maintenance LVMDP) (Maintenance LVMDP)

Sidoarjo, 07 Februari 2022

PT. WISMATATA ELTRA PERKASA

EWIN WALUYO
Project Coordinator

Anda mungkin juga menyukai